Model 9406-800 and 9406-810 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Table 1. Server specifications

Pictured is the model 9406-800 or 9406-810 server.

The 7116 expansion unit is available with model 9406-800 or 9406-810.

The 7116 expansion unit requires a power cord.

Dimensions are shown for model 9406-800 or 9406-810 only.

model 9406-810

Dimensions 9406-800 and 9406-810 Width 9406-800 and 9406-810 with 7116 Width 9406-800 and 9406-810 Depth 9406-800 and 9406-810 Height Height in 0551 rack2, 4
Metric 366 mm 552 mm 610 mm 610 mm 16 EIA
English 14.5 in. 21.9 in. 24 in. 24 in. 16 U
 
  Model 9406-800 and 9406-810 Model 9406-800 and 9406-810 with 7116
Maximum configuration weight 52.7 kg (116 lb.) 79.6 kg (175 lb.)
Electrical
  model 9406-800 and 9406-810 7116 expansion unit
Maximum kVA (each has its own power cord) 0.421 0.368
Rated voltage and frequency5 100-127/200-240 V ac at 50-60 plus or minus 0.5 Hz
Thermal output (maximum) 1365 Btu/hr 1194 Btu/hr
Power requirements maximum (watts) 400 350
Power factor 0.95
Inrush current 41 A
Leakage current (maximum) 3.5 mA
Phase 1
Compatible plug types 4, 5, 6, 10, 18, 19, 22, 23, 24, 25, 32, 34
Power cord length 2.7 m (9 ft.), 1.8 m (6 ft.) (U.S. and Canada only), 4.3 m (14 ft.) (9406-810 only)
Temperature requirements
Operating 10 degrees to 38 degrees C (50 degrees to 100.4 degrees F)
Nonoperating 1 degrees to 60 degrees C (33.8 degrees to 140 degrees F)
Environment requirements Operating Nonoperating
Noncondensing humidity 8 to 80% 8 to 80%
Wet bulb temperature 23 degrees C (73.4 degrees F) 27 degrees C (80.6 degrees F)
Maximum altitude 3048 m (10000 ft.)
Noise emissions1 Operating Idle
LWAd (Category 2E, General business) 9406-800 or 9406-810 only 5.9 bels 5.8 bels
LWAd (Category 2E, General business) 9406-800 or 9406-810 with 7116 6.3 bels 6.1 bels
LpAm (1-meter bystander) 9406-800 or 9406-810 only 41 dB 40 dB
LpAm (1-meter bystander) 9406-800 or 9406-810 with 7116 45 dB 43 dB
Service clearances
Front Back Sides3 Top3
762 mm 1219 mm 762 mm 762 mm
30 in. 48 in. 30 in. 30 in.

Notes:

  1. For a description of noise emission values, see the Acoustics chapter of the Site Preparation and Physical Planning Guide, SA76-0103.
  2. Feature code 0133 is manufacturing installed in a rack. Feature code 0137 is field installed in a rack.
  3. Side and top clearances are optional when operating.
  4. See 0551 rack configurations for typical configurations when the 0551 rack is populated with various server models.
  5. The power supplies automatically accept any voltage with the published rated voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.

Delivery and subsequent transportation of the equipment

DANGER
Heavy equipment—personal injury or equipment damage might result if mishandled. (D006)

You must prepare your environment to accept the new product based on the installation planning information provided, with assistance from an IBM® Installation Planning Representative (IPR) or IBM authorized service provider. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The IBM authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.