Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.
| Dimensions | Rack only | Rack with side doors |
|---|---|---|
| Height | 2024.38 mm (79.7 in.) | 2024.38 mm (79.7 in.) |
| Width | 749.3 mm (29.5 in.) | 784.86 mm (30.9 in.) |
| Depth | 1272.54 mm (50.1 in.) | 1272.54 mm (50.1 in.) |
| Dimensions | One frame | Two frame | Front and rear door heat exchanger system unit frame |
|---|---|---|---|
| Height | 2024.38 mm (79.7 in.) | 2024.38 mm (79.7 in.) | 2024.38 mm (79.7 in.) |
| Width | 784.86 mm (30.9 in.) | 1567.18 mm (61.7 in.) | 784.86 mm (30.9 in.) |
| Depth | 1485.9 mm (58.5 in.) | 1485.9 mm (58.5 in.) | 1521.46 mm (59.9 in.) |
| Dimensions | One frame | Two frame | Front and rear door heat exchanger system unit frame |
|---|---|---|---|
| Height | 2024.38 mm (79.7 in.) | 2024.38 mm (79.7 in.) | 2024.38 mm (79.7 in.) |
| Width | 784.86 mm (30.9 in.) | 1567.18 mm (61.7 in.) | 784.86 mm (30.9 in.) |
| Depth | 1805.94 mm (71.1 in.) | 1805.94 mm (71.1 in.) | 1795.78 mm (70.7 in.) |
| Physical characteristics | Weight |
|---|---|
| Fully configured system unit frame | 1451 kg (3200 lb) |
| Physical characteristics | Weight |
|---|---|
| Side covers, pair | 50 kg (110 lb) |
| Slimline door, single | 15 kg (33 lb) |
| Acoustic door, single | 25 kg (56 lb) |
| Physical characteristics | Dimensions |
|---|---|
| Height | 231 cm (91 in.) |
| Width | 94 cm (37 in.) |
| Depth | 162 cm (63.5 in.) |
| Weight | Varies by configuration. The maximum weight is 1724 kg (3800 lb). |
| Electrical and thermal characteristics | Properties | |
|---|---|---|
| Voltage and frequency | 200 - 240 V ac at 50 - 60 Hz | |
| System rating, 5 GHz | 48 A | 80 A |
| System rating, 4.2 GHz | 48 A | 63 A |
| The system rating varies by configuration. See Total system power consumption to determine which system configurations have the higher rating. | ||
| Electrical and thermal characteristics | Properties | |
|---|---|---|
| Voltage and frequency | 480 V ac at 50 - 60 Hz | |
| System rating, 5 GHz | 24 A | 34 A |
| System rating, 4.2 GHz | 24 A | 24 A |
| Electrical and thermal characteristics | Properties | |||
|---|---|---|---|---|
| Voltage and frequency | 200 - 240 V ac at 50 - 60 Hz | 380 - 415 V ac at 50 - 60 Hz | ||
| System rating, 5 GHz | 48 A | 80 A | 34 A | 43 A |
| System rating, 4.2 GHz | 48 A | 63 A | 34 A | 34 A |
| Electrical and thermal characteristics | Properties |
|---|---|
| Maximum power (fully configured 5 GHz system) | 27.7 kW |
| Maximum power (fully configured 4.2 GHz system) | 21.7 kW |
| Power factor | .99 |
| Inrush current | 250 Note: Refer to the Inrush current table.
|
| Thermal output (5 GHz system)1 | 94.5 kBTU/hr |
| Thermal output (4.2 GHz system) 1 | 74.1 kBTU/hr |
Note: The system rating of the 9119-FHA is dependent on
its configuration. See Total system power consumption for
more information.
1Power draw and heat load vary greatly by configuration. When planning for an electrical system, it is important to use maximum values. However, when planning for heat load, the IBM® Systems Energy Estimator allows a user to obtain a heat output estimate based on a specific configuration. See The IBM Systems Energy Estimator web site for more information. |
|
| BPR number | 208 V ac amperage | 208 time (micro seconds) | 480 V ac amperage | 480 time (micro seconds) |
|---|---|---|---|---|
| Zero | 100 | 20 | 120 | 20 |
| One | 110 | 150 | 140 | 150 |
| Two | 140 | 150 | 170 | 150 |
| Three | 170 | 150 | 210 | 150 |
| Four | 200 | 150 | 250 | 150 |
| Environment | Properties | Operating | Storage | Shipping |
|---|---|---|---|---|
| Temperature | 8 - 32-core | 50 - 89.6°F (10 - 32°C) | 33.8 - 140°F (1 - 60°C) | -40 - 140°F (-40 - 60°C) |
| Temperature | 40 - 64-core | 50 - 82.4°F (10 - 28°C) | 33.8 - 140°F (1 - 60°C) | -40 - 140°F (-40 - 60°C) |
| Relative humidity | 20 - 80% | 5 - 80% | 5 - 100% | |
| Maximum altitude | 8 - 32 core | 3048 m (10 000 ft) | ||
| 40 - 64 core | 2133 m (7000 ft) |
| Product configuration | Declared A-Weighted Sound Power Level, LWAd (B) | Declared A-Weighted Sound Pressure Level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idling | Operating | Idling | |
| 5.0-GHz, Typical configuration with acoustical door set: five processor nodes (40-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8.04 | 8.04 | 62 | 62 |
| 5.0-GHz, Typical configuration with nonacoustical (slimline) door set: five processor nodes (40-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 9.06 | 9.06 | 72 | 72 |
| 5.0-GHz, Typical configuration with rear door heat exchanger option and acoustical door set: five processor nodes (40-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8.5 | 8.5 | 70 | 70 |
| 4.2-GHz, Typical configuration with acoustical door set: five processor nodes (40-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 7.75 | 7.75 | 60 | 60 |
| 4.2-GHz, Typical configuration with nonacoustical (slimline) door set: five processor nodes (40-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8.5 | 8.5 | 68 | 68 |
| 4.2-GHz, Typical configuration with rear door heat exchanger option and acoustical door set: five processor nodes (40-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8.04 | 8.04 | 65 | 65 |
1Declared level LWAd is the upper-limit A-weighted sound power level. Declared level LpAm is the mean A-weighted sound pressure level measured at the 1-meter bystander positions. 2All measurements are made in conformance with ISO 7779 and are declared in conformance with ISO 9296. 31 Bel (B) equals 10 Decibels (dB). 4Meets IT Product Noise Limits for, Generally Unattended Data Center, per Statskontoret Technical Standard 26:6. 5Meets IT Product Noise Limits for, Generally Attended Data Center, per Statskontoret Technical Standard 26:6. Note: 6 Government
regulations (such as those prescribed by Occupational Safety and Health
Administration (OSHA) or European Community Directives) might govern
noise level exposure in the workplace and might apply to you and your
server installation. This IBM system is available with an optional
acoustical door feature that can help reduce the noise emitted from
this system. The actual sound pressure levels in your installation
depend on; a variety of factors, including the number of racks in
the installation, the size, materials, the configuration of the room
where you designate the racks to be installed, the noise levels from
other equipment, the room ambient temperature, and employees'
location in relation to the equipment. Compliance with such government
regulations also depends on a variety of additional factors, including
the duration of employees' exposure and whether employees wear
hearing protection. It is recommended that you consult qualified experts
in this field to determine whether you are in compliance with the
applicable regulations.
|
||||
| Product Configuration | Declared A-Weighted Sound Power Level, LWAd (B) | Declared A-Weighted Sound Pressure Level, LpAm (dB) | ||
|---|---|---|---|---|
| Operating | Idling | Operating | Idling | |
| 5.0-GHz, Maximum configuration with acoustical door set: eight processor nodes (64-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8.3 | 8.3 | 65 | 65 |
| 5.0-GHz, Maximum configuration with nonacoustical (slimline) door set: eight processor nodes (64-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 9.36 | 9.36 | 76 | 76 |
| 5.0-GHz, Maximum configuration with rear door heat exchanger option and acoustical door set: eight processor nodes (64-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8.96 | 8.96 | 73 | 73 |
| 4.2-GHz, Maximum configuration with acoustical door set: eight processor nodes (64-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8 | 8 | 62 | 62 |
| 4.2-GHz, Maximum configuration with nonacoustical (slimline) door set: eight processor nodes (64-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 9.06 | 9.06 | 72 | 72 |
| 4.2-GHz, Maximum configuration with rear door heat exchanger option and acoustical door set: eight processor nodes (64-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. | 8.5 | 8.5 | 68 | 68 |
1Declared level LWAd is the upper-limit A-weighted sound power level. Declared level LpAm is the mean A-weighted sound pressure level measured at the 1-meter bystander positions. 2All measurements are made in conformance with ISO 7779 and declared in conformance with ISO 9296. 31 Bel (B) equals 10 Decibels (dB). 4 Meets IT Product Noise Limits for, Generally Unattended Data Center, per Statskontoret Technical Standard 26:6. 5 Meets IT Product Noise Limits for, Generally Attended Data Center, per Statskontoret Technical Standard 26:6. Note: 6 Government
regulations (such as those prescribed by OSHA or European Community
Directives) might govern noise level exposure in the workplace and
might apply to you and your server installation. This IBM system is available with
an optional acoustical door feature that can help reduce the noise
emitted from this system. The actual sound pressure levels in your
installation depend upon a variety of factors, including the number
of racks in the installation, the size, materials, the configuration
of the room where you designate the racks to be installed, the noise
levels from other equipment, the room ambient temperature, and employees'
location in relation to the equipment. Compliance with such government
regulations also depends upon a variety of additional factors, including
the duration of employees' exposure and whether employees wear
hearing protection. It is recommended that you consult qualified experts
in this field to determine whether you are in compliance with the
applicable regulations.
|
||||