Product Documentation
Abstract
Features and technical details of the IBM eServer 2130 UPS3000X, UPS Extend Run Battery Pack, and NetBAY PDU
Content
General Information
- IBM UPS 3000 XLV, 3000 XHV Operation and Setup Guide
- IBM UPS Extended Run Battery Pack Operation and Setup Guide
- IBM UPS 2130 service part numbers
Now you can protect and substantially extend the backup power runtimes of your mission-critical applications with cost-effective, high-density, uninterruptable power supply (UPS) options. In addition, a new 60-A power distribution unit (PDU) is now available to more efficiently support IBM eServer xSeries rack installations.
The new UPS3000X and UPS Extend Run Battery Pack
- Includes a suite of easy-to-use management tools
- Supports rack-mounting or stand-alone-tower installations
- Saves valuable rack space
- Extends battery run times
The 2 U high, UPS3000X is 33% smaller than its predecessor and provides the highest watt/U backup power of any of our xSeries UPS offerings.
This means you can gain valuable rack space for other components or provide greater backup capacity over that of less powerful UPS offerings
taking the same space. In addition, the UPS3000X takes leadership with high-availability features and functions:
-
Ability to hot-swap:
- Electronic components
- Battery packs
- Support for extend run battery pack options increase backup power runtimes to 90 minutes or more
-
Standard USB and network communications
- Management via serial, USB, or over the network
- Support for unattended shut down of individual systems using network connection
- Ability to remotely control outlets so critical servers can run for a longer period of time
- Highly efficient - Power factor of .95
NETBAY Single Phase 60A Front-end Power Distribution Unit
This new power distribution unit (PDU) is designed to handle the increased power demands of today's Intel-based servers. With a compact 1U mechanical, this modular front-end PDU enables efficient power distribution to xSeries servers while reducing the number of line cords coming from the rack for power. It helps reduce operational costs and rack clutter. This high-amperage product is especially useful for high-density servers such as:
- BladeCenter
- xSeries 345
- xSeries 335
(United States, PCNA, Canada)
(1) On-site applies to UPS3000X.
With respect to on-site service, IBM sends a technician after attempting to diagnose and resolve the problem remotely.
For information on the IBM Statement of Limited Warranty, visit:
http://www.ibm.com/servers/support/machine_warranties/
(Asia Pacific, Latin America, Europe, Middle East, Africa)
(1) For information on warranty, contact your local IBM representative. Copies are
available upon request.
(2) IBM makes no warranties, express or implied, for non-IBM products including the warranties of merchantability and fitness for a particular purpose. IBM is not responsible for warranty, service, or support for this product. Please contact APC for warranty or service details.
At a glance
UPS3000X and UPS Extend Run Battery Pack
New, high-density uninterruptible power supply (UPS) options deliver cost-effective, extended run-time power backup to IBM eServer xSeries servers while consuming less space.
- Up to 3,000 Volt Amps (VA) and 2,850-watt load capacity
- 2 U rack mountable or standalone tower
- USB and network communications standard - Lets you manage and control UPS via serial, USB, or over the network
- UPS management software integrates with IBM Director - Delivers seamless systems management
- Hot-swap battery pack and electronics
- Optional runtime battery packs - Increase run time under full load for 90 minutes or more
- Outlets grouped supporting remote management for individual on/off function - Allows non-critical components to be turned off to extend battery power to critical components
- High-density design - Preserves valuable rack space and allows more room for other rack components
- Three-year, on-site, limited warranty(1)
NETBAY Single Phase 60A Front-end Power Distribution Unit
- Compact 1 U, modular design
- Rack side wall mounting - Saves valuable rack space
- High amperage for rack-dense servers
Product Marketing and FRU Part Number(s)
Part numbers applicable to United States, Latin America, Canada
IBM UPS3000XLV
Marketing part number: 2130R30
IBM UPS3000XHV
Marketing part number: 2130R31
IBM UPS Extend Run Battery Pack
Marketing part number: 32P1692
Field replaceable unit (FRU) part number:
NetBAY Single Phase 60 A Front-End Power Distribution Unit
Marketing part number: 73P5790
Part numbers applicable to Asia Pacific, Europe, Middle East, Africa
IBM UPS3000XLV
Marketing part number: 2130R30
IBM UPS3000XHV
Marketing part number: 2130R31
IBM UPS Extend Run Battery Pack
Marketing part number: 32P1692
Field replaceable unit (FRU) part number:
NetBAY Single Phase 60 A Front-end Power Distribution Unit
Marketing part number: 73P5790(*)
NetBAY Single Phase 60 A Front-end Power Distribution Unit(International)
Marketing part number: 73P5789
2 (*) Not available in all countries
Technical information
Energy Star-compliant: No
NOTE: The Energy Star emblem does not represent EPA endorsement of any product or service.
Performance specifications
UPS3000XLV
Output
-
Rated output power ranges
- 100 V range: 2,400 VA/2,400 watts
- 110 V range: 2,600 VA/2,600 watts
- 120 V range: 2,850 VA/2,850 watts
- 127 V range: 3,000 VA/2,850 watts
- Nominal output voltage - 100, 110, 120, and 127 VAC
-
Three outlet groups:
- Three IEC320, C-13
- Three IEC320, C-13
- Nema L5-20
Input
- Nominal input voltage range - 100, 110, 120, and 127 VAC
- Current - 24 A
- Input frequency - 47/63 Hz (auto adjusting)
- AC inlet - Fixed power cord length; 9 feet; Nema L5-30P plug
-
Input voltage range - default:
- 75-119 VAC
- 79-129 VAC
- 87-140 VAC
- 91-149 VAC
-
Input voltage adjustable range widest on line:
- 70-126 VAC
- 74-135 VAC
- 79-150 VAC
- 84-159 VAC
Efficiency rating
o On battery - 98%
o On line - 96%
UPS3000XHV
Output
- Rated output power - 3,000 VA/2,850 watts
- Nominal output voltage - 200, 208, 220, 230, and 240 VAC
-
Three outlet groups:
- Three IEC320, C-13
- Three IEC320, C-13
- One IEC320 C13 with one IEC320 C19
Input
- Nominal input voltage range - 200, 208, 220, 230, and 240 VAC
- Current - 16 A
- Input frequency - 47/63 Hz (auto adjusting)
- AC inlet - IEC320 C20 (16 A)
-
Input voltage range - default:
- 150-238 VAC
- 149-248 VAC
- 162-267 VAC
- 170-279 VAC
- 177-291 VAC
-
Input voltage adjustable range widest on line:
- 140-251 VAC
- 139-261 VAC
- 153-280 VAC
- 160-292 VAC
- 167-304 VAC
Efficiency rating
- On battery - 90%
- On line - 97%
UPS3000X
Internal battery pack
- Typical backup time at half load - 12 minutes
- Battery type - Maintenance-free sealed lead-acid battery with suspended electrolyte, leakproof
- Typical recharge time - less than 3 hours for 90% of internal batteries
- Battery charger - Temperature compensated; current limited; float charger; 200-watt
Communications and Management
- Interface port - DB-9 RS-232, USB, and built-in 10 baseT and 100 baseT Ethernet interface
-
Management software included:
- PowerChute Business Edition
- PowerChure Network Shutdown
- Control panel - LED status display with load and battery bar-graphs and On-line; On Battery; Replace Battery; and Overload Indicators
- Audible alarm - Alarm when on battery; distinctive low battery alarm; configurable delays
- Emergency Power Off (EPO) - Provided through a cable included with the unit
Surge protection and filtering
- Surge - EN50091-2
-
Overload:
- Online - Alarm at 107%, limited by breakers
- On battery - Shutdown at 107%
-
Thermal protection:
- Two heat sinks monitored for > 90 C
- Fan monitored for operation
Physical Specifications
UPS3000X
Dimensions
- Approximate height: 88.9 mm (3.5 in)
- Approximate width: 430 mm (16.9 in)
- Approximate depth: 685 mm (26.9 in)
- Rack height: 2 U
- Approximate weight: 46.7 kg (103 lbs)
Shipping dimensions
- Approximate height: 250 mm (9.8 in)
- Approximate width: 596 mm (23.5 in)
- Approximate depth: 980 mm (36.6 in)
- Approximate weight: 56.7 kg (125 lb)
Operating environment
- Temperature: 0 to 40 degrees C (32 to 104 degrees F) at 0 to 3000 m (0 to 10,000 ft.)
- Relative humidity: 0% to 95%
- Maximum Altitude: 3,000 m (10,000 ft.)
Electrical specifications
UPS3000XLV
82 - 147 VAC
24 A
50/60 Hz
UPS3000XHV
200 - 240 VAC single phase
16 A
50/60 Hz
- Audible noise at 1 meter - <50 dBA (80% load)
- Audible noise at 1 meter - <55 dBA (100% load)
- Online thermal dissipation - 300 BTU/hr
Agency approvals
UPS3000X
- FCC - Verified to comply with Part 15 of the FCC Rules for a Class A digital device
- UL 1778
- CSA C22.2 Number 950
- NOM
- CE Mark (EN55022 Class A)
- C-Tick Mark (AS/NZS 3548 Class A)
- VDE EN50091-1-1 and 60950
- GOST - Russia
- CCC - China
- Type Approval - South Korea
- Taiwan (BCIQEMC Type Certification)
Hardware requirement
The UPS3000X must be installed in a Netfinity or NetBAY rack or an 19-inch, EIA-310-D industry-standard rack.
Software requirements
The UPS3000X will provide backup power to your server regardless of what operating system is used. However, to enjoy the benefits and manageability features provided with PowerChute Business Edition and Network Shutdown software, included with this UPS, one of the following operating systems must be used:
- Novell NetWare 6.0
- Microsoft Windows NT 4.0
- Windows 2000 (Professional, Server, and Advanced Server)
- Windows XP
- Linux - Red Hat 7.3
Compatibility
The PowerChute Business Edition software is compatible with IBM Director.
The UPS3000X options are compatible with all xSeries and Nefinity servers and IntelliStation workstations and other supporting devices that
require AC power.
The NetBAY Rack PDU is supported with both UPS options.
Document Location
Worldwide
Was this topic helpful?
Document Information
Modified date:
24 January 2019
UID