Racks can be heavy when populated with several drawers. Use the Weight distribution distances for racks when loaded and Floor loading for racks when loaded tables to ensure proper floor loading and weight distribution.
The 7014-T00, 7014-T42, and 0553 racks can be extremely heavy when several drawers are present. The following table shows the necessary weight distribution distances for the 7014-T00, 7014-T42, and 0553 racks when loaded.
Rack | System weight (1) lb (kg) | Width (2) in. (mm) | Depth (2) in. (mm) | Weight distribution distance (3) | |
---|---|---|---|---|---|
Front and back in. (mm) | Left and right in. (mm) | ||||
7014-T00 (4) | 1795 (816) | 24.5 (623) | 40.2 (1021) | 20.3 (515.6), 18.8 (477.5) | 18.4 (467.4) |
7014-T00 (5) | 1795 (816) | 24.5 (623) | 40.2 (1021) | 20.3 (515.6), 18.8 (477.5) | 0.0 (0.0) |
7014-T00 (6) | 1795 (816) | 24.5 (623) | 40.2 (1021) | 20.3 (515.6), 18.8 (477.5) | 22 (559) |
7014-T42 and 0553 (4) | 2045 (930) | 24.5 (623) | 40.2 (1021) | 20.3 (515.6), 18.8 (477.5) | 18.4 (467.4) |
7014-T42 and 0553 (5) | 2045 (930) | 24.5 (623) | 40.2 (1021) | 20.3 (515.6), 18.8 (477.5) | 0.0 (0.0) |
7014-T42 and 0553(6) | 2045 (930) | 24.5 (623) | 40.2 (1021) | 20.3 (515.6), 18.8 (477.5) | 27 (686) |
The following table shows the necessary floor loading for the 7014-T00, 7014-T42 and 0553 racks when loaded.
Rack | Floor loading | |||
---|---|---|---|---|
Raised kg/m2 | Non-raised kg/m2 | Raised lb/ft2 | Non-raised lb/ft2 | |
7014-T00 (4) | 366.7 | 322.7 | 75 | 66 |
7014-T00 (5) | 734.5 | 690.6 | 150.4 | 141.4 |
7014-T00 (6) | 341 | 297 | 70 | 61 |
7014-T42 and 0553 (4) | 403 | 359 | 82.5 | 73.5 |
7014-T42 and 0553 (5) | 825 | 781 | 169 | 160 |
7014-T42 and 0553(6) | 341.4 | 297.5 | 70 | 61 |
The following notes are for both of the preceding tables.