POWER7 information

Model 7014-T42, 7014-B42, and 0553 rack

Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.

Note: Before installing rear door heat exchangers on your 7014-T42 rack, see Planning for the installation of rear door heat exchangers.
Table 1. Dimensions
Dimensions Properties
Height 2015 mm (79.3 in.)
Capacity 42 usable EIA units
Height with PDP - DC only Not applicable
Width without side panels 623 mm (24.5 in.)
Width with side panels 644 mm (25.4 in)
Depth with back door only 1042 mm (41.0 in.)
Depth with back door and front door 1098 mm (43.3 in.)
Depth with sculptured style front door 1147 mm (45.2 in.)
Depth with ERG7 front door 1176 mm (46.3 in.)
Weight base rack (empty) 261 kg (575 lb)
Weight full rack

930 kg (2045 lb)

See 7014-T00, 7014-T42, and 0553 rack weight distribution and floor loading.

Weight slim doors 15.4 kg (34 lb)
Weight side covers 16.3 kg (36 lb)
Weight ERG7 doors 16.8 kg (37 lb)
Table 2. Electrical1
Electrical characteristics Properties
DC rack voltage (nominal) -48 V dc
Power source loading maximum in kVa2 See Power distribution unit and power cord options for 7014, 0551, 0553, and 0555 racks.
Voltage range (V dc) -40 to -60
AC rack 683 Btu/hr
Power source loading maximum in kVa (per PDB)3 135 W
Voltage range (V ac) 200 - 240 V ac
Frequency (Hz) 50 or 60

1Recommended minimum vertical service clearance from floor is 2439 mm (8 ft).

2When installing a model 9117-MMB or 9179-MHB in a 7014-T42 rack, there are restrictions to what height the rack installation can begin so that SMP and FSP flex assemblies are accommodated. The installation configurations are as follows:
  • 16-core configurations (16U) start installation between EIA 1 through EIA 21
  • 12-core configurations (12U) start installation between EIA 1 though EIA 25
  • 8-core configurations (8U) start installation between EIA 1 through EIA 29
  • 4-core configurations (4U) start installation between EIA 1 through EIA 37, EIA 37 through 39 (does not use SMP or SMP flex assemblies)
Associated I/O platforms can be mounted in the upper locations of the rack.

3Acoustic doors are available for the IBM® racks. Feature code 6248 is available for the 0551 and 7014-T00 racks. Feature code 6249 is available for the 0553 and 7014-T42 racks. The overall sound reduction is approximately 6 dB. The doors add 381 mm (15 in.) to the depth of the racks.

Table 3. Service clearances
Front Back Sides
915 mm (36 in.) 915 mm (36 in.) 915 mm (36 in.)
Recommended minimum vertical service clearance from floor is 2439 mm (8 ft).

See your server or hardware specifications for specific requirements.

Rack noise levels are a function of the number and type of drawers installed. See your server or hardware specifications for specific requirements.
Note: Acoustic doors are available for the IBM racks. Feature code 6248 is available for the 0551 and 7014-T00 racks. Feature code 6249 is available for the 0553 and 7014-T42 racks. The overall sound reduction is approximately 6 dB. The doors add 381 mm (15 in.) to the depth of the racks.
Rack airflow requirements are a function of the number and type of drawers installed.
Note: All rack installations require careful site and facilities planning designed to address both the cumulative drawer heat output and provide the airflow volume rates necessary to comply with drawer temperature requirements.
Refer to the individual drawer specifications.

Caster and leveler locations

The following figure provides the caster and leveler locations for the 7014-T00, 7014-T42, 0551, 0553, and 0555 racks.

Figure 1. Caster and leveler locations Caster and leveler locations


Send feedback Rate this page