Identifying a service action by using sensor and event information for the 8335-GTB

You can use the sensor and event information from the system event log (SEL) to determine a service action to perform for the IBM® Power® System S822LC (8335-GTB).

If you have not done so already, complete Identifying a service action by using system event logs. Then, use the following table to determine the service action to perform.
Table 1. Sensor information, event description, and service action for the 8335-GTB
Sensor name (Sensor ID) Event description Service action
Watchdog (0x00)
  • Timer Expired
  • Reserved1
  • Reserved2
  • Reserved3
  • Reserved4
No service action is required.
  • Hard Reset
  • Power Down
  • Power Cycle
  • Timer Interrupt
SEL events with OEM record c0 | 000e000 | 3a150xxxxxxx indicate that a boot failed. Search for boot failure SEL events that have a time stamp close to the time stamp of this SEL event. If events exist, go to Resolving a system firmware boot failure. If there are no boot failure SEL events and the system booted correctly, no service action is required.
Host Status (0x04) Unknown Go to Getting fixes and update the system firmware to the most recent level of firmware that is available. If this SEL event continues to be logged each time you power on the system, go to Collecting diagnostic data. Then, go to Contacting IBM service and support.
  • S0/Go "Working"
  • S1 "Sleeping with system h/w & processor context maintained"
  • S2 "sleeping, processor context lost"
  • S3 "sleeping, processor & h/w context lost, memory retained"
  • S4 "non-volatile sleep / suspend-to disk"
  • S5 / G2: "soft-off"
  • S4 / S5: "soft-off"
  • G3 mechanical Off
  • Sleeping in an S1/S2/S3 State
  • G1: Sleeping
  • S5: entered by override
  • Legacy ON state
  • Legacy OFF state
No service action is required.
FW Boot Progress (0x05)
  • System Firmware Error
  • System Firmware Hang
SEL events with OEM record c0 | 000e000 | 3a150xxxxxxx indicate that a boot failed. Search for boot failure SEL events that have a time stamp close to the time stamp of this SEL event. If events exist, go to Resolving a system firmware boot failure.
System Firmware Progress No service action is required.
  • OCC 1 Active (0x08)
  • OCC 2 Active (0x09)
Device Disabled If the sensor name is OCC 1 Active, replace CPU 1. If the sensor name is OCC 2 Active, replace CPU 2. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • State Deasserted
  • Device Enabled
No service action is required.
Ambient Temp (0x0A)
  • Upper Critical - going low
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Lower Critical - going low
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
Upper Critical - going high Ensure that the room temperature meets the requirements that are specified for the system. Ensure that no obstructions are blocking air flow to the system.
  • CPU1 Temp (0x0B)
  • CPU2 Temp (0x0D)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical - going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Lower Critical - going low
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
  • CPU Func 1 (0x0C)
  • CPU Func 2 (0x0E)
  • IERR
  • Transition to Non-recoverable
  • Predictive Failure
If the sensor name is CPU Func 1, replace CPU 1. If the sensor name is CPU Func 2, replace CPU 2. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • Thermal Trip
  • FRB1 BIST Failure
  • FRB2 Hang In POST Failure
  • FRB3 Processor Startup Initialization Failure
  • Configuration Error
  • SMBIOS Uncorrectable CPU Complex Error
  • Processor Disabled
  • Terminator Presence Detected
  • Processor Automatically Throttled
  • Machine Check Exception
  • Correctable Machine Check Error
  • State Deasserted
  • Device Disabled
  • Transition to Critical from Less Severe
  • Transition to Non-recoverable from Less Severe
  • Transition to Critical from Non-recoverable
  • Processor Presence Detected
  • State Asserted
  • Device Enabled
  • Transition to OK
  • Transition to Non-Critical from OK
  • Transition to Non-Critical from More Severe
  • Monitor
  • Informational
No service action is required.
All PGood (0x1C)
  • Interlock Power Down
  • Power Off Power Down
  • Power Cycle
  • 240VA Power Down
No service action is required.
  • AC Lost
  • Soft Power Control Failure
  • Ensure that ac power is supplied to the rack.
  • Ensure that the system power cords are plugged tightly into both the power supply and the rack power distribution unit (PDU) for both system power supplies.
  • Ensure that the system was not powered off.
  • Power Unit Failure Detected
  • Predictive Failure
  • DIMM Func 1 (0x1E)
  • DIMM Func 2 (0x1F)
  • DIMM Func 3 (0x20)
  • DIMM Func 4 (0x21)
  • DIMM Func 5 (0x22)
  • DIMM Func 6 (0x23)
  • DIMM Func 7 (0x24)
  • DIMM Func 8 (0x25)
  • DIMM Func 9 (0x26)
  • DIMM Func 10 (0x27)
  • DIMM Func 11 (0x28)
  • DIMM Func 12 (0x29)
  • DIMM Func 13 (0x2A)
  • DIMM Func 14 (0x2B)
  • DIMM Func 15 (0x2C)
  • DIMM Func 16 (0x2D)
  • DIMM Func 17 (0x2E)
  • DIMM Func 18 (0x2F)
  • DIMM Func 19 (0x30)
  • DIMM Func 20 (0x31)
  • DIMM Func 21 (0x32)
  • DIMM Func 22 (0x33)
  • DIMM Func 23 (0x34)
  • DIMM Func 24 (0x35)
  • DIMM Func 25 (0x36)
  • DIMM Func 26 (0x37)
  • DIMM Func 27 (0x38)
  • DIMM Func 28 (0x39)
  • DIMM Func 29 (0x3A)
  • DIMM Func 30 (0x3B)
  • DIMM Func 31 (0x3C)
  • DIMM Func 32 (0x3D)
  • Memory Device Disabled
  • Uncorrectable Memory Error
  • Memory Scrub Failed
  • State Deasserted
  • Device Disabled
  • Transition to Critical from Less Severe
  • Transition to Non-recoverable from Less Severe
  • Transition to Critical from Non-recoverable
  • Correctable Memory Error
  • Parity
  • Correctable Memory Error Logging Limit Reached
  • Memory Automatically Throttled
  • Critical Over temperature
  • Presence Detected
  • Spare
  • State Asserted
  • Device Enabled
  • Transition to OK
  • Transition to Non-Critical from OK
  • Transition to Non-Critical from More Severe
  • Monitor
  • Informational
No service action is required.
  • Transition to Non-recoverable
  • Predictive Failure
If the sensor name is DIMM Func 1, replace DIMM 1. If the sensor name is DIMM Func 2, replace DIMM 2. And so on. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • DIMM Func 1 (0x1E)
  • DIMM Func 2 (0x1F)
  • DIMM Func 3 (0x20)
  • DIMM Func 4 (0x21)
  • DIMM Func 5 (0x22)
  • DIMM Func 6 (0x23)
  • DIMM Func 7 (0x24)
  • DIMM Func 8 (0x25)
  • DIMM Func 9 (0x26)
  • DIMM Func 10 (0x27)
  • DIMM Func 11 (0x28)
  • DIMM Func 12 (0x29)
  • DIMM Func 13 (0x2A)
  • DIMM Func 14 (0x2B)
  • DIMM Func 15 (0x2C)
  • DIMM Func 16 (0x2D)
  • DIMM Func 17 (0x2E)
  • DIMM Func 18 (0x2F)
  • DIMM Func 19 (0x30)
  • DIMM Func 20 (0x31)
  • DIMM Func 21 (0x32)
  • DIMM Func 22 (0x33)
  • DIMM Func 23 (0x34)
  • DIMM Func 24 (0x35)
  • DIMM Func 25 (0x36)
  • DIMM Func 26 (0x37)
  • DIMM Func 27 (0x38)
  • DIMM Func 28 (0x39)
  • DIMM Func 29 (0x3A)
  • DIMM Func 30 (0x3B)
  • DIMM Func 31 (0x3C)
  • DIMM Func 32 (0x3D)
Configuration Error Complete the following steps:
  1. If the sensor name is DIMM Func 1, ensure that DIMM 1 is seated properly. If the sensor name is DIMM Func 2, ensure that DIMM 2 is seated properly. And so on.
  2. If you recently installed or replaced memory DIMMs, ensure that the DIMMs are plugged in the correct memory slots.
  3. If the sensor name is DIMM Func 1, replace DIMM 1. If the sensor name is DIMM Func 2, replace DIMM 2. And so on. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • CPU Core Func 1 (0x3E)
  • CPU Core Func 2 (0x3F)
  • CPU Core Func 3 (0x40)
  • CPU Core Func 4 (0x41)
  • CPU Core Func 5 (0x42)
  • CPU Core Func 6 (0x43)
  • CPU Core Func 7 (0x44)
  • CPU Core Func 8 (0x45)
  • CPU Core Func 9 (0x46)
  • CPU Core Func 10 (0x47)
  • CPU Core Func 11 (0x48)
  • CPU Core Func 12 (0x49)
  • IERR
  • Transition to Non-recoverable
  • Predictive Failure
Replace system processor CPU 1. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • FRB1 BIST Failure
  • FRB2 Hang In POST Failure
  • FRB3 Processor Startup Initialization Failure
  • Configuration Error
  • SMBIOS Uncorrectable CPU Complex Error
  • Processor Disabled
  • Terminator Presence Detected
  • Machine Check Exception
  • Correctable Machine Check Error
  • State Deasserted
  • Device Disabled
  • Transition to Critical from Less Severe
  • Transition to Non-recoverable from Less Severe
  • Transition to Critical from Non-recoverable
  • Thermal Trip
  • Processor Automatically Throttled
  • Processor Presence Detected
  • State Asserted
  • Device Enabled
  • Transition to OK
  • Transition to Non-Critical from OK
  • Transition to Non-Critical from More Severe
  • Monitor
  • Informational
No service action is required.
  • CPU Core Func 13 (0x4A)
  • CPU Core Func 14 (0x4B)
  • CPU Core Func 15 (0x4C)
  • CPU Core Func 16 (0x4D)
  • CPU Core Func 17 (0x4E)
  • CPU Core Func 18 (0x4F)
  • CPU Core Func 19 (0x50)
  • CPU Core Func 20 (0x51)
  • CPU Core Func 21 (0x52)
  • CPU Core Func 22 (0x53)
  • CPU Core Func 23 (0x54)
  • CPU Core Func 24 (0x55)
  • IERR
  • Transition to Non-recoverable
  • Predictive Failure
Replace system processor CPU 2. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • FRB1 BIST Failure
  • FRB2 Hang In POST Failure
  • FRB3 Processor Startup Initialization Failure
  • Configuration Error
  • SMBIOS Uncorrectable CPU Complex Error
  • Processor Disabled
  • Terminator Presence Detected
  • Machine Check Exception
  • Correctable Machine Check Error
  • State Deasserted
  • Device Disabled
  • Transition to Critical from Less Severe
  • Transition to Non-recoverable from Less Severe
  • Transition to Critical from Non-recoverable
  • Thermal Trip
  • Processor Automatically Throttled
  • Processor Presence Detected
  • State Asserted
  • Device Enabled
  • Transition to OK
  • Transition to Non-Critical from OK
  • Transition to Non-Critical from More Severe
  • Monitor
  • Informational
No service action is required.
  • Mem Buf Func 1 (0x56)
  • Mem Buf Func 2 (0x57)
  • Mem Buf Func 3 (0x58)
  • Mem Buf Func 4 (0x59)
  • Mem Buf Func 5 (0x5A)
  • Mem Buf Func 6 (0x5B)
  • Mem Buf Func 7 (0x5C)
  • Mem Buf Func 8 (0x5D)
  • Uncorrectable Memory Error
  • Memory Device Disabled
  • State Deasserted
  • Device Disabled
  • Transition to Critical from Less Severe
  • Transition to Non-recoverable from Less Severe
  • Transition to Critical from Non-recoverable
  • Correctable Memory Error
  • Parity
  • Memory Scrub Failed
  • Correctable Memory Error Logging Limit Reached
  • Memory Automatically Throttled
  • Critical Over temperature
  • Presence Detected
  • Spare
  • State Asserted
  • Device Enabled
  • Transition to OK
  • Transition to Non-Critical from OK
  • Transition to Non-Critical from More Severe
  • Monitor
  • Informational
No service action is required.
  • Configuration Error
  • Transition to Non-recoverable
  • Predictive Failure
If the sensor name is Mem Buf Func 1, replace memory riser 1. If the sensor name is Mem Buf Func 2, replace memory riser 2. And so on. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
Boot Count (0x5F) None No service action is required.
Motherboard Flt (0x60) State Deasserted No service action is required.
State Asserted Replace the system backplane. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
System Event (0x61) Undetermined system hardware failure Go to Collecting diagnostic data. Then, go to Contacting IBM service and support.
  • System Reconfigured
  • OEM System boot event
  • Entry added to auxiliary log
  • PEF Action
  • Timestamp Clock Sync
  • Transition State Active
  • Transition State Idle
  • Transition State Busy
No service action is required.
Activate Pwr Lt (0x62) None No service action is required.
  • Ref Clock Fault (0x63)
  • PCI Clock Fault (0x64)
  • State Deasserted
  • State Asserted
No service action is required.
  • DIMM1 Temp (0x69)
  • DIMM2 Temp (0x6A)
  • DIMM3 Temp (0x6B)
  • DIMM4 Temp (0x6C)
  • DIMM5 Temp (0x6D)
  • DIMM6 Temp (0x6E)
  • DIMM7 Temp (0x6F)
  • DIMM8 Temp (0x70)
  • DIMM9 Temp (0x71)
  • DIMM10 Temp (0x72)
  • DIMM11 Temp (0x73)
  • DIMM12 Temp (0x74)
  • DIMM13 Temp (0x75)
  • DIMM14 Temp (0x76)
  • DIMM15 Temp (0x77)
  • DIMM16 Temp (0x78)
  • DIMM17 Temp (0x79)
  • DIMM18 Temp (0x7A)
  • DIMM19 Temp (0x7B)
  • DIMM20 Temp (0x7C)
  • DIMM21 Temp (0x7D)
  • DIMM22 Temp (0x7E)
  • DIMM23 Temp (0x7F)
  • DIMM24 Temp (0x80)
  • DIMM25 Temp (0x81)
  • DIMM26 Temp (0x82)
  • DIMM27 Temp (0x83)
  • DIMM28 Temp (0x84)
  • DIMM29 Temp (0x85)
  • DIMM30 Temp (0x86)
  • DIMM31 Temp (0x87)
  • DIMM32 Temp (0x88)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
  • CPU Core Temp 1 (0x89)
  • CPU Core Temp 2 (0x8A)
  • CPU Core Temp 3 (0x8B)
  • CPU Core Temp 4 (0x8C)
  • CPU Core Temp 5 (0x8D)
  • CPU Core Temp 6 (0x8E)
  • CPU Core Temp 7 (0x8F)
  • CPU Core Temp 8 (0x90)
  • CPU Core Temp 9 (0x91)
  • CPU Core Temp 10 (0x92)
  • CPU Core Temp 11 (0x93)
  • CPU Core Temp 12 (0x94)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
  • CPU Core Temp 13 (0x95)
  • CPU Core Temp 14 (0x96)
  • CPU Core Temp 15 (0x97)
  • CPU Core Temp 16 (0x98)
  • CPU Core Temp 17 (0x99)
  • CPU Core Temp 18 (0x9A)
  • CPU Core Temp 19 (0x9B)
  • CPU Core Temp 20 (0x9C)
  • CPU Core Temp 21 (0x9D)
  • CPU Core Temp 22 (0x9E)
  • CPU Core Temp 23 (0x9F)
  • CPU Core Temp 24 (0xA0)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
  • System Power (0xA1)
  • Proc0 Power (0xA2)
  • Proc1 Power (0xA3)
  • PCIE Proc0 Pwr (0xA6)
  • PCIE Proc1 Power (0xA7)
  • GPU Power (0xAA)
  • Mem Cache Power (0xAB)
  • Mem Proc0 Pwr (0xAC)
  • Mem Proc1 Pwr (0xAD)
  • Fan Power (0xB0)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action required.
  • TOD Clock Fault (0xB1)
  • APSS Fault (0xB2)
  • State Deasserted
  • State Asserted
No service action is required.
PS Derating Fac (0xB4) None No service action is required.
OS Boot (0xB5)
  • Installation aborted
  • Installation failed
Ensure that the operating system boot image is loaded. Ensure that the disk drive or solid-state drive is ready. Reload the operating system boot image.
  • A: boot completed
  • C: boot completed
  • PXE boot completed
  • Diagnostic boot completed
  • CD-ROM boot completed
  • ROM boot completed
  • Boot completed - device not specified
  • Installation started
  • Installation completed
No service action is required.
PCI (0xB6)
  • State Deasserted
  • State Asserted
No service action is required.
  • GPU Func 1 (0xB8)
  • GPU Func 2 (0xB9)
  • GPU Func 3 (0xBA)
  • GPU Func 4 (0xBB)
  • Uncorrectable Memory Error
  • Parity
  • Memory Scrub Failed
  • Memory Device Disabled
  • Configuration Error
  • Memory Automatically Throttled
If the sensor name is GPU Func 1, replace GPU 1. If the sensor name is GPU Func 2, replace GPU 2. And so on. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • Correctable Memory Error
  • Parity
  • Correctable Memory Error Logging Limit Reached
  • Presence Detected
  • Spare
  • Critical Over temperature
No service action is required.
  • GPU Temp 1 (0xBC)
  • GPU Temp 2 (0xBD)
  • GPU Temp 3 (0xBE)
  • GPU Temp 4 (0xBF)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
  • Mem Buf Temp 1 (0xC0)
  • Mem Buf Temp 2 (0xC1)
  • Mem Buf Temp 3 (0xC2)
  • Mem Buf Temp 4 (0xC3)
  • Mem Buf Temp 5 (0xC4)
  • Mem Buf Temp 6 (0xC5)
  • Mem Buf Temp 7 (0xC6)
  • Mem Buf Temp 8 (0xC7)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
  • CPU Diode 1 (0xC8)
  • CPU Diode 2 (0xCB)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
Checkstop (0xC9) IERR If this event immediately precedes a system power off, no service action is required. Otherwise, search for SEL events that meet the following criteria:

If you found a SEL event that matches the criteria, perform the service action that is indicated in this table for the SEL event. Otherwise, go to Collecting diagnostic data. Then, go to Contacting IBM service and support.

  • Thermal Trip
  • Configuration Error
  • Processor Automatically Throttled
  • Correctable Machine Check Error
  • Processor Presence Detected
No service action is required.
  • FRB1 BIST Failure
  • FRB2 Hang In POST Failure
  • FRB3 Processor Startup Initialization Failure
  • SMBIOS Uncorrectable CPU Complex Error
  • Processor Disabled
  • Terminator Presence Detected
  • Machine Check Exception
Go to Collecting diagnostic data. Then, go to Contacting IBM service and support.
  • PSU Fault 1 (0xCD)
  • PSU Fault 2 (0xCE)
Power Supply Failure Detected An assert event immediately followed by a deassert event indicates that a power cycle of the system occurred. No service action is required. If there is no deassert event immediately following the assert event, replace the power supply. If the sensor name is PSU Fault 1, replace PSU 1. If the sensor name is PSU Fault 2, replace PSU 2. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • Predictive Failure
  • Power Supply Input Out of Range But Present
If the sensor name is PSU Fault 1, replace PSU 1. If the sensor name is PSU Fault 2, replace PSU 2. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • Power Supply Input Lost or AC DC
  • Power Supply Input Lost Or Out Of Range
Ensure that ac power is supplied to the rack. Ensure that the system power cords are plugged tightly into both the power supply and the rack PDU unit for both system power supplies. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
Configuration Error Ensure that both power supplies are securely seated in the system. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
  • Presence Detected
  • Power Supply Inactive
No service action is required.
CPU VDD Volt (0xCF)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
CPU VDD Curr (0xD0)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
No service action is required.
BIOS Golden Side (0xD2) None Go to Resolving a system firmware boot failure and follow the service action for a system event log (SEL) with the value OEM record c0 and OEM c0 specific log information 3a1504xxxxxx.
BMC Golden Side (0xD3) None Go to Resolving a system firmware boot failure and follow the service action for a system event log (SEL) with the value OEM record c0 and OEM c0 specific log information 3a1504xxxxxx.
  • Fan 1 (0xD4)
  • Fan 2 (0xD5)
  • Fan 3 (0xD6)
  • Fan 4 (0xD7)
  • Lower Non-critical – going low
  • Lower Non-critical – going high
  • Lower Critical – going low
  • Lower Critical – going high
  • Lower Non-recoverable – going low
  • Lower Non-recoverable – going high
  • Upper Non-critical – going low
  • Upper Non-critical – going high
  • Upper Critical - going low
  • Upper Critical - going high
  • Upper Non-recoverable – going low
  • Upper Non-recoverable – going high
  • Device Inserted/Device Present
No service action is required.
  • Device Removed/Device Absent
  • Transition to degraded
  • Install error
  • Redundancy lost
  • Non-redundant insufficient resources
Ensure that all fans are seated securely. Go to 8335-GTB locations to identify the physical location and removal and replacement procedure.
CurPwr Redundant (0xD8)
  • State Deasserted
  • State Asserted
No service action is required.
NxtPwr Redundant (0xD9)
  • State Deasserted
  • State Asserted
No service action is required.
Turbo Allowed (0xDA)
  • State Deasserted
  • State Asserted
No service action is required.
  • Freq Limit OT 1 (0xDB)
  • Freq Limit OT 2 (0xDF)
  • State Deasserted
  • State Asserted
No service action is required.
  • Freq Limit Pwr 1 (0xDC)
  • Freq Limit Pwr 2 (0xE0)
  • State Deasserted
  • State Asserted
No service action is required.
  • Mem Thrtl OT 1 (0xDD)
  • Mem Thrtl OT 2 (0xE1)
  • State Deasserted
  • State Asserted
No service action is required.
  • Quick Pwr Drop 1 (0xDE)
  • Quick Pwr Drop 2 (0xE2)
State Deasserted No service action is required.
State Asserted
Water Cooled (0xE3) None No service action is required.
CPU 1 VDD Temp (0xE4) Upper Critical - going high If the system is a water-cooled system, go to Resolving an over temperature problem for a water-cooled 8335-GTB system. If the system is an air-cooled system, ensure that there are no air flow obstructions at the front or at the rear of the system. Ensure that the fans are operating properly.
CPU 2 VDD Temp (0xE5) Upper Critical - going high If the system is a water-cooled system, go to Resolving an over temperature problem for a water-cooled 8335-GTB system. If the system is an air-cooled system, ensure that there are no air flow obstructions at the front or at the rear of the system. Ensure that the fans are operating properly.



Last updated: Thu, December 02, 2021