5079 1.8 m storage/PCI expansion unit

Hardware specifications provide detailed information for your expansion unit, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Hardware specifications

Pictured is the 5079 1.8 m storage/PCI expansion unit.

There are two 5074 expansions (with side covers and casters removed) in a 5079 1.8 m storage/PCI expansion unit.

Dimensions are shown for the 5079 1.8 m Storage/PCI expansion unit only.

5079
Dimensions Height Width Depth
Metric 1800 mm 650 mm 1020 mm
English 71.0 in. 25.5 in. 40.1 in.
 
Maximum configuration weight 726 kg (1600 lb.)
Electrical 50741 50742
kVA 1.100 1.100
Rated Voltage/Frequency 200-240 at 50-60 plus or minus 0.5 Hz 200-240 at 50-60 plus or minus 0.5 Hz
Thermal Output (maximum) 3379 Btu/hr 3379 Btu/hr
Power requirements (maximum) 990 W 990 W
Power factor 0.91 0.91
Inrush current 50 A 50 A
Leakage current (maximum) 3.5 mA 3.5 mA
Phase 1 1
Plug type (Canada and U.S.)

Type 10 lower unit cord feature 1453 (6 ft. 14F1549) and upper unit cord feature 1458 (9 ft. 12J5119, with only 6 ft. usable length),

Type 34 lower unit cord feature 1455 (6 ft. 14F1551) and upper unit cord feature 1459 (9 ft. 55H6644, with only 6 ft. usable length), or

Type 5 lower unit cord feature 1451 (6 ft. 14F1547) and upper unit cord feature 1457 (9 ft. 12J5120, with only 6 ft. usable length)

Power cord length (U.S. only) 1.8 m (6 ft.) 2.7 m (9 ft.) 1.8 m (6 ft.) 2.7 m (9 ft.)
Temperature requirements
Operating 10 degrees to 38 degrees C (50 degrees to 100.4 degrees F)
Nonoperating 1 degrees to 60 degrees C (33.8 degrees to 140 degrees F)
Environment requirements Operating Nonoperating
Noncondensing Humidity 8% to 80% 8% to 80%
Wet bulb temperature 23 degrees C (73.4 degrees F) 27 degrees C (80.6 degrees F)
Maximum altitude 3048 m (10000 ft.)
Noise emissions3 Operating Idle
LWAd Category 2E, General Business 7.0 bels 6.9 bels
<LpA>m 52 dB 52 dB
Service clearances
Front Back Sides Top
762 mm 762 mm 762 mm 762 mm
30 in. 30 in. 30 in. 30 in.
Note:
  1. Because the 5079 1.8 m storage/PCI expansion unit consists of two 5074 storage/PCI expansions, electrical requirements for each 5074 need to be planned for individually. Hence, the (1) and (2) represent the specs for each 5074. The 5074 requires the appropriate receptacle for the power cord included with each 5074.
  2. The usable length of the power cord for the top/upper 5074 is reduced by 1.2 m (4 ft.) because of the routing inside the 1.8 m enclosure. Therefore, a 4.3 m (14 ft.) cord results in a usable length of 3 m (10 ft.), and a 2.7 m (9 ft.) cord results in a usable length of 1.5 m (5 ft.).
  3. For a description of noise emission values, see the Acoustics chapter of the Site Preparation and Physical Planning Guide, SA76-0103.

For information about floor loading, contact your IBM® service or installation planning representative. Because the thickness of the covers are negligible, the height, width, and depth of the overall dimensions may be used in floor loading calculations.