Planning for 6954 and 6953 racks

Hardware specifications provide detailed information for your rack. This includes dimensions, electrical, power, temperature, environment, and service clearances.

The 6954 base rack is an optional second-base frame with a separate connection to AC power that is designed for use with model 9119-FHB. A complete set of planning information is provided to address the resulting system.

Table 1. 6954 base rack components
Feature code Description
6868 Slimline doors for expansion rack
6888 Acoustic doors for expansion rack
6878 Acoustic doors for bolt on expansion rack
6880 Slimline doors for bolt on expansion rack
Notes:
  1. A Hardware Management Console (HMC) can connect to multiple systems (therefore, a Hardware Management Console might not need to be ordered), or up to two HMCs can connect to the system for redundancy.
  2. A maximum of 32 I/O drawers can be connected to the 9119-FHB rack using two FC 6954 and 6953. Typically, I/O drawers are populated in the server frame first.
Table 2. Full system weights (no doors)
Physical characteristics Weight
Powered I/O rack 1275 kg (2810 lb)
Powered I/O rack and expansion rack 2341 kg (5160 lb)
Table 3. Cover weights
Physical characteristics Weight
One acoustic door 25 kg (56 lb)
One non-acoustic door 15 kg (33 lb)
Table 4. Dimensions and weight
Physical characteristics Slim Line Acoustic
Number of frames One frame Two frame One frame Two frame
Height 2014 mm (79.3 in) 2014 mm (79.3 in) 2014 mm (79.3 in) 2014 mm (79.3 in)
Width 775 mm (30.5 in) 1567.18 mm (61.7 in.) 775 mm (30.5 in) 1567.18 mm (61.7 in.)
Depth 1485.9 mm (58.5 in.) 1485.9 mm (58.5 in.) 1805.94 mm (71.1 in.) 1805.94 mm (71.1 in.)
Table 5. Maximum rack weights
Physical characteristics Weight
Powered I/O rack 1388 kg (3060 lb)
Powered I/O rack and bolt on expansion rack 2567 kg (5660 lb)
Table 6. Powered I/O rack without the internal battery feature
I/O drawers Weight
1 571 kg (1258 lb)
2 668 kg (1473 lb)
3 766 kg (1688 lb)
4 863 kg (1903 lb)
5 986 kg (2174 lb)
6 1084 kg (2389 lb)
7 1181 kg (2604 lb)
8 1279 kg (2819 lb)
Table 7. Powered I/O rack with bolt on expansion rack, without the internal battery feature
I/O drawers Weight
9 1750 kg (3858 lb)
10 1847 kg (4073 lb)
11 1945 kg (4288 lb)
12 2068 kg (4559 lb)
13 2165 kg (4774 lb)
14 2263 kg (4989 lb)
15 2360 kg (5204 lb)
16 2458 kg (5419 lb)
Table 8. Powered I/O rack with the internal battery feature
I/O drawers Weight
1 777 kg (1712 lb)
2 874 kg (1927 lb)
3 972 kg (2142 lb)
4 1095 kg (2413 lb)
5 1192 kg (2628 lb)
6 1290 kg (2843 lb)
7 1387 kg (3058 lb)
Table 9. Powered I/O rack with bolt on expansion rack, with the internal battery feature
I/O drawers Weight
8 1858 kg (4097 lb)
9 1956 kg (4312 lb)
10 2053 kg (4527 lb)
11 2176 kg (4798 lb)
12 2274 kg (5013 lb)
13 2371 kg (5228 lb)
14 2469 kg (5443 lb)
15 2566 kg (5658 lb)
Table 10. Shipping dimension and weight per rack
Physical characteristics Dimensions
Height 231 cm (91 in.)
Width 94 cm (37 in.)
Depth 162 cm (63.5 in.)
Weight 1134 kg (2500 lb)
Table 11. System Rating (POWER7 I/O rack new build)
  US, Canada, Japan US High Voltage World Trade Corporation World Trade Corporation
Voltage and frequency 200 - 240 V ac at 50 - 60 Hz 480 V ac at 50 - 60 Hz 200 - 240 V ac at 50 - 60 Hz 380 - 415 V ac at 50 - 60 Hz
System rating for the I/O rack 48 A 63 A 22 A 25.6 A 48 A 63 A 25.6 A 32 A
Note:

The system rating varies by configuration. See Electrical requirements for which system configurations will have the higher rating.

Table 12. System Rating (POWER7 I/O rack upgrade from a POWER6 I/O rack)
  US, Canada, Japan US High Voltage World Trade Corporation World Trade Corporation
Voltage and frequency 200 - 240 V ac at 50 - 60 Hz 480 V ac at 50 - 60 Hz 200 - 240 V ac at 50 - 60 Hz 380 - 415 V ac at 50 - 60 Hz
System rating for the I/O rack 48 A 63 A 24 A 24 A 48 A 63 A 34 A 34 A
Note:

The system rating varies by configuration. See Electrical requirements for which system configurations will have the higher rating.

Table 13. Electrical and thermal characteristics
Electrical and thermal characteristics Properties
Maximum power for a single fully configured powered I/O rack (FC 6954) 11.6 kW
Maximum power for a single fully configured powered I/O rack (FC 6954) and a single fully configured non powered I/O rack (FC 6953) 23.1 kW
Thermal output for a single fully configured powered I/O rack (FC 6954) 39.5 kBTU/hr
Thermal output power for a single fully configured powered I/O rack (FC 6954) and a single fully configured non powered I/O rack (FC 6953) 78.8 kBTU/hr
Table 14. Environment specifications
Environment Operating Storage Shipping
Temperature 50 - 80.6°F (10 - 27°C) 1 33.8 - 140°F (1 - 60°C) -40 - 140°F (-40 - 60°C)
Relative humidity 20 - 80% 5 - 80% 5 - 100%
Maximum altitude 3048 m (10 000 ft)
1 Derate maximum temperature 2°C per 1000 ft over 7000 ft
Table 15. Declared acoustical noise emissions for powered I/O rack for the 9119-FHB
Product Configuration Declared A-Weighted Sound Power Level, LWAd (B) Declared A-Weighted Sound Pressure Level, LpAm (dB)
Operating Idling Operating Idling
Single I/O drawer alone in rack with acoustical door set. Blowers at nominal speeds. 7.0 7.0 52 52
Single I/O drawer alone in rack with nonacoustical (slimline) door set. Blowers at nominal speeds. 7.5 7.5 59 59
Bulk power assembly alone in rack with acoustical door set. Blowers at nominal speeds. 6.9 6.9 52 52
Bulk power assembly alone in rack with 7.5 7.5 59 59
Non-Acoustical (Slimline) Door Set. Blowers at nominal speeds.
Typical configuration of powered I/O rack with acoustical door set: 4 I/O drawers and bulk power assembly. Blowers at nominal speeds. 7.75 7.75 59 59
Typical configuration of powered I/O rack with nonacoustical (slimline) Door set: 4 I/O drawers and bulk power assembly. Blowers at nominal speeds. 8.2 8.2 66 66
Maximum configuration of powered I/O rack with acoustical doorset: 8 I/O drawers and bulk power assembly. Blowers at nominal speeds. 7.94 7.94 61 61
Maximum configuration of powered I/O rack with nonacoustical (slimline) door set: 8 I/O drawers and bulk power assembly. Blowers at nominal speeds. 8.4 8.4 68 68

1Declared level LWAd is the upper-limit A-weighted sound power level. Declared level LpAm is the mean A-weighted sound pressure level measured at the 1-meter bystander positions.

2All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.

3B, dB, abbreviations for bels and decibels, respectively, where 1 B = 10 dB.

4Meets IT Product Noise Limits for, Generally Unattended Data Center, per Statskontoret Technical Standard 26:6.

5Meets IT Product Noise Limits for, Generally Attended Data Center, per Statskontoret Technical Standard 26:6.

Front-service access is necessary on the 6954 to accommodate a lift tool for the servicing of large drawers (I/O drawers). Front and rear service access is necessary to accommodate the lift tool for servicing of the optional integrated battery backup.

Figure 1. Floor plan considerations for single units
Floor plan considerations for single units