The system detected that the temperature threshold was exceeded in a CEC enclosure.

Perform the following steps:
  1. Is the room temperature less than 40°C (104°F)?
    Yes:
    Continue with the next step.
    No:
    Notify the customer. The customer must bring the room temperature within normal range. If the problem persists, continue with the next step
  2. Are the front and rear doors of the system free of obstructions?
    Yes:
    Continue with the next step.
    No:
    Notify the customer. The system must be free of obstructions for proper air flow. If the problem persists, continue with the next step.
  3. Do all the unused FRU positions contain fillers?
    Yes:
    Continue with the next step.
    No:
    Fill any unused FRU positions with fillers. If the problem persists, continue with the next step.
  4. There might be a problem with the CEC enclosure cooling. Contact your next level of support. This ends the procedure.