POWER7 information
EDR1 expansion unit
Hardware specifications provide detailed information for your expansion unit, including dimensions, electrical, power, temperature, environment, and service clearances.
| Weight (with drives installed) | Width | Depth (including front bezel) | Height (with support rails) |
|---|---|---|---|
| 21.8 kg (48.0 lb) | 444.5 mm (17.5 in.) | 762 mm (30 in.) | 44.5 mm (1.75 in.) |
| Electrical characteristics | Properties |
|---|---|
| kVA (maximum)1 | 0.46 |
| Rated voltage and frequency | 100 - 127 V ac or 200 - 240 V ac at 50 - 60 Hz |
| Thermal output (maximum)1 | 1501 Btu/hr |
| Power requirements (maximum) | 440 W |
| Phase | 1 |
| 1All measurements are made in conformance with ISO 7779 and declared in conformance with ISO 9296. | |
| Operating | Nonoperating |
|---|---|
| 10°C - 38°C (50°F - 100.4°F)1 | -40°C to 60°C (-40°F to 140°F) |
| 1The maximum 38°C (100.4°F) temperature must be derated 1°C (1.8 °F) per 137 m (450 ft) above 1295 m (4250 ft). | |
| Environment | Operating | Nonoperating | Maximum altitude |
|---|---|---|---|
| Noncondensing humidity | 20% - 80% (allowable) 40% - 55% (recommended) |
8% - 80% (including condensing) | 2134 m (7000 ft) above sea level |
| Wet bulb temperature | 21°C (69.8°F) | 27°C (80.6°F) |
Safety compliance: This hardware is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all national differences