Priming control unit data

You can prime your I/O configuration in a work IODF with the control unit serial number for the active processor. For the prerequisites for this function refer to Prerequisites.

To prime the control unit serial number, select the action Prime serial number from the context menu (or action code  i ) on the Control Unit List. The Confirm Priming Control Unit Data List shows the selected control units with the sensed data for the control unit types and serial numbers, and their corresponding definitions in the IODF.
┌────────── Confirm Priming Control Unit Data List ──────────┐
│                                                  Row 1 of 9│
│ Command ===> ___________________________ Scroll ===> CSR   │
│                                                            │
│ Press Enter to confirm priming, or Cancel to leave the     │
│ list. A blank value will not change the IODF definition.   │
│                                                            │
│ CU     ---------- Type ----------- --- Serial Number ---   │
│ Number actual        defined       sensed     defined      │
│ 90C1                 3990          __________ 33333   1    │
│ 9100   3990-L03      3990          30984              2    │
│ 9101   3990-L03      3990          30984      30984        │
│ 9140   3990-L03      3990          37160      A7199   3    │
│ 9141   3990-L03      3990          37160      A7199        │
│ 9180   3990-L03      3990          37201                   │
│ 9181   3990-L03      3990          37201                   │
│ 91C0   3990-L03      3990          37163      37163        │
│ 91C1   3990-L03      3990          37163      37163        │
│ ********************* Bottom of data **********************│
│                                                            │
│  F1=Help        F2=Split       F3=Exit        F5=Reset     │
│  F7=Backward    F8=Forward     F9=Swap       F12=Cancel    │
└────────────────────────────────────────────────────────────┘
 1 
The control unit serial number is defined in the IODF, but no sensed data is available on the active system.
 2 
No control unit serial number is defined in the IODF, but the sensed data of the active system is available. To confirm the sensed data, and to define them in the IODF, press Enter.
 3 
The control unit serial numbers that are defined in the IODF, and that are sensed are different. Press Enter, to overwrite the defined data by the sensed data.
Note: The sensed values can only be blanked out or left unchanged. Blank out the sensed values, if you don't want to change the defined IODF values. To confirm priming, press Enter. Use the F12=Cancel key, if you don't want to use the sensed values, and to leave the list.