Model 0551 and 9406-270 rack

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Pictured is model 0551 and 9406-270 rack. The 0551 consists of two models 9406-270 with 7104 system unit expansions installed in a 1.8 m rack. Specify code 0121 represents the first model 9406-270 in the rack (on the bottom). Specify code 0122 represents the second model 9406-270 in the rack (on the top).

Figure 1. Model 0551 and 9406-270 rack
Model 0551 and 9406-270 rack
Table 1. Dimensions
Maximum configuration weight1 Height Width Depth
403 kg (885 lb) 1800 mm (71.0 in.) 650 mm (25.5 in.) 1020 mm (40.0 in.)
1Side and top clearances are optional when operating.
Table 2. Electrical
Electrical characteristics Properties
kVA (maximum) 0.789
Rated voltage and frequency 100 - 127 or 200 - 240 V ac at 50 - 60 plus or minus 0.5 Hz
Thermal output (maximum) 2560 Btu/hr
Power requirements (maximum) 750 W
Power factor 0.95
Inrush current 41 A
Leakage current (maximum) 3.5 mA
Phase 1
Table 3. Temperature requirements
Operating Nonoperating
10 - 38°C (50 - 100.4°F) 1 - 60°C (33.8 - 140°F)
Table 4. Environment requirements
Environment Operating Nonoperating
Wet bulb temperature 23°C (73.4°F) 27°C (80.6°F)
Maximum altitude 3048 m (10 000 ft) 3048 m (10 000 ft)
Table 5. Noise emissions
Properties Operating Idle
LWAd (Category 2E, General business) 6.6 bels 6.3 bels
<LpA>m 48 dB 46 dB
For a description of noise emission values, see Acoustics.
Table 6. Service clearances
Front Back Sides Top
762 mm (30 in. ) 762 mm (30 in. ) 762 mm (30 in. ) 762 mm (30 in. )
Side and top clearances are optional when operating.
Notes:
  1. The 1.8 meter rack has six EIA units of space remaining. This space will be filled with a three-EIA filler panel and three of the one-EIA filler panels.
  2. Only the 4.3 m (14 ft) power cord features are offered for racked 9406-270 systems. There are a total of four power cords that are routed through cable management arms. Also, there is a cable management device that might be used to restrict the length of the power cord exiting the bottom of the rack. See model 9406-270 Cable Poster Addendum included with the 0551 model 9406-270 rack.
  3. The rack does not have power distribution. Each model 9406-270 and 7104 requires a power cord of sufficient length to reach the receptacle. The power cord feature codes for model 9406-270s must be used to determine the appropriate receptacles.



Last updated: Tue, February 02, 2021