Planning for 6954 and 6953 racks
Hardware specifications provide detailed information for your rack. This includes dimensions, electrical, power, temperature, environment, and service clearances.
The 6954 base rack is an optional second-base frame with a separate connection to AC power that is designed for use with model 9119-FHB. A complete set of planning information is provided to address the resulting system.
| Feature code | Description |
|---|---|
| 6868 | Slimline doors for expansion rack |
| 6888 | Acoustic doors for expansion rack |
| 6878 | Acoustic doors for bolt on expansion rack |
| 6880 | Slimline doors for bolt on expansion rack |
| Notes:
|
|
| Physical characteristics | Weight |
|---|---|
| Powered I/O rack | 1275 kg (2810 lb) |
| Powered I/O rack and expansion rack | 2341 kg (5160 lb) |
| Physical characteristics | Weight |
|---|---|
| One acoustic door | 25 kg (56 lb) |
| One non-acoustic door | 15 kg (33 lb) |
| Physical characteristics | Slim Line | Acoustic | ||
|---|---|---|---|---|
| Number of frames | One frame | Two frame | One frame | Two frame |
| Height | 2014 mm (79.3 in) | 2014 mm (79.3 in) | 2014 mm (79.3 in) | 2014 mm (79.3 in) |
| Width | 775 mm (30.5 in) | 1567.18 mm (61.7 in.) | 775 mm (30.5 in) | 1567.18 mm (61.7 in.) |
| Depth | 1485.9 mm (58.5 in.) | 1485.9 mm (58.5 in.) | 1805.94 mm (71.1 in.) | 1805.94 mm (71.1 in.) |
| Physical characteristics | Weight |
|---|---|
| Powered I/O rack | 1388 kg (3060 lb) |
| Powered I/O rack and bolt on expansion rack | 2567 kg (5660 lb) |
| I/O drawers | Weight |
|---|---|
| 1 | 571 kg (1258 lb) |
| 2 | 668 kg (1473 lb) |
| 3 | 766 kg (1688 lb) |
| 4 | 863 kg (1903 lb) |
| 5 | 986 kg (2174 lb) |
| 6 | 1084 kg (2389 lb) |
| 7 | 1181 kg (2604 lb) |
| 8 | 1279 kg (2819 lb) |
| I/O drawers | Weight |
|---|---|
| 9 | 1750 kg (3858 lb) |
| 10 | 1847 kg (4073 lb) |
| 11 | 1945 kg (4288 lb) |
| 12 | 2068 kg (4559 lb) |
| 13 | 2165 kg (4774 lb) |
| 14 | 2263 kg (4989 lb) |
| 15 | 2360 kg (5204 lb) |
| 16 | 2458 kg (5419 lb) |
| I/O drawers | Weight |
|---|---|
| 1 | 777 kg (1712 lb) |
| 2 | 874 kg (1927 lb) |
| 3 | 972 kg (2142 lb) |
| 4 | 1095 kg (2413 lb) |
| 5 | 1192 kg (2628 lb) |
| 6 | 1290 kg (2843 lb) |
| 7 | 1387 kg (3058 lb) |
| I/O drawers | Weight |
|---|---|
| 8 | 1858 kg (4097 lb) |
| 9 | 1956 kg (4312 lb) |
| 10 | 2053 kg (4527 lb) |
| 11 | 2176 kg (4798 lb) |
| 12 | 2274 kg (5013 lb) |
| 13 | 2371 kg (5228 lb) |
| 14 | 2469 kg (5443 lb) |
| 15 | 2566 kg (5658 lb) |
| Physical characteristics | Dimensions |
|---|---|
| Height | 231 cm (91 in.) |
| Width | 94 cm (37 in.) |
| Depth | 162 cm (63.5 in.) |
| Weight | 1134 kg (2500 lb) |
| US, Canada, Japan | US High Voltage | World Trade Corporation | World Trade Corporation | |||||
|---|---|---|---|---|---|---|---|---|
| Voltage and frequency | 200 - 240 V ac at 50 - 60 Hz | 480 V ac at 50 - 60 Hz | 200 - 240 V ac at 50 - 60 Hz | 380 - 415 V ac at 50 - 60 Hz | ||||
| System rating for the I/O rack | 48 A | 63 A | 22 A | 25.6 A | 48 A | 63 A | 25.6 A | 32 A |
Note:
The system rating varies by configuration. See Electrical requirements for which system configurations will have the higher rating. |
||||||||
| US, Canada, Japan | US High Voltage | World Trade Corporation | World Trade Corporation | |||||
|---|---|---|---|---|---|---|---|---|
| Voltage and frequency | 200 - 240 V ac at 50 - 60 Hz | 480 V ac at 50 - 60 Hz | 200 - 240 V ac at 50 - 60 Hz | 380 - 415 V ac at 50 - 60 Hz | ||||
| System rating for the I/O rack | 48 A | 63 A | 24 A | 24 A | 48 A | 63 A | 34 A | 34 A |
Note:
The system rating varies by configuration. See Electrical requirements for which system configurations will have the higher rating. |
||||||||
| Electrical and thermal characteristics | Properties |
|---|---|
| Maximum power for a single fully configured powered I/O rack (FC 6954) | 11.6 kW |
| Maximum power for a single fully configured powered I/O rack (FC 6954) and a single fully configured non powered I/O rack (FC 6953) | 23.1 kW |
| Thermal output for a single fully configured powered I/O rack (FC 6954) | 39.5 kBTU/hr |
| Thermal output power for a single fully configured powered I/O rack (FC 6954) and a single fully configured non powered I/O rack (FC 6953) | 78.8 kBTU/hr |
| Environment | Operating | Storage | Shipping |
|---|---|---|---|
| Temperature | 50 - 80.6°F (10 - 27°C) 1 | 33.8 - 140°F (1 - 60°C) | -40 - 140°F (-40 - 60°C) |
| Relative humidity | 20 - 80% | 5 - 80% | 5 - 100% |
| Maximum altitude | 3048 m (10 000 ft) | ||
| 1 Derate maximum temperature 2°C per 1000 ft over 7000 ft | |||
| Product Configuration | Declared A-Weighted Sound Power Level, LWAd (B) | Declared A-Weighted Sound Pressure Level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idling | Operating | Idling | |
| Single I/O drawer alone in rack with acoustical door set. Blowers at nominal speeds. | 7.0 | 7.0 | 52 | 52 |
| Single I/O drawer alone in rack with nonacoustical (slimline) door set. Blowers at nominal speeds. | 7.5 | 7.5 | 59 | 59 |
| Bulk power assembly alone in rack with acoustical door set. Blowers at nominal speeds. | 6.9 | 6.9 | 52 | 52 |
| Bulk power assembly alone in rack with | 7.5 | 7.5 | 59 | 59 |
| Non-Acoustical (Slimline) Door Set. Blowers at nominal speeds. | ||||
| Typical configuration of powered I/O rack with acoustical door set: 4 I/O drawers and bulk power assembly. Blowers at nominal speeds. | 7.75 | 7.75 | 59 | 59 |
| Typical configuration of powered I/O rack with nonacoustical (slimline) Door set: 4 I/O drawers and bulk power assembly. Blowers at nominal speeds. | 8.2 | 8.2 | 66 | 66 |
| Maximum configuration of powered I/O rack with acoustical doorset: 8 I/O drawers and bulk power assembly. Blowers at nominal speeds. | 7.94 | 7.94 | 61 | 61 |
| Maximum configuration of powered I/O rack with nonacoustical (slimline) door set: 8 I/O drawers and bulk power assembly. Blowers at nominal speeds. | 8.4 | 8.4 | 68 | 68 |
1Declared level LWAd is the upper-limit A-weighted sound power level. Declared level LpAm is the mean A-weighted sound pressure level measured at the 1-meter bystander positions. 2All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296. 3B, dB, abbreviations for bels and decibels, respectively, where 1 B = 10 dB. 4Meets IT Product Noise Limits for, Generally Unattended Data Center, per Statskontoret Technical Standard 26:6. 5Meets IT Product Noise Limits for, Generally Attended Data Center, per Statskontoret Technical Standard 26:6. |
||||
Front-service access is necessary on the 6954 to accommodate a lift tool for the servicing of large drawers (I/O drawers). Front and rear service access is necessary to accommodate the lift tool for servicing of the optional integrated battery backup.