System specifications for the IBM Elastic Storage Server (5147 and 5148)

IBM® Elastic Storage Server specifications provide detailed information for your system, including dimensions, electrical, power, temperature, environmental requirements, and noise emissions.

Note: Each IBM Elastic Storage Server must be installed in a rack with a front door, rear door, and side panels for electromagnetic interference (EMI) compliance.

Use the following specifications to plan for your server.

Table 1. Empty rack dimensions1
Width Depth Height EIA units Weight
644 mm (25.4 in.) 1098 mm (43.3 in.) 2015 mm (79.3 in.) 42 289 kg (636 lb)
  1. The rack is equivalent to a 7014-T42 rack. For more information about the 7014-T42 rack, see Model 7014-T42, 7014-B42, and 0553.
Table 2. IBM Elastic Storage Server building block dimensions and airflow information

Building Block

Width

Depth

Height

EIA units

Weight (Maximum)

Airflow information

IBM Elastic Storage Server Management Server (5148-21L)

443 mm (17.5 in.)

755 mm (29.7 in.)

87 mm (3.5 in.)

2

28.6 kg (63 lb)

80 cubic feet per minute (CFM) typical

230 CFM maximum

IBM Elastic Storage Server Data Server (5148-22L)

443 mm (17.5 in.)

755 mm (29.7 in.)

87 mm (3.5 in.)

2

28.6 kg (63 lb)

80 CFM typical

230 CFM maximum

IBM Elastic Storage Server expansion model 024 (5147-024)

448.6 mm (17.7 in.)

744.22 mm (29.3 in.)

87.4 mm (3.4 in.)

2

31.1 kg (68.6 lb)

 

IBM Elastic Storage Server expansion model 084 (5147-084)

482.6 mm (19.0 in.)

915 mm (36.0 in.)

222.3 mm (8.75 in.)

5

135 kg (298 lb)

254 CFM (with all fans running)

IBM Elastic Storage Server expansion model 106 (5147-106)

441 mm (17.36 in.)

1139 mm (44.84 in.)

176.4 mm (6.94 in.)

4

With drives: 145.6 kg (321 lb)

Without drives: 43.1 kg (95 lb)

100 CFM typical

200 CFM maximum

Mellanox Switch (8828-E36)

427 mm (16.84 in.)

627 mm (24.7 in.)

43.68 mm (1.72 in.)

1

9.5 kg (21 lb)

 

Mellanox SX1710 1U Switch Systems (8831-NF2)

428 mm (16.85 in.)

685 mm (27.0 in.)

43.6 mm (1.716 in.)

1

10.9 kg (24 lb)

 

Mellanox 1U Switch (8831-F36)

427 mm (16.84 in.)

627 mm (24.7 in.)

43.68 mm (1.72 in.)

1

9.3 kg (20.5 lb)

 

Mellanox Switch (8831-S48)

428 mm (16.85 in.)

426.7 mm (16.8 in.)

43.68 mm (1.72 in.)

1

8.8 kg (19.5 lb)

 

Mellanox Switch (8831-S52)

440 mm (17.3 in.)

350 mm (13.77 in.)

45 mm (1.7 in.)

1

5.4 kg (12 lb)

40 CFM typical

80 CFM maximum

IBM RackSwitch G8052 (7120-48E)

439 mm (17.3 in.)

445 mm (17.5 in.)

44 mm (1.73 in.)

1

5.4 kg (12 lb)

 

IBM RackSwitch G8264 (7120-64C)

439 mm (17.3 in.)

513 mm (20.2 in.)

44 mm (1.73 in.)

1

6.4 kg (14 lb)

 

7042-T42 rack (with side covers)

644 mm (25.4 in.)

1016 mm (40.0 in.)

2015 mm (79.3 in.)

42

261 kg (575 lb)

 

7063-S42 rack (without side covers)

Side covers are 12 mm (0.25 in.) and 20 kg (44 lb) each.

600 mm (23.6 in.)

1070 mm (42.1 in.)

2020 mm (79.5 in.)

42

166 kg (365 lb)

 
Table 3. IBM Elastic Storage Server building block electrical specifications1,2,3

Building Block

Power (Watts)

Maximum kVA

Thermal (BTU/hr)

Amperes (A) at 200 Volts (V)

IBM Elastic Storage Server Management Server (5148-21L)

665 W

0.679

2270 BTU/hr

3.39

IBM Elastic Storage Server Data Server (5148-22L)

1250 W

1.276

4266 BTU/hr

6.38

IBM Elastic Storage Server expansion model 024 (5147-024)

275 W

0.280

939 BTU/hr

1.40

IBM Elastic Storage Server expansion model 084 (5147-084)

1225 W

1.269

4181 BTU/hr

6.35

IBM Elastic Storage Server expansion model 106 (5147-106)

1568 W

1.650

5350 BTU/hr

8.25

Mellanox Switch (8828-E36)

231 W

0.236

788 BTU/hr

1.18

Mellanox SX1710 1U Switch Systems (8831-NF2)

235 W

0.247

802 BTU/hr

1.24

Mellanox 1U Switch (8831-F36)

231 W

0.243

788 BTU/hr

1.22

Mellanox Switch (8831-S48)

300 W

0.316

1024 BTU/hr

1.58

Mellanox Switch (8831-S52)

92 W

0.097

314 BTU/hr

0.48

IBM RackSwitch G8052 (7120-48E)

200 W

0.211

683 BTU/hr

1.05

IBM RackSwitch G8264 (7120-64C)

375 W

0.395

1280 BTU/hr

1.97

  1. The input voltage is based on the power distribution unit (PDU) power cord. For more information, see Power distribution unit and power cord options for 7014, 0551, 0553, and 0555 racks.
  2. All drawers that are mounted in the rack are rated 200 - 240 V ac. The power supplies automatically accept any voltage within the rated voltage range. With dual power supplies installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  3. DC power is not supported.
Table 4. Environment requirements
Environment Recommended operating requirements Allowable operating requirements Nonoperating requirements
ASHRAE class   A2  
Airflow direction1   Front-to-back  
Temperature2 18°C - 27°C (64°F - 80°F) 10°C - 35°C (50°F - 95°F) 5°C - 45°C (41°F - 113°F)
Humidity range 5.5°C (42°F) dew point (DP) to 60% relative humidity (RH) and 15°C (59°F) dew point 20% - 80% RH 8% - 80% RH
Maximum rate of change   5°C per 20 hrs  
Maximum dew point   21°C (70°F) 27°C (80°F) 
Maximum operating altitude   3050 m (10000 ft)  
Shipping temperature     -40°C to 60°C (-40°F to 140°F)
Shipping relative humidity     5% - 100%
  1. Nominal cubic feet per minute (CFM) is approximately 2030. Maximum CFM is approximately 4025.
  2. Derate maximum allowable dry-bulb temperature 1°C per 175 m above 950 m.

Electromagnetic compatibility compliance

Electromagnetic compatibility compliance: CISPR 22; CISPR 24; FCC, CFR 47, Part 15 (US); VCCI (Japan); Directive 2004/108/EC (EEA); ICES-003, Issue 4 (Canada); ACMA radio communications standard (Australia, New Zealand); CNS 13438 (Taiwan); Radio Waves Act, MIC Rule No. 210 (Korea); Commodity Inspection Law (China); TCVN 7189 (Vietnam); MoCI (Saudi Arabia); SI 961 (Israel); GOST R 51318.22, 51318.24 (Russia).

Product safety compliance

Product safety compliance: IEC 60950-1; UL 60950-1; CSA 60950-1.

Delivery and subsequent transportation of the equipment

DANGER
Heavy equipment—personal injury or equipment damage might result if mishandled. (D006)

You must prepare your environment, with assistance from an authorized service provider, to accept the new product based on the installation planning information provided. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If, for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers can transport the equipment. The authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.




Last updated: Wed, July 31, 2019