IBM Support

Overview - IBM 1000 VA, 1500 VA, 2200 VA, 3000 VA, 5000 VA, 6000 VA, 8000 VA and 11000 VA UPS options for IBM System x, BladeCenter, and Flex Systems

Product Documentation


Abstract

Technical overview for the IBM IBM 1000 VA, 1500 VA, 2200 VA, 3000 VA, 5000 VA, 6000 VA, 8000 VA and 11000 VA UPS options for IBM System x, BladeCenter, and Flex Systems.

Content

Planned Availability Date

October 23, 2014

At a glance

IBM 1000VA, 1500VA, 2200VA, 3000VA 2U LCD, 5000VA, 6000VA 3U LCD and 8000VA, 11000VA 6U Uninterruptible Power Supply (UPS) offerings provide rack-dense power protection with increased efficiency and simplified power management to safeguard high availability.

IBM System x and BladeCenter servers and Flex Systems environments 2U 1500VA (1000 W), 2U 2200VA (1920 W), and 2U 3000VA (2700 W), 3U 5000VA, 3U 6000VA, 6U 8000VA and 6U 11000VA rack mount and tower offerings
95+% energy efficiency across line at 100% load.

Nine-language graphical Liquid Crystal Display (LCD) which provides intuitive, at-the-rack management and monitoring capabilities Hot-swappable batteries for optimum uptime, availability, and ease of maintenance.

ABM three-stage charging technology for significantly extending battery service life and optimizing recharge time
Standard UPS Power Manager Supervisory software to monitor, manage, and to gradually shut down the connected load in the event of a power failure.


1500VA/2200VA, 3000VA, 5000VA/6000VA, 8000VA/11000VA Extended Battery Modules (EBM) for scalable runtime requirements.

Optional Network Management Card (46M4110) for enhanced UPS monitoring and control.

The Network Management Card is standard on all models except tower models and 1500VA and 2200VA rack and towwer models Optional Environmental Monitoring Probe (46M4113) for thermal management requirements
Integration with IBM Systems Director Active Energy Manager (AEM) for single pane of glass power and thermal trending analysis and management

Overview

In high availability server environments, unplanned power outages or line quality irregularities can have a considerable financial impact on small, medium, and large enterprise businesses. Selecting the right uninterruptible power supply (UPS) can efficiently, reliably, and affordably help protect against these potentially costly incidents The new power-dense IBM 1500VA, 2200VA, 3000VA, 5000VA, 6000VA, 8000VA and 11000VA Rack or Tower UPS and IBM 1000VA, 1500VA Tower offerings provide optimized protection, increased efficiency, and simplified power management to safeguard IBM System x(R) and BladeCenter(R) servers and Flex Systems environments
IBM 5594 UPS offerings come in space-efficient 1.5KVA/2.2KVA 2U as well as 3KVA 2U, and also come in 5KVA/6KVA 3U, and 8KVA/11KVA 6U rack mount designs.

These models are equipped to meet the requirements of your highest availability systems with geography-specific high-voltage and low-voltage solutions.

  • 1500 VA/1000 W 2U Rack
  • 55941AX (100V/120V) with eight NEMA 5-15R
  • 55941KX (230V) with eight IEC 320 C13 receptacles
  • 2200 VA/1920 W 2U Rack
  • 55942AX (100V/120V) with eight NEMA 5-20R
  • 55942KX (230V) with eight IEC 320 C13 and one IEC 320 C19 receptacles 3000 VA/2700 W 2U Rack
  • 55943AX (100V/120V) with one NEMA L5-20R, two NEMA 5-20R, 55943KX (200/208V) with eight IEC 320, and one IEC 320 C19 receptacle
  • 5000 VA/2700 W 3U Rack
  • 55945KX (200/208V) with eight IEC 320 C13, two IEC 320 C19 receptacles and one terminal block
  • 6000 VA/2700 W 6U Rack
  • 55946KX (200/208V) with eight IEC 320 C13, two IEC 320 C19 receptacles and one terminal block
  • 8000 VA/2700 W 6U Rack
  • 55948KX (200/208V) with four IEC 320 C19 receptacles and on AC output terminal block
  • 55948PX (380V/415V 3 phase) with four IEC 320 C19 receptacles and one AC output terminal block
  • 11000 VA/2700 W 6U Rack
  • 55949KX (200/208V) with two NEMA L6-20R, two four IEC 320 C19 receptacles and one AC output terminal block
  • 55949PX (380V/415V 3 phase) with four IEC 320 C19 receptacles and one AC output terminal block
  • IBM 5595 UPS offerings come in space-efficient 1.0kVA/1.5kVA tower mount designs.

As with the rack mount models, these tower mount models are equipped to meet the requirements of your highest availability systems with geography- specific high-voltage and low-voltage solutions

  • 1000 VA/1000 W Tower
  • 55951AX (110V) with eight NEMA 5-15R
  • 55951KX (230V) with six IEC 320 C13 receptacles
  • 1500 VA/2700 W Tower
  • 55952AX (110V) with eight NEMA 5-15R
  • 55952KX (230V) with eight IEC 320 C13 receptacles

New 1.5KVA/2.2KVA and 3KVA 2U Extended Battery Module and 5KVA/6KVA and 8KVA/11KVA 3U Extended Battery Modules are available to provide extended life for all UPS models.

These units are designed to operate at a 95% to 98% efficiency rating at full load and can increase uptime, with next-generation power protection, while helping to reduce operating costs These new offerings also provide intuitive power management and monitoring capabilities. The intelligent three-button, dual-color backlight graphical Liquid Crystal Display (LCD) features a bright easy-to-navigate panel that provides configurability and displays important status information in nine languages: English, French, German Spanish, Russian, Korean, Japanese, Simplified Chinese, and Traditional Chinese. Runtime, load troubleshooting, and other vital information are also displayed. UPS power manager supervisory software is also standard to monitor, manage, and to gradually shut down the connected server loads in the event of an extended power interruption They also come equipped with a communication bay for installation of an optional Network Management Card (46M4110). The Network Management Card provides convenient over-the-network UPS remote monitoring and management through a standard web browser. The Network Management Card is standard on all models except tower models and 1500VA and 2200VA rack and tower models.

An optional Environmental Monitoring Probe (46M4113) is also available for thermal (temperature and humidity) management requirements.

IBM Systems Director Active Energy Manager (AEM) provides an array of new features that allow power and thermal trending analysis for improved power management. By plugging systems into an IBM UPS, AEM is able to collect power information for each device, presenting a more complete view of energy usage within the data center. With access to accurate detailed information on power usage right at their fingertips, IT and facility managers are now able to manage data centers for optimal energy efficiency, migrating workloads to alleviate hot spots or transferring work from underutilized systems to conserve energy The new IBM 5594 and 5595 UPS models also feature ABM(R) technology which incorporates sophisticated sensing circuitry and an innovative three-stage charging technique to significantly extend battery service life and optimize recharge time. ABM also provides up to a 60-day notification when a hot-swappable battery is approaching the end of its useful life Hot-swappable batteries enable maximum uptime, availability, and ease of maintenance. All 5594 and 5595 units come equipped with intelligent load segments.

These individual receptacle groups can be programmed and controlled allowing mission-critical devices to be prioritized during shutdown to preserve battery runtime. For applications requiring extended backup times, an external battery module can also be added to all the new UPS rack and tower models to deliver hours of runtime to critical systems during a prolonged power outage.


Key prerequisites

The following customer-supplied wall outlets are required:

  • UPs 1500VA, 2200VA Rack or Tower UPS and 1000VA, 1500VA
  • Tower UPS: 100 V to 240 V 10-20 A circuit (single phase)
  • UPS 3000VA, 5000VA Rack or Tower UPS: 100 V to 240 V 20-32A circuit (single phase)
  • UPS 6000VA, 8000VA and 11000VA Rack or Tower UPS 100 V to 240 V, 30-32 A circuit (single phase) hard wired from UPS terminal block UPS 8000VA and 11000VA 6U 3/1
  • Phase UPS: 380 V to 415 V 30-32 A circuit (3 phase) hard wired from UPS terminal block

Warranty

  • 5594 Rack UPS - Three years
  • 5595 Tower UPS - Three years
  • Options (battery Modules) - One year

Packaging

IBM 1kVA, 1.5kVA, 2.2kVA, 3kVA, 5kVA, 6kVA, 8kVA, 11kVA UPS

IBM 1.0kVA 2U Tower UPS System unit carton 1
IBM 1.5kVA 2U
Rack or Tower UPS
IBM 2.2kVA 2U
Rack or Tower UPS
IBM 3.0kVA 2U
Rack or Tower UPS
IBM 5.0kVA 3U
Rack or Tower UPS
IBM 6.0kVA 3U
Rack or Tower UPS
IBM 8.0kVA 6U
Rack or Tower UPS
IBM 11.0kVA 6U
Rack or Tower UPS

Base UPS with X-SNMP / Web Adapter Card with Serial Functionality Accessory kit, includes:

  • Front Bezel
  • Rack Mount Kit with Rails and Hardware
  • Rack Installation Instructions
  • Serial Cable (3.7 m, 12 ft.)
  • USB Cable
  • REPO Connector
  • Documentation Kit, includes:
  • Important Notices Manual
  • Warranty Flyer
  • Documentation CD
  • Software CD

 

 

Physical specifications

IBM 1000VA 2U UPS :

Dimensions

  • Approximate height: 84.5 mm (3.3 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 470 mm (18.5 in)
  • Approximate weight: 18.4 kg (40.5 lb) / 1KX-19.5 kg (42.9 lb)

Shipping dimensions

  • Approximate height: 270 mm (10.6 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 800 mm (31.5 in)
  • Approximate weight: 27.5 kg (60.7 lb) - 1AX
    • 28.6 kg (63.0 lb) - 1KX

IBM 1500VA 2U UPS:

Dimensions

  • Approximate height: 84.5 mm (3.3 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 470 mm (18.5 in)
  • Approximate weight: 18.4 kg (40.5 lb) / 1KX-19.5 kg (42.9 lb)

Shipping dimensions

  • Approximate height: 270 mm (10.6 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 800 mm (31.5 in)
  • Approximate weight:
    • 27.5 kg (60.7 lb) - 1AX
    • 28.6 kg (63.0 lb) - 1KX

IBM 2200VA 2U UPS

Dimensions

  • Approximate height: 84.5 mm (3.3 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 580 mm (22.8 in)
  • Approximate weight
    • 30.5 kg (67.1 lb) - 2AX
    • 30.7 kg (67.6 lb) - 2KX

Shipping dimensions

  • Approximate height: 270 mm (10.6 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 1000 mm (39.4 in)
  • Approximate weight:
    • 40.3 kg (88.7 lb) - 2AX
    • 40.5 kg (89.3 lb) - 2KX

IBM 3000VA 2U UPS

Dimensions

  • Approximate height: 127 mm (5.0 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 528 mm (20.8 in)
  • Rack height: 3 U
  • Approximate weight:
    • 38.5 kg (84.8 lb) - 3AX
    • 39.2 kg (86.4 lb) - 3JX
    • 40.9 kg (90.1 lb) - 3KX

Shipping dimensions

  • Approximate height: 330 mm (13.0 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 800 mm (31.5 in)
  • Approximate weight:
    • 48.8 kg (107.4 lb) - 3AX
    • 51.2 kg (112.7 lb) - 3JX
    • 49.5 kg (109.1 ln) - 3KX

IBM 5000VA 3U UPS:

Dimensions

  • Approximate height: 127 mm (5.0 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 528 mm (20.8 in)
  • Rack height: 3 U
  • Approximate weight:
    • 38.5 kg (84.8 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

Shipping dimensions

  • Approximate height: 330 mm (13.0 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 800 mm (31.5 in)
  • Approximate weight:
    • 48.8 kg (107.4 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

IBM 6000VA 3U UPS:

Dimensions

  • Approximate height: 127 mm (5.0 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 528 mm (20.8 in)
  • Rack height: 3 U
  • Approximate weight:
    • 38.5 kg (84.8 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

Shipping dimensions

  • Approximate height: 330 mm (13.0 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 800 mm (31.5 in)
  • Approximate weight:
    • 48.8 kg (107.4 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

IBM 8000VA 6U 8KX and 8PX UPS:

Dimensions

  • Approximate height: 127 mm (5.0 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 528 mm (20.8 in)
  • Rack height: 3 U
  • Approximate weight:
    • 38.5 kg (84.8 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

Shipping dimensions

  • Approximate height: 330 mm (13.0 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 800 mm (31.5 in)
  • Approximate weight:
    • 48.8 kg (107.4 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

IBM 11000VA 6U 9KX and 9PX UPS:

Dimensions

  • Approximate height: 127 mm (5.0 in)
  • Approximate width: 482.6 mm (19.0 in)
  • Approximate depth: 528 mm (20.8 in)
  • Rack height: 3 U
  • Approximate weight:
    • 38.5 kg (84.8 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

Shipping dimensions

  • Approximate height: 330 mm (13.0 in)
  • Approximate width: 600 mm (23.6 in)
  • Approximate depth: 800 mm (31.5 in)
  • Approximate weight:
    • 48.8 kg (107.4 lb) - 3AX
    • 40.9 kg (90.1 lb) - 3KX

Electrical specifications:

  • UPS 1,500 VA / 1000W 2U Rack - (single phase)
  • 55941AX 1200/1440 VA, 100V/120V AC, 60 Hz, 12 A Output through 4 NEMA 5-15R and 2 IEC 320 C13 receptacles UPS 1,500 VA / 1000W 2U Rack - (single phase)
  • 55941KX 1,500 VA, 220-240V AC, 50 Hz, 7.5 A Output through 4 IEC 320 C13 receptacles
    UPS 2,200 VA / 1920W 2U Rack - (single phase)
  • 55942AX 1500/1920 VA, 100V/120V AC, 60 Hz, 16 A Output through 6 NEMA 5-20R, 2 IEC 320 C13, and 2 IEC 320 C19 320 C19 receptacles 55942KX 2,200 VA, 220-240V AC, 50 Hz, 10 A Output through 8 IEC 320 C13 and 2 IEC 320 C19 receptacles UPS 3,000 VA / 2700W 3U Rack - (single phase)
  • 55943AX 2300/2880 VA, 100V/120V AC, 60 Hz, 24 A Output through 1 NEMA L5-20R, 2 NEMA 5-20R, 2 IEC 320 C19, and 2 IEC 320 C13 receptacles Output through 2 NEMA L6-20R, 2 IEC 320 C19, and 2 IEC 320 C13 receptacles
    55943KX 220-240V AC, 50 Hz, 16 A Output through 8 IEC 320 C13 and 2 IEC 320 C19 receptacles Audible noise at 1 meter - 55 dBa (100% load)
  • Online thermal dissipation:
    • 1AX, 1KX - 180 btu/hr
    • 2AX, 2KX - 345 BTU/hr
    • 3AX, 3JX/3KX - 485 BTU/hr

Hardware requirements:

  • The IBM 1500VA LCD UPS or 2200VA LCD UPS or 3000VA LCD UPS must be installed in an Enterprise or S2 rack or a 19-inch EIA-310-D industry-standard rack

Operating Environment

  • Temperature:
    • 0 to 40.0 degrees C (32 to 104 degrees F) at 0 to 2,000 m (0 to 6,600 ft)
    • Relative humidity: 5% to 95%
    • Maximum altitude: 3,000 m ( 9,843 ft)

Product marketing and replacement part numbers (FRU)

Description Marketing part number
IBM RT1.5kVA 2U Rack or Tower UPS (100-125VAC) 55941AX
IBM RT1.5kVA 2U Rack or Tower UPS (200-240VAC)
55941KX
IBM RT2.2kVA 2U Rack or Tower UPS (100-125VAC) 55942AX
IBM RT2.2kVA 2U Rack or Tower UPS (200-240VAC) 55942KX
IBM RT3kVA 2U Rack or Tower UPS (100-125VAC) 55943AX
IBM RT3kVA 2U Rack or Tower UPS (200-240VAC) 55943KX
IBM RT5kVA 3U Rack or Tower UPS (200-240VAC) 55945KX
IBM RT6kVA 6U Rack or Tower UPS (200-240VAC) 55946KX
IBM RT8kVA 6U Rack or Tower UPS (200-240VAC) 55948KX
IBM RT11kVA 6U Rack or Tower UPS (200-240VAC) 55949KX
IBM RT8kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC) 55948PX
IBM RT11kVA 6U 3:1 Phase Rack or Tower UPS (380-415VAC) 55949PX
IBM 1.5kVA/2.2kVA 2U Rack or Tower Extended Battery Module 55942BX
IBM 3kVA 2U Rack or Tower Extended Battery Module 55943BX
IBM 5kVA/6kVA 3U Rack or Tower Extended Battery Module 55946BX
IBM 8kVA/11kVA 3U Rack or Tower Extended Battery Module Tower Models 55949BX
IBM T1kVA Tower UPS (100-125VAC) 55951AX
IBM T1kVA Tower UPS (200-240VAC) 55951KX
IBM T1.5kVA Tower UPS (100-125VAC) 55952AX
IBM T1.5kVA Tower UPS (200-240VAC) 55952KX

Hardware requirements

None.

Software requirements

The 1000VA, 1500VA, 2200VA, 3000VA, 5000VA, 6000VA, 8000VA or the 11000VA UPS can provide backup power to your
server regardless of the operating system used.

However, to enjoy the benefits and manageability features provided with the IBM UPS Management Software (which is needed to shutdown the server gracefully during a power outage by receiving and processing the shutdown commands from the UPS or NMC based on the operating state of the UPS) through SNMP or serial one of the following operating systems must be used:

  • Microsoft Windows XP Professional Edition
  • Microsoft Windows XP Professional x64 Edition
  • Microsoft Windows Server 2003/2003 R2, Enterprise Edition
  • Microsoft Windows Server 2003/2003 R2, Enterprise x64 Edition Microsoft Windows Server 2003/2003 R2, Standard Edition
  • Microsoft Windows Server 2003/2003 R2, Standard x64 Edition
  • Microsoft Windows Vista Business x86
  • Microsoft Windows Vista Business x64
  • Microsoft Windows Vista Ultimate x86
  • Microsoft Windows Vista Ultimate x64
  • Microsoft Windows 7 Prof x86
  • Microsoft Windows 7 Prof x64
  • Microsoft Windows 7 Ultimate x86
  • Microsoft Windows 7 Ultimate x64
  • Microsoft Windows Server 2008, Enterprise x86 Edition
  • Microsoft Windows Server 2008, Enterprise x64 Edition
  • Microsoft Windows Server 2008, Standard x86 Edition
  • Microsoft Windows Server 2008, Standard x64 Edition
  • Microsoft Windows Server 2008, Standard Edition R2 x64 Edition Red Hat Enterprise Linux 5 Server Edition
  • Red Hat Enterprise Linux 5 Server x64 Edition
  • Red Hat Enterprise Linux 4 AS for Intel x86
  • Red Hat Enterprise Linux 4 AS for 64 bit
  • Red Hat Enterprise Linux 4 ES for x86
  • Red Hat Enterprise Linux 4 ES for 64 bit
  • Red Hat Enterprise Linux 4 AS for iSeries and pSeries

Also, to enjoy the benefits and manageability features provided with the IBM UPS Management Software through USB, one of the following operating systems must be used:

  • Microsoft Windows XP Professional Edition
  • Microsoft Windows XP Professional x64 Edition
  • Microsoft Windows Server 2003/2003 R2, Enterprise Edition
  • Microsoft Windows Server 2003/2003 R2, Enterprise x64 Edition Microsoft Windows Server 2003/2003 R2, Standard Edition
  • Microsoft Windows Server 2003/2003 R2, Standard x64 Edition
  • Microsoft Windows Vista Business x86
  • Microsoft Windows Vista Business x64
  • Microsoft Windows Vista Ultimate x86
  • Microsoft Windows Vista Ultimate x64
  • Microsoft Windows 7 Prof x86
  • Microsoft Windows 7 Prof x64
  • Microsoft Windows 7 Ultimate x86
  • Microsoft Windows 7 Ultimate x64
  • Microsoft Windows Server 2008, Enterprise x86 Edition
  • Microsoft Windows Server 2008, Enterprise x64 Edition
  • Microsoft Windows Server 2008, Standard x86 Edition
  • Microsoft Windows Server 2008, Standard x64 Edition
  • Microsoft Windows Server 2008, Standard Edition R2 x64 Edition

Compatibility

The IBM UPS 1000VA, 1500VA, 2200VA, 3000VA, 5000VA, 6000VA, 8000VA and 11000VA UPS offerings are compatible with all System x servers and other supporting devices that require ac power

Limitations

IBM 1kVA, 1.5kVA, 2.2kVA, 3kVA, 5kVA, 6kVA, 8kVA, 11kVA UPS offerings require either 2U, 3U or 6U of rack space in one of the following rack cabinets:

  • IBM 42U Enterprise Rack
  • IBM 42U Enterprise V2 Rack
  • IBM S2 42U Dynamic Rack
  • IBM S2 42U Rack
  • IBM S2 25U Rack
  • IBM 11U Office Enablement Kit
  • IBM 1200MM Deep Racks
  • IBM PureFlex Rack

The UPS and connected EBMs must be installed no higher than 5 ft.(1.5m) above the floor to allow for easy installation and servicing.

Document Location

Worldwide

Operating System

System x Hardware Options:Windows Server 2003

System x Hardware Options:Windows Server 2003 x86-64

System x Hardware Options:Windows XP

System x Hardware Options:Windows XP x86-64

System x Hardware Options:Windows Vista

System x Hardware Options:Windows Server 2008

System x Hardware Options:Red Hat Enterprise Linux 4

System x Hardware Options:Red Hat Enterprise Linux 4 x86-64

System x Hardware Options:Red Hat Enterprise Linux 5

System x Hardware Options:Red Hat Enterprise Linux 5 x86-64

System x Hardware Options:Windows Server 2008 x86-64 & 2008 R2

[{"Type":"HW","Business Unit":{"code":"BU016","label":"Multiple Vendor Support"},"Product":{"code":"QUOEABJ","label":"System x Hardware Options->Power Accessories->Power distribution unit (PDU)->46M4167"},"Platform":[{"code":"PF042","label":"Caldera"},{"code":"PF033","label":"Windows"}],"Line of Business":{"code":"","label":""}},{"Type":"HW","Business Unit":{"code":"BU054","label":"Systems w\/TPS"},"Product":{"code":"QUOEABK","label":"System x Hardware Options->Power Accessories->Power distribution unit (PDU)->46M4116"},"Platform":[{"code":"PF042","label":"Caldera"},{"code":"PF033","label":"Windows"}],"Line of Business":{"code":"","label":""}},{"Type":"HW","Business Unit":{"code":"BU054","label":"Systems w\/TPS"},"Product":{"code":"QUOEABL","label":"System x Hardware Options->Power Accessories->Power distribution unit (PDU)->46M4134"},"Platform":[{"code":"PF042","label":"Caldera"},{"code":"PF033","label":"Windows"}],"Line of Business":{"code":"","label":""}}]

Document Information

Modified date:
24 January 2019

UID