Power distribution units (PDUs) can be used with the 7014 ,
0551, 0553, and 0555 racks.
The various configurations and specifications are provided.
The following figure shows the four vertical PDU locations in
a rack.
Power distribution units (PDUs)
are required with 7014-T00, 7014-T42 IBM® racks and optional with 7014-B42, 0551, 0553, and 0555 IBM racks,
except with a 0578 or 0588 expansion unit. If a PDU is not defaulted
or ordered, a power cord is provided with each individual rack-mounted drawer
for connection to a country-specific utility mains receptacle or uninterruptible
power supply. See the individual rack-mounted drawer specifications for the
appropriate power cords.
PDU features
The following table describes the PDU
features and the racks on which they are used.
9188 or 7188 universal PDU
The 9188
or 7188 PDU is available for the 7014-T00, 7014-T42, 0551, 0553,
and 0555 racks.
The
following power cords are supported on the 9188 or 7188:
- 6489 - 4.3 m (14 ft.) 3-phase IEC309 3P+N+G
32 A plug (PDU rated 24 A per phase)
- 6491 - 4.3 m (14 ft.) 1-phase IEC309 P+N+G
63 A plug (PDU rated 48 A)
- 6492 - 4.3 m (14 ft.) 1-phase IEC309 2P+G
60 A plug (PDU rated 48 A)
- 6653 -
4.3 m (14 ft.) 3-phase IEC 309 3P+N+G 16 A plug (PDU rated 16 A per phase)
- 6654 -
4.3 m (14 ft.) 1-phase NEMA L6-30 plug (PDU rated 24 A)
- 6655 -
4.3 m (14 ft.) 1-phase Russell Stoll 3750DP plug (PDU rated 24 A)
- 6656 -
4.3 m (14 ft.) 1-phase IEC 309 P+N+G 32A plug (PDU rated 24 A)
- 6657 -
4.3 m (14 ft.) 1-phase PDL 250 V ac; 30 A plug (PDU rated 24 A)
- 6658 -
4.3 m (14 ft.) 1-phase 250 V ac, 30 A Korean plug (PDU rated 24 A)
The amperage rating of the PDU is either 16 A, 24 A, or 48 A, single
phase or three phase, depending on the power cord.
Note: All power cords
are 4.3 m (14 ft.). For installation in Chicago, only 2.8 m (6 ft.) of the
4.3 m (14 ft.) power cord can extend beyond the perimeter of the rack frame.
If more than 2.8 m (6 ft.) can exit the rack, retain any additional cordage
within the rack frame via Velcro ties in the cable management space until
2.8 (6 ft.) or less exits the rack.
The PDU has twelve customer-usable
IEC 320-C13 outlets rated at 200-240 V ac. There are six groups of two outlets
fed by six circuit breakers. Each outlet is rated up to 10 A, but each group
of two outlets is fed from one 20 A circuit breaker derated to 16 A. The following
IEC 320-C13 to IEC 320-C14 power cords are available to supply power from
the PDU outlet to the rack-mounted device:
- 1422 - 3.0 m (10 ft.)
- 6458 - 4.3 m (14 ft.)
- 6459 - 3.7 m (12 ft.)
- 6095 - 3.0 m - 4.3 m (10 ft. - 14 ft.)
- 9911 - 4.3 m (14 ft.)
To calculate the power loading requirements and
proper loading sequence for the 7188 and 9188 PDU, see Power
load calculating for 7188 or 9188 power distribution units.
9176 or 7176 single phase PDU
The
9176 or 7176 PDU is available for the 7014 racks.
The following power
cords are supported on the 9176 or 7176:
- 6442, 9800, or 9824 - 200 V ac; 4.3 m (14 ft.) locking line cord (L6-30P)
- 6443 or 9801 - 200 V ac; 4.3 m (14 ft.) watertight line cord (3750DP)
- 6444 or 9822 - 200 V ac; 4.3 m (14 ft.) PDL 250 V ac; 30 A plug
- 6447 or 9826 - 200 V ac; 4.3 m (14 ft.) PDL 250 V ac; 30 A plug Right
Angle
- 6448 or 9835 - 200 V ac; 4.3 m (14 ft.) 250 V ac, 30 A Korean plug
- 6449 or 9986 - 200 V ac; 1.8 m (6 ft.) locking line cord (L6-30P) Chicago
- 6450 or 9987 - 200 V ac; 1.8 m (6 ft.) watertight line cord (3750DP) Chicago
9177 or 7177 single phase PDU
The
9177 or 7177 PDU is available for the 7014 racks.
The following power
cord is supported on the 9177 or 7177:
- 6445 or 9823 - 200 V ac; 4.3 m (14 ft.) (IEC 309, 3-pin, 32 A; plug type
46)
9178 or 7178 three phase wye PDU
The
9178 or 7178 PDU is available for the 7014 racks.
The following power
cord is supported on the 9178 or 7178:
- 400 V ac; 4.3 m (14 ft.) (IEC 309, 5-pin, 16 A; plug type 46)
The PDUs have nine customer-usable IEC 320-C13 outlets rated
at 200-240 V ac. There are three groups of three outlets fed by three circuit
breakers. Each outlet is rated up to 10 A, but each group of three outlets
is fed from one 15 A circuit breaker. The following IEC 320-C13 to IEC 320-C14
power cords are available to supply from the PDU outlet to the rack-mounted
device:
- 6095 - 3.0 m – 4.3 m (10 ft. – 14 ft.)
- 9911 - 4.3 m (14 ft.)
5160 single phase PDU
The 5160 PDU
is available for the 0551 and 0553 racks.
The
following power cords are supported on the 5160:
- 1426 - 200 V ac; 4.3 m (14 ft.) locking power cord (L6-30P)
- 1427 - 200 V ac; 4.3 m (14 ft.) watertight power cord (3750DP)
- 1446 - 200 V ac; 4.3 m (14 ft.) 30 A Korean (250 V ac, 30 A Korean plug)
- 1447 - 200 V ac; 4.3 m (14 ft.) 30 A AU (PDL 250 V ac; 30 A plug)
- 1448 - 200 V ac; 4.3 m (14 ft.) 30 A NZ (PDL 250 V ac; 30 A plug)
5161 single phase PDU
The 5161 PDU
is available for the 0551 and 0553 racks.
The
following power cord is supported on the 5161:
- 1449 - 200 V ac; 4.3 m (14 ft.) (IEC 309, 3-pin, 32 A; plug type 46)
5163 three phase wye PDU
The 5163
PDU is available for the 0551 and 0553 racks.
The
following power cord is supported on the 5163:
- 1477 - 400 V ac; 4.3 m (14 ft.) (IEC 309, 5-pin, 16 A; plug type 46)
The PDUs have six customer-usable IEC 320-C13 outlets rated at
200-240 V ac. Each outlet is rated 8 A and is protected by a circuit breaker.
The following IEC 320-C13 to IEC 320-C14 power cords are available to supply
from the PDU outlet to the rack-mounted device:
- 1422 - 3.0 m (10 ft.)
- 6458 - 4.3 m (14 ft.)
- 6459 - 3.7 m (12 ft.)
Power distribution unit
plus specifications
The power distribution unit plus (PDU+) has power-monitoring
capabilities. The PDU+ is
an intelligent ac power distribution unit (PDU+) that monitors the amount
of power being used by the devices that are plugged into it. The PDU+ provides twelve C13
power outlets and receives power through a Souriau UTG connector. The PDU+ can be used in many
geographies and for many applications by varying the PDU-to-wall power cord,
which must be ordered separately. Each PDU+ requires
one PDU-to-wall power cord. When the PDU+ is
connected to a dedicated power source, it conforms to UL60950, CSA C22.2-60950,
EN-60950, and IEC-60950 standards.
The following feature codes are available
for the
PDU+.
- 5889 - First PDU+ (with
12 IEC 320-C13 outlets) installed on a 7014-S25, 7014-T00, or 7014-T42 rack
- 7109 - Additional PDU+ (with
12 IEC 320-C13 outlets) installed on a 7014-S25, 7014-T00, or 7014-T42 rack
- 7189 - PDU+ (
with six IEC 320-C19 outlets) installed on a 7014-B42 rack
- 7196 - PDU+ (with
six IEC320-C19 outlets with an attached power cord) installed on a 7014-B42
rack
Table 2. PDU+ specificationsHeight |
43.9 mm (1.73 in.) |
Width |
447 mm (17.6 in.) |
Depth |
350 mm (13.78 in.) |
Additional clearance |
25 mm (0.98 in.) for circuit breakers
3 mm (0.12 in.) for outlets
|
Weight (not including power cord) |
6.3 kg (13.8 lb.) |
Weight of power cord (approximate) |
5.4 kg (11.8 lb.) |
Operating temperature at 0 - 914 m (0 - 3000 ft) (room
ambient) |
10 - 35 degrees C (50 - 95 degrees F) |
Operating temperature at 914 - 2133 m (3000 - 7000 ft)
(room ambient) |
10 - 32 degrees C (50 - 90 degrees F) |
Operating humidity |
8 - 80 % (noncondensing) |
Localized air temperature in PDU |
60 degrees C (140 degrees F) maximum |
Rated voltage for 5889, 7109 and 7189 PDU+ |
- 220 - 240 or 380 - 415 V, three phase, Wye, 32 A
- 220 - 240 or 380 - 415 V, three phase, Wye, 16A
- 220 - 240 V, single phase, 32 A
- 220 - 240 V, single phase, 63 A
- 200 - 208 V, single phase, 24 A
- 200 - 208 V, single phase, 48 A
|
Rated voltage for 7196 PDU+ |
200 - 208 V, three phase, Delta, 48 A |
Rated frequency (all feature codes) |
50 - 60 Hz |
Circuit breakers |
Six double-pole branch rated circuit breakers rated
at 20 A |
Power cord features for 5889 and 7109 PDU+ |
6489, 6491, 6492, 6653, 6654, 6655, 6656, 6657, and 6658 |
Power cord features for 7189 PDU+ |
6489, 6491, 6492, 6653 |
Power cord features for 7196 PDU+ |
Fixed power cord with IEC 309, 3P+G, 60 A plug |
Power outlets for feature codes 7189 and 7196 |
Six IEC 320-C19 outlets rated at
16 A (VDE) or 20 A (UL/CSA)
|
Power outlets for feature codes 5889 and 7109 |
12 IEC 320-C13 outlets rated at
10 A (VDE) or 15 A (UL/CSA)
|
To use the power-monitoring capabilities of the PDU+,
see Setting
up power monitoring using the PDU+