Model 9119-FHA server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Rack dimensions
Dimensions Rack only Rack with side doors
Height 2024.38 mm (79.7 in.) 2024.38 mm (79.7 in.)
Width 749.3 mm (29.5 in.) 784.86 mm (30.9 in.)
Depth 1272.54 mm (50.1 in.) 1272.54 mm (50.1 in.)
Table 2. Slimline door dimensions
Dimensions One frame Two frame Front and rear door heat exchanger system unit frame
Height 2024.38 mm (79.7 in.) 2024.38 mm (79.7 in.) 2024.38 mm (79.7 in.)
Width 784.86 mm (30.9 in.) 1567.18 mm (61.7 in.) 784.86 mm (30.9 in.)
Depth 1485.9 mm (58.5 in.) 1485.9 mm (58.5 in.) 1521.46 mm (59.9 in.)
Table 3. Acoustic door dimensions
Dimensions One frame Two frame Front and rear door heat exchanger system unit frame
Height 2024.38 mm (79.7 in.) 2024.38 mm (79.7 in.) 2024.38 mm (79.7 in.)
Width 784.86 mm (30.9 in.) 1567.18 mm (61.7 in.) 784.86 mm (30.9 in.)
Depth 1805.94 mm (71.1 in.) 1805.94 mm (71.1 in.) 1795.78 mm (70.7 in.)
Table 4. Full system weights (no covers)
Physical characteristics Weight
Fully configured system unit frame 1451 kg (3200 lb)
Table 5. Cover weights
Physical characteristics Weight
Side covers, pair 50 kg (110 lb)
Slimline door, single 15 kg (33 lb)
Acoustic door, single 25 kg (56 lb)
Table 6. Shipping dimensions
Physical characteristics Dimensions
Height 231 cm (91 in.)
Width 94 cm (37 in.)
Depth 162 cm (63.5 in.)
Weight Varies by configuration. The maximum weight is 1724 kg (3800 lb).
Table 7. Electrical and thermal characteristics for the US, Canada, Japan
Electrical and thermal characteristics Properties
Voltage and frequency 200 - 240 V ac at 50 - 60 Hz
System rating, 5 GHz 48 A 80 A
System rating, 4.2 GHz 48 A 63 A
The system rating varies by configuration. See Total system power consumption to determine which system configurations have the higher rating.
Table 8. Electrical and thermal characteristics for US high voltage
Electrical and thermal characteristics Properties
Voltage and frequency 480 V ac at 50 - 60 Hz
System rating, 5 GHz 24 A 34 A
System rating, 4.2 GHz 24 A 24 A
Table 9. Electrical and thermal characteristics for the World Trade Corporation
Electrical and thermal characteristics Properties
Voltage and frequency 200 - 240 V ac at 50 - 60 Hz 380 - 415 V ac at 50 - 60 Hz
System rating, 5 GHz 48 A 80 A 34 A 43 A
System rating, 4.2 GHz 48 A 63 A 34 A 34 A
Table 10. Electrical and thermal characteristics (Three-phase)
Electrical and thermal characteristics Properties
Maximum power (fully configured 5 GHz system) 27.7 kW
Maximum power (fully configured 4.2 GHz system) 21.7 kW
Power factor .99
Inrush current 250
Note: Refer to the Inrush current table.
Thermal output (5 GHz system)1 94.5 kBTU/hr
Thermal output (4.2 GHz system) 1 74.1 kBTU/hr
Note: The system rating of the 9119-FHA is dependent on its configuration. See Total system power consumption for more information.

1Power draw and heat load vary greatly by configuration. When planning for an electrical system, it is important to use maximum values. However, when planning for heat load, the IBM® Systems Energy Estimator allows a user to obtain a heat output estimate based on a specific configuration. See The IBM Systems Energy Estimator web site for more information.

Table 11. Inrush current. Inrush current per phase of each line cord to BPE
BPR number 208 V ac amperage 208 time (micro seconds) 480 V ac amperage 480 time (micro seconds)
Zero 100 20 120 20
One 110 150 140 150
Two 140 150 170 150
Three 170 150 210 150
Four 200 150 250 150
Table 12. Environment specifications
Environment Properties Operating Storage Shipping
Temperature 8 - 32-core 50 - 89.6°F (10 - 32°C) 33.8 - 140°F (1 - 60°C) -40 - 140°F (-40 - 60°C)
Temperature 40 - 64-core 50 - 82.4°F (10 - 28°C) 33.8 - 140°F (1 - 60°C) -40 - 140°F (-40 - 60°C)
Relative humidity   20 - 80% 5 - 80% 5 - 100%
Maximum altitude 8 - 32 core 3048 m (10 000 ft)    
40 - 64 core 2133 m (7000 ft)    
Table 13. Declared acoustical noise emissions for typical configuration of the 9119-FHA
Product configuration Declared A-Weighted Sound Power Level, LWAd (B) Declared A-Weighted Sound Pressure Level, LpAm (dB)
Operating Idling Operating Idling
5.0-GHz, Typical configuration with acoustical door set: five processor nodes (40-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8.04 8.04 62 62
5.0-GHz, Typical configuration with nonacoustical (slimline) door set: five processor nodes (40-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. 9.06 9.06 72 72
5.0-GHz, Typical configuration with rear door heat exchanger option and acoustical door set: five processor nodes (40-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8.5 8.5 70 70
4.2-GHz, Typical configuration with acoustical door set: five processor nodes (40-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. 7.75 7.75 60 60
4.2-GHz, Typical configuration with nonacoustical (slimline) door set: five processor nodes (40-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8.5 8.5 68 68
4.2-GHz, Typical configuration with rear door heat exchanger option and acoustical door set: five processor nodes (40-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8.04 8.04 65 65

1Declared level LWAd is the upper-limit A-weighted sound power level. Declared level LpAm is the mean A-weighted sound pressure level measured at the 1-meter bystander positions.

2All measurements are made in conformance with ISO 7779 and are declared in conformance with ISO 9296.

31 Bel (B) equals 10 Decibels (dB).

4Meets IT Product Noise Limits for, Generally Unattended Data Center, per Statskontoret Technical Standard 26:6.

5Meets IT Product Noise Limits for, Generally Attended Data Center, per Statskontoret Technical Standard 26:6.

Note: 6 Government regulations (such as those prescribed by Occupational Safety and Health Administration (OSHA) or European Community Directives) might govern noise level exposure in the workplace and might apply to you and your server installation. This IBM system is available with an optional acoustical door feature that can help reduce the noise emitted from this system. The actual sound pressure levels in your installation depend on; a variety of factors, including the number of racks in the installation, the size, materials, the configuration of the room where you designate the racks to be installed, the noise levels from other equipment, the room ambient temperature, and employees' location in relation to the equipment. Compliance with such government regulations also depends on a variety of additional factors, including the duration of employees' exposure and whether employees wear hearing protection. It is recommended that you consult qualified experts in this field to determine whether you are in compliance with the applicable regulations.
Table 14. Declared acoustical noise emissions for maximum configuration of the 9119-FHA
Product Configuration Declared A-Weighted Sound Power Level, LWAd (B) Declared A-Weighted Sound Pressure Level, LpAm (dB)
Operating Idling Operating Idling
5.0-GHz, Maximum configuration with acoustical door set: eight processor nodes (64-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8.3 8.3 65 65
5.0-GHz, Maximum configuration with nonacoustical (slimline) door set: eight processor nodes (64-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. 9.36 9.36 76 76
5.0-GHz, Maximum configuration with rear door heat exchanger option and acoustical door set: eight processor nodes (64-core), three I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8.96 8.96 73 73
4.2-GHz, Maximum configuration with acoustical door set: eight processor nodes (64-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8 8 62 62
4.2-GHz, Maximum configuration with nonacoustical (slimline) door set: eight processor nodes (64-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. 9.06 9.06 72 72
4.2-GHz, Maximum configuration with rear door heat exchanger option and acoustical door set: eight processor nodes (64-core), two I/O drawers, and bulk power assembly. Blowers at nominal speeds. 8.5 8.5 68 68

1Declared level LWAd is the upper-limit A-weighted sound power level. Declared level LpAm is the mean A-weighted sound pressure level measured at the 1-meter bystander positions.

2All measurements are made in conformance with ISO 7779 and declared in conformance with ISO 9296.

31 Bel (B) equals 10 Decibels (dB).

4 Meets IT Product Noise Limits for, Generally Unattended Data Center, per Statskontoret Technical Standard 26:6.

5 Meets IT Product Noise Limits for, Generally Attended Data Center, per Statskontoret Technical Standard 26:6.

Note: 6 Government regulations (such as those prescribed by OSHA or European Community Directives) might govern noise level exposure in the workplace and might apply to you and your server installation. This IBM system is available with an optional acoustical door feature that can help reduce the noise emitted from this system. The actual sound pressure levels in your installation depend upon a variety of factors, including the number of racks in the installation, the size, materials, the configuration of the room where you designate the racks to be installed, the noise levels from other equipment, the room ambient temperature, and employees' location in relation to the equipment. Compliance with such government regulations also depends upon a variety of additional factors, including the duration of employees' exposure and whether employees wear hearing protection. It is recommended that you consult qualified experts in this field to determine whether you are in compliance with the applicable regulations.

Electromagnetic compatibility compliance

This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 2004/108/EC; BSMI (CNS-13438, 2006 - Certification in Taiwan is for 220 V ac/60 Hz only); AS/NZS CISPR 22: 2006; ICES/NMB-003; Korean EMI/EMC (RLL Notice 2007-69, Notice 2007-71); People's Republic of China Commodity Inspection Law
The 6954 base rack is an optional second base frame with its own separate connection to AC power that is designed for use with model 9119-FHA For a complete set of planning information refer to Planning for 6954 and 6953 racks.