subscribe iconSubscribe to this information

Power distribution unit and power cord options for 7014, 0551, 0553, or 0555 rack

Power distribution units (PDUs) can be used with the 7014 , 0551, 0553, and 0555 racks. The various configurations and specifications are provided.

The following figure shows the four vertical PDU locations in a rack.

Power distribution unit vertical locations

Power distribution units (PDUs) are required with 7014-T00, 7014-T42 IBM® racks and optional with 7014-B42, 0551, 0553, and 0555 IBM racks, except with a 0578 or 0588 expansion unit. If a PDU is not defaulted or ordered, a power cord is provided with each individual rack-mounted drawer for connection to a country-specific utility mains receptacle or uninterruptible power supply. See the individual rack-mounted drawer specifications for the appropriate power cords.

PDU features

The following table describes the PDU features and the racks on which they are used.
Table 1. PDU features
PDU Number Racks usage
9188 or 7188 universal PDU 7014, 05510553, and 0555 IBM racks.
9176 or 7176 single phase PDU 7014 IBM racks
9177 or 7177 single phase PDU 7014 IBM racks
9178 or 7178 three phase wye PDU 7014 IBM racks
5160 single phase PDU 0551,0553, and 0555 IBM racks
5161 single phase PDU 0551, 0553, and 0555 IBM racks
5163 three phase wye PDU 0551, 0553, and 0555 IBM racks
Power distribution unit plus specifications 7014 IBM racks

9188 or 7188 universal PDU

The 9188 or 7188 PDU is available for the 7014-T00, 7014-T42, 0551, 0553, and 0555 racks.

The following power cords are supported on the 9188 or 7188:

The amperage rating of the PDU is either 16 A, 24 A, or 48 A, single phase or three phase, depending on the power cord.

Note: All power cords are 4.3 m (14 ft.). For installation in Chicago, only 2.8 m (6 ft.) of the 4.3 m (14 ft.) power cord can extend beyond the perimeter of the rack frame. If more than 2.8 m (6 ft.) can exit the rack, retain any additional cordage within the rack frame via Velcro ties in the cable management space until 2.8 (6 ft.) or less exits the rack.
The PDU has twelve customer-usable IEC 320-C13 outlets rated at 200-240 V ac. There are six groups of two outlets fed by six circuit breakers. Each outlet is rated up to 10 A, but each group of two outlets is fed from one 20 A circuit breaker derated to 16 A. The following IEC 320-C13 to IEC 320-C14 power cords are available to supply power from the PDU outlet to the rack-mounted device:
  • 1422 - 3.0 m (10 ft.)
  • 6458 - 4.3 m (14 ft.)
  • 6459 - 3.7 m (12 ft.)
  • 6095 - 3.0 m - 4.3 m (10 ft. - 14 ft.)
  • 9911 - 4.3 m (14 ft.)

PDU outlet graphic

To calculate the power loading requirements and proper loading sequence for the 7188 and 9188 PDU, see Power load calculating for 7188 or 9188 power distribution units.

9176 or 7176 single phase PDU

The 9176 or 7176 PDU is available for the 7014 racks.

The following power cords are supported on the 9176 or 7176:
  • 6442, 9800, or 9824 - 200 V ac; 4.3 m (14 ft.) locking line cord (L6-30P)
  • 6443 or 9801 - 200 V ac; 4.3 m (14 ft.) watertight line cord (3750DP)
  • 6444 or 9822 - 200 V ac; 4.3 m (14 ft.) PDL 250 V ac; 30 A plug
  • 6447 or 9826 - 200 V ac; 4.3 m (14 ft.) PDL 250 V ac; 30 A plug Right Angle
  • 6448 or 9835 - 200 V ac; 4.3 m (14 ft.) 250 V ac, 30 A Korean plug
  • 6449 or 9986 - 200 V ac; 1.8 m (6 ft.) locking line cord (L6-30P) Chicago
  • 6450 or 9987 - 200 V ac; 1.8 m (6 ft.) watertight line cord (3750DP) Chicago

9177 or 7177 single phase PDU

The 9177 or 7177 PDU is available for the 7014 racks.

The following power cord is supported on the 9177 or 7177:
  • 6445 or 9823 - 200 V ac; 4.3 m (14 ft.) (IEC 309, 3-pin, 32 A; plug type 46)

9178 or 7178 three phase wye PDU

The 9178 or 7178 PDU is available for the 7014 racks.

The following power cord is supported on the 9178 or 7178:
  • 400 V ac; 4.3 m (14 ft.) (IEC 309, 5-pin, 16 A; plug type 46)
The PDUs have nine customer-usable IEC 320-C13 outlets rated at 200-240 V ac. There are three groups of three outlets fed by three circuit breakers. Each outlet is rated up to 10 A, but each group of three outlets is fed from one 15 A circuit breaker. The following IEC 320-C13 to IEC 320-C14 power cords are available to supply from the PDU outlet to the rack-mounted device:
  • 6095 - 3.0 m – 4.3 m (10 ft. – 14 ft.)
  • 9911 - 4.3 m (14 ft.)

Type 7 primary power distribution units

5160 single phase PDU

The 5160 PDU is available for the 0551 and 0553 racks.

The following power cords are supported on the 5160:
  • 1426 - 200 V ac; 4.3 m (14 ft.) locking power cord (L6-30P)
  • 1427 - 200 V ac; 4.3 m (14 ft.) watertight power cord (3750DP)
  • 1446 - 200 V ac; 4.3 m (14 ft.) 30 A Korean (250 V ac, 30 A Korean plug)
  • 1447 - 200 V ac; 4.3 m (14 ft.) 30 A AU (PDL 250 V ac; 30 A plug)
  • 1448 - 200 V ac; 4.3 m (14 ft.) 30 A NZ (PDL 250 V ac; 30 A plug)

5161 single phase PDU

The 5161 PDU is available for the 0551 and 0553 racks.

The following power cord is supported on the 5161:
  • 1449 - 200 V ac; 4.3 m (14 ft.) (IEC 309, 3-pin, 32 A; plug type 46)

5163 three phase wye PDU

The 5163 PDU is available for the 0551 and 0553 racks.

The following power cord is supported on the 5163:
  • 1477 - 400 V ac; 4.3 m (14 ft.) (IEC 309, 5-pin, 16 A; plug type 46)
The PDUs have six customer-usable IEC 320-C13 outlets rated at 200-240 V ac. Each outlet is rated 8 A and is protected by a circuit breaker. The following IEC 320-C13 to IEC 320-C14 power cords are available to supply from the PDU outlet to the rack-mounted device:
  • 1422 - 3.0 m (10 ft.)
  • 6458 - 4.3 m (14 ft.)
  • 6459 - 3.7 m (12 ft.)

Type 6 power distribution unit

Typical rack and PDU configurations

See 0551, 0553, 7014, or 0555 rack configurations for typical configurations and PDUs when the 0551, 0553, 7014, or 0555 rack is populated with various server models.

Power distribution unit plus specifications

The power distribution unit plus (PDU+) has power-monitoring capabilities. The PDU+ is an intelligent ac power distribution unit (PDU+) that monitors the amount of power being used by the devices that are plugged into it. The PDU+ provides twelve C13 power outlets and receives power through a Souriau UTG connector. The PDU+ can be used in many geographies and for many applications by varying the PDU-to-wall power cord, which must be ordered separately. Each PDU+ requires one PDU-to-wall power cord. When the PDU+ is connected to a dedicated power source, it conforms to UL60950, CSA C22.2-60950, EN-60950, and IEC-60950 standards.

The following feature codes are available for the PDU+.
  • 5889 - First PDU+ (with 12 IEC 320-C13 outlets) installed on a 7014-S25, 7014-T00, or 7014-T42 rack
  • 7109 - Additional PDU+ (with 12 IEC 320-C13 outlets) installed on a 7014-S25, 7014-T00, or 7014-T42 rack
  • 7189 - PDU+ ( with six IEC 320-C19 outlets) installed on a 7014-B42 rack
  • 7196 - PDU+ (with six IEC320-C19 outlets with an attached power cord) installed on a 7014-B42 rack
Table 2. PDU+ specifications
Height 43.9 mm (1.73 in.)
Width 447 mm (17.6 in.)
Depth 350 mm (13.78 in.)
Additional clearance

25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets

Weight (not including power cord) 6.3 kg (13.8 lb.)
Weight of power cord (approximate) 5.4 kg (11.8 lb.)
Operating temperature at 0 - 914 m (0 - 3000 ft) (room ambient) 10 - 35 degrees C (50 - 95 degrees F)
Operating temperature at 914 - 2133 m (3000 - 7000 ft) (room ambient) 10 - 32 degrees C (50 - 90 degrees F)
Operating humidity 8 - 80 % (noncondensing)
Localized air temperature in PDU 60 degrees C (140 degrees F) maximum
Rated voltage for 5889, 7109 and 7189 PDU+
  • 220 - 240 or 380 - 415 V, three phase, Wye, 32 A
  • 220 - 240 or 380 - 415 V, three phase, Wye, 16A
  • 220 - 240 V, single phase, 32 A
  • 220 - 240 V, single phase, 63 A
  • 200 - 208 V, single phase, 24 A
  • 200 - 208 V, single phase, 48 A
Rated voltage for 7196 PDU+ 200 - 208 V, three phase, Delta, 48 A
Rated frequency (all feature codes) 50 - 60 Hz
Circuit breakers Six double-pole branch rated circuit breakers rated at 20 A
Power cord features for 5889 and 7109 PDU+ 6489, 6491, 6492, 6653, 6654, 6655, 6656, 6657, and 6658
Power cord features for 7189 PDU+ 6489, 6491, 6492, 6653
Power cord features for 7196 PDU+ Fixed power cord with IEC 309, 3P+G, 60 A plug
Power outlets for feature codes 7189 and 7196

Six IEC 320-C19 outlets rated at
16 A (VDE) or 20 A (UL/CSA)

Power outlets for feature codes 5889 and 7109

12 IEC 320-C13 outlets rated at
10 A (VDE) or 15 A (UL/CSA)

To use the power-monitoring capabilities of the PDU+, see Setting up power monitoring using the PDU+


Send feedback | Rate this page