Off |
(any) |
(any) |
Power is not being provided by any power
supply unit (PSU) in the enclosure, or power is coming from the battery
in the canister.
If at least one PSU is powering the enclosure,
the canister or the enclosure midplane might be faulty.
If both node canisters in an enclosure indicate this
state at the same time, it is more likely that the enclosure midplane
is faulty. Reseat any node canister in this state, as described in Procedure: Reseating a Storwize V7000 Gen2 node canister. If the condition persists,
replace the node canister. If just one canister is affected, see Replacing a Storwize V7000 Gen2 node canister. If both canisters are affected,
see Replacing a Storwize V7000 Gen2 control enclosure midplane assembly.
|
Flashing slowly |
Power is available, but the canister is powered
off. (The main CPU is not running.)
Restart the node canister,
as described in Procedure: Reseating a Storwize V7000 Gen2 node canister.
|
Flashing fast |
The node canister is doing a self test during
start-up.
Wait for the canister to complete its start-up sequence.
|
On |
Off |
Off |
The node canister is in standby mode. (The
Storwize V7000
software
is
not running.)
It is safe to remove or reseat the canister.
Restart
the node canister, as described in Procedure: Reseating a Storwize V7000 Gen2 node canister.
|
Flashing |
The node canister is in candidate state.
The node is not doing I/O in the system.
Unless indicated by
the battery status LED, it is safe to remove or reseat the canister.
See Table 4.
If
the node state is candidate and the system is running on the other
node canister, the candidate node is automatically added to the system.
If
both node canisters are in candidate state, determine whether you
must recover the system or create a new system.
|
Flashing fast |
The node is doing an emergency
shutdown operation, using the battery for power, after detecting a
loss of power from the power supply units.
Wait for the emergency
shutdown operation to complete. If the partner node has also done
an emergency shutdown operation, there was most likely a loss of input
power to both enclosure power supply units and the system restarts
when the input power is restored. Otherwise, there might be a fault
the node canister, enclosure midplane, or power supply units.
|
On |
The
Storwize V7000
software
is
running, and the node canister is participating in the system.
The
canister must not be removed.
This is the normal operational
LED state.
|
On |
Flashing |
Off |
The node canister is in standby mode. (The
Storwize V7000
software
is
not running.)
It is safe to remove or reseat the canister.
|
Flashing |
The Identify function for this canister has
been activated. To determine if it is safe to remove the canister,
use the management GUI or
service assistant to turn off the Identify function, then check the
node canister status LEDs again. |
On |
Flashing |
Flashing fast |
The Identify function for
this canister has been activated.
The node is doing an emergency
shutdown operation, using the battery for power, after detecting a
loss of power from the power supply units.
Wait for the emergency
shutdown operation to complete. If the partner node has also done
an emergency shutdown operation, there was most likely a loss of input
power to both enclosure power supply units and the system restarts
when the input power is restored. Otherwise, there might be a fault
in the power supply units or the node canister.
|
On |
Flashing |
On |
The Identify function for this canister was
activated.
To determine if it is safe to remove the canister,
use the management GUI or
service assistant to turn off the Identify function, then check the
node canister status LEDs, again.
|
On |
On |
Off |
The
Storwize V7000
software
is
not running. The BIOS might have detected a fault.
It is safe
to remove or reseat the canister.
Try reseating the canister,
as described in Procedure: Reseating a Storwize V7000 Gen2 node canister.
If the canister still shows this fault, replace the node canister,
as described in Replacing a Storwize V7000 Gen2 node canister.
|
On |
On |
Flashing |
The node is in service state.
It is
safe to remove or reseat the canister.
See Table 4 to determine
whether the battery charge is insufficient.
Use the service
assistant to identify any node errors or to determine what to do,
see Procedure: Fixing node errors.
If
the node is able to communicate with the configuration node, there
might also be an error alert in the system event log, in which case
you should run the associated fix procedure.
|
On |
On |
Flashing fast |
The node is in service state.
There
is a code update in progress.
The canister must not be removed.
No action is required until the code update completes.
|
On |
On |
On |
The
Storwize V7000
software
is
running but there might be an error alert in the event log, such as
error code 550.
The canister must not be removed.
If possible,
go to the management GUI and
run the fix procedure for the error alerts listed there. If this is
not possible, refer to the service actions for node error 550.
|