Troubleshooting
Problem
This RETAIN tip is to list Power Details.
Resolving The Problem
Source
RETAIN tip: H193411
Issue
This RETAIN tip is to list Power Details.
Affected configurations
The system may be any of the following IBM servers:
- BladeCenter H, type 8852, any model
This tip is not option specific.
This tip is not Operating System specific.
Additional information
- BladeCenter H (Type 8852) blowers are powered directly from the AC input cables to the chassis. Each blower gets power from a different AC cable.
- Chassis AC feed 1 provides power to Power Module's (PM) 1 and 4 and blower 2. AC feed 2 provides power to PM's 2 and 3 and blower 1.
- Both PM's 1 and 2 in power domain 1 must be active for Switch Modules in bays 7 and 8 to work. PM's 3 and 4 in power domain 2 must both be active for Switch Modules in bays 9 and 10 to work. See RETAIN tip H191392 Unable to power on high speed switches - IBM BladeCenter H
- At least one PM in domain 1, PM 1 or 2, must work for Blade slots 1-7 and Switch Module bays 3 and 4 to work. At least one PM in domain 2, PM 3 or 4, must work for Blade slots 8-14 and Bridge Module bays 1 and 2 to work.
- Only one of the four PM's (PM 1, 2, 3 or 4) need to work for the Advanced Management Modules (AMM) in slots 1 and 2 and Switch Module bays 1 and 2 to work. Any one on the four PM's can power up the AMM and the switches in bays 1 and 2.
Document Location
Worldwide
[{"Type":"HW","Business Unit":{"code":"BU054","label":"Systems w\/TPS"},"Product":{"code":"HW21Y","label":"BladeCenter H Chassis"},"Platform":[{"code":"PF025","label":"Platform Independent"}],"Line of Business":{"code":"","label":""}}]
Was this topic helpful?
Document Information
Modified date:
29 January 2019
UID