System specifications for the IBM Elastic Storage Server (5147 and 5148)
IBM® Elastic Storage Server specifications provide detailed information for your system, including dimensions, electrical, power, temperature, environmental requirements, and noise emissions.
Use the following specifications to plan for your server.
Width | Depth | Height | EIA units | Weight |
---|---|---|---|---|
644 mm (25.4 in.) | 1098 mm (43.3 in.) | 2015 mm (79.3 in.) | 42 | 289 kg (636 lb) |
|
Building Block |
Width |
Depth |
Height |
EIA units |
Weight (Maximum) |
Airflow information |
---|---|---|---|---|---|---|
IBM Elastic Storage Server Management Server (5148-21L) |
443 mm (17.5 in.) |
755 mm (29.7 in.) |
87 mm (3.5 in.) |
2 |
28.6 kg (63 lb) |
80 cubic feet per minute (CFM) typical 230 CFM maximum |
IBM Elastic Storage Server Data Server (5148-22L) |
443 mm (17.5 in.) |
755 mm (29.7 in.) |
87 mm (3.5 in.) |
2 |
28.6 kg (63 lb) |
80 CFM typical 230 CFM maximum |
IBM Elastic Storage Server expansion model 024 (5147-024) |
448.6 mm (17.7 in.) |
744.22 mm (29.3 in.) |
87.4 mm (3.4 in.) |
2 |
31.1 kg (68.6 lb) |
|
IBM Elastic Storage Server expansion model 084 (5147-084) |
482.6 mm (19.0 in.) |
915 mm (36.0 in.) |
222.3 mm (8.75 in.) |
5 |
135 kg (298 lb) |
254 CFM (with all fans running) |
IBM Elastic Storage Server expansion model 106 (5147-106) |
441 mm (17.36 in.) |
1139 mm (44.84 in.) |
176.4 mm (6.94 in.) |
4 |
With drives: 145.6 kg (321 lb) Without drives: 43.1 kg (95 lb) |
100 CFM typical 200 CFM maximum |
Mellanox Switch (8828-E36) |
427 mm (16.84 in.) |
627 mm (24.7 in.) |
43.68 mm (1.72 in.) |
1 |
9.5 kg (21 lb) |
|
Mellanox SX1710 1U Switch Systems (8831-NF2) |
428 mm (16.85 in.) |
685 mm (27.0 in.) |
43.6 mm (1.716 in.) |
1 |
10.9 kg (24 lb) |
|
Mellanox 1U Switch (8831-F36) |
427 mm (16.84 in.) |
627 mm (24.7 in.) |
43.68 mm (1.72 in.) |
1 |
9.3 kg (20.5 lb) |
|
Mellanox Switch (8831-S48) |
428 mm (16.85 in.) |
426.7 mm (16.8 in.) |
43.68 mm (1.72 in.) |
1 |
8.8 kg (19.5 lb) |
|
Mellanox Switch (8831-S52) |
440 mm (17.3 in.) |
350 mm (13.77 in.) |
45 mm (1.7 in.) |
1 |
5.4 kg (12 lb) |
40 CFM typical 80 CFM maximum |
IBM RackSwitch G8052 (7120-48E) |
439 mm (17.3 in.) |
445 mm (17.5 in.) |
44 mm (1.73 in.) |
1 |
5.4 kg (12 lb) |
|
IBM RackSwitch G8264 (7120-64C) |
439 mm (17.3 in.) |
513 mm (20.2 in.) |
44 mm (1.73 in.) |
1 |
6.4 kg (14 lb) |
|
7042-T42 rack (with side covers) |
644 mm (25.4 in.) |
1016 mm (40.0 in.) |
2015 mm (79.3 in.) |
42 |
261 kg (575 lb) |
|
7063-S42 rack (without side covers) Side covers are 12 mm (0.25 in.) and 20 kg (44 lb) each. |
600 mm (23.6 in.) |
1070 mm (42.1 in.) |
2020 mm (79.5 in.) |
42 |
166 kg (365 lb) |
Building Block |
Power (Watts) |
Maximum kVA |
Thermal (BTU/hr) |
Amperes (A) at 200 Volts (V) |
---|---|---|---|---|
665 W |
0.679 |
2270 BTU/hr |
3.39 |
|
1250 W |
1.276 |
4266 BTU/hr |
6.38 |
|
275 W |
0.280 |
939 BTU/hr |
1.40 |
|
1225 W |
1.269 |
4181 BTU/hr |
6.35 |
|
1568 W |
1.650 |
5350 BTU/hr |
8.25 |
|
231 W |
0.236 |
788 BTU/hr |
1.18 |
|
235 W |
0.247 |
802 BTU/hr |
1.24 |
|
231 W |
0.243 |
788 BTU/hr |
1.22 |
|
300 W |
0.316 |
1024 BTU/hr |
1.58 |
|
Mellanox Switch (8831-S52) |
92 W |
0.097 |
314 BTU/hr |
0.48 |
200 W |
0.211 |
683 BTU/hr |
1.05 |
|
375 W |
0.395 |
1280 BTU/hr |
1.97 |
|
|
Environment | Recommended operating requirements | Allowable operating requirements | Nonoperating requirements |
---|---|---|---|
ASHRAE class | A2 | ||
Airflow direction1 | Front-to-back | ||
Temperature2 | 18°C - 27°C (64°F - 80°F) | 10°C - 35°C (50°F - 95°F) | 5°C - 45°C (41°F - 113°F) |
Humidity range | 5.5°C (42°F) dew point (DP) to 60% relative humidity (RH) and 15°C (59°F) dew point | 20% - 80% RH | 8% - 80% RH |
Maximum rate of change | 5°C per 20 hrs | ||
Maximum dew point | 21°C (70°F) | 27°C (80°F) | |
Maximum operating altitude | 3050 m (10000 ft) | ||
Shipping temperature | -40°C to 60°C (-40°F to 140°F) | ||
Shipping relative humidity | 5% - 100% | ||
|
Electromagnetic compatibility compliance
Electromagnetic compatibility compliance: CISPR 22; CISPR 24; FCC, CFR 47, Part 15 (US); VCCI (Japan); Directive 2004/108/EC (EEA); ICES-003, Issue 4 (Canada); ACMA radio communications standard (Australia, New Zealand); CNS 13438 (Taiwan); Radio Waves Act, MIC Rule No. 210 (Korea); Commodity Inspection Law (China); TCVN 7189 (Vietnam); MoCI (Saudi Arabia); SI 961 (Israel); GOST R 51318.22, 51318.24 (Russia).
Product safety compliance
Product safety compliance: IEC 60950-1; UL 60950-1; CSA 60950-1.
Delivery and subsequent transportation of the equipment
You must prepare your environment, with assistance from an authorized service provider, to accept the new product based on the installation planning information provided. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If, for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers can transport the equipment. The authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.