The signal connection between a 2145 and its 2145 UPS-1U
is failing.
Explanation
The signal connection between a 2145 and its 2145
UPS-1U is failing.
User response
- Exchange the FRUs for new FRUs in the sequence shown.
- Check node status. If all nodes show a status of "online", mark the error that you have just repaired as "fixed". If
any nodes do not show a status of "online", go to start MAP.
If you return to this step, contact your support center to resolve
the problem with the uninterruptible power supply.
- Go to repair verification MAP.
Possible Cause-FRUs or other:
2145-CF8
or 2145-CG8
- Power cable assembly (40%)
- 2145 UPS-1U assembly (30%)
- System board (30%)
2145-8G4
- Power cable assembly (40%)
- 2145 UPS-1U assembly (30%)
- System board (30%)