subscribe iconSubscribe to this information

Model 7014-T00 rack

Hardware specifications provide detailed information for your rack, including dimensions, electrical, power, temperature, environment, and service clearances.

Table 1. Rack specifications
Dimensions
Height 1804 mm (71.0 in.)
Capacity 36 usable EIA units
Height with PDP - DC only 1926 mm (75.8 in.)
Width without side panels 623 mm (24.5 in.)
Width with side panels 644 mm (25.4 in)
Depth with rear door only 1042 mm (41.0 in.)
Depth with rear door and front door 1098 mm (43.3 in.)
Depth with sculptured style front door 1147 mm (45.2 in.)
Weight
Base rack (empty) 244 kg (535 lb.)
Full rack

816 kg (1795 lb.)

See 7014-T00, 7014-T42 and 0553 rack weight distribution and floor loading

Electrical1 (sum specified values for drawers or enclosures in rack)
DC rack voltage (nominal) -48 V dc
Power source loading maximum in kVa2 See Power distribution unit and power cord options for 7014, 0551, 0553, or 0555 rack for details
Voltage range (V dc) -40 to -60
AC rack 683 Btu/hr
Power source loading maximum in kVa (per PDB)3 135 W
Voltage range (V ac) 200 to 240
Frequency (Hz) 50 or 60
Temperature requirements See your server or hardware specifications for specific requirements
Humidity requirements See your server or hardware specifications for specific requirements
Noise emissions5 Rack noise levels are a function of the number and type of drawers installed. See your server or hardware specifications for specific requirements
Install or airflow Rack airflow requirements are a function of the number and type of drawers installed4. Refer to the individual drawer specifications.
Service clearances
Front Back Sides
915 mm (36 in.) 915 mm (36 in.) 915 mm (36 in.)
Note:
  1. The total rack power should be derived from the sum of the power used by the drawers in the rack.
  2. The power distribution panel (PDP) on the DC-powered rack can hold up to eighteen (nine per power source) 48-volt, 20- to 50-amp circuit breakers (configuration dependent). Each power source supports up to 8.4 kVa.
  3. Each ac power distribution bus (PDB) can supply 4.8 kVa. A rack can have up to four PDBs as required by the drawers mounted in the rack.
  4. All rack installations require careful site and facilities planning designed to both address the cumulative drawer heat output and provide the airflow volume rates necessary to comply with drawer temperature requirements.
  5. Acoustic doors are available for the IBM® racks. Feature code 6248 is available for the 0551 and 7014-T00 racks. Feature code 6249 is available for the 0553 and 7014-T42 racks. The overall sound reduction is approximately 6 dB. The doors add 381 mm (15 in.) to the depth of the racks.

Send feedback | Rate this page