TS7760 specifications and requirements
The following specifications and requirements are specific to the TS7760 and its components.
The 3952 Tape Frame (3952 F06 or 3952 F07) houses the components of the TS7760.
When
designated as a TS7760 Base Frame
(FC 7333, TS7700 Encryption-capable base frame), the
3952 F06 or 3952 F07 contains
the following components:
- TS7760 Server (3957-VEC) (includes control unit and 2 I/O drawers)
- TS7760 Cache Controller (3956-CSA)
- TS7760 Cache Drawer(s) (3956-XSA)
- Internal power distribution units Note: The standard 3952 Tape Frame ships with one internal power distribution unit. However, FC 1903, Power Distribution Unit is required to provide two power distribution units to support the availability characteristics of the TS7760.
Specification | Measurement |
---|---|
Width | 616 mm (24.25 in.) |
Depth | 1425 mm (56.1 in.) |
Height | 1930.4 mm (76 in.) |
Weight | 1644 lbs (745.7 kg) |
When designated as a TS7760 Storage Expansion Frame (FC 7334, TS7760 Encryption Capable Expansion Frame (VEC section below)), the 3952 F06 or
3952 F07
contains the following components:
- TS7760 Cache Controllers (3956-CSA)
- TS7760 Cache Drawer(s) (3956-XSA)
Note: FC 9323, R4 Expansion Frame Attachment is also required
to attach the base and expansion frames.
If FC 7334, TS7700 Encryption-capable expansion
frame is installed the TS7760 Storage Expansion Frame has these physical
specifications when fully configured:
Specification | Measurement |
---|---|
Width | 616 mm (24.25 in.) |
Depth | 1425 mm (56.1 in.) |
Height | 1930.4 mm (76 in.) |
Weight | 794 kg (1750 lb.) |
The distance between a TS7760 Storage Expansion Frame and the TS7700 Base Frame cannot exceed 10 meters. This distance permits connection of the frames by using a 30-meter cable.
Table 3 displays the maximum configuration of a TS7760. Table 4 displays the physical specifications for each TS7760 component. Use these tables and the tape frame specifications, located from the links in the Related information section, to determine the correct physical requirements for your configuration.Component | Quantity of each component in 3952 Tape Frame as TS7760 Base Frame | Quantity of each component in 3952 Tape Frame as optional TS7760 Storage Expansion Frame |
---|---|---|
TS7760 Server (3957-VEC) | 1 | 0 |
TS7760 Cache Controller (3956-CSA) | 1 | 1 |
TS7760 Cache Drawers (3956-XSA) | 9 | 15 |
Specification | TS7760 Server | TS7760 Cache Subsystem | ||
---|---|---|---|---|
Type and Model | 3957-VEC | I/O expansion drawer (each of 2) |
3956-CSA cache controller | 3956-XSA cache expansion drawer |
Width | 427.5 mm (16.8 in.) | 440 mm (17.32 in.) Total width of two joined drawers |
449 mm (17.7 in.) | 449 mm (17.7 in.) |
Depth | 747.5 mm (29.4 in.) | 800 mm (31.5 in.) | 540 mm (21.3 in.) | 540 mm (21.3 in.) |
Height | 86.5 mm (3.4 in.) | 220 mm (8.66 in.) | 86 mm (3.4 in.) | 86 mm (3.4 in.) |
Weight | 29.5 kg (65 lbs.) | 42.2 kg (92.8 lb.) weight of two combined Reflects weight of each, without cassettes |
27 kg (59.6 lb. lb.) fully configured | 26.3 kg (57.9 lb.) fully configured |
Power | 200-240 V AC 50/60 Hz (+/- 3 Hz) |
200-240 V AC 50/60 Hz |
198-264 RMS† V AC 50/60 Hz |
198-264 RMS† V AC 50/60 Hz |
Unit height | 2 U | 5 U | 2 U | 2 U |
Temperature (non-operating) | 5-45 degrees C (41-113 degrees F) | Included in 3952 Tape Frame maximum | −10-65 degrees C (14-149 F) | 5-45 degrees C (41-113 F) |
Temperature (operating) | 5-40 degrees C (41-104 degrees F) Temperature depends on altitude, see Table 5. Suggested: 18-27 degrees C (64-80 degrees F) |
Included in 3952 Tape Frame maximum | 10-32 degrees C (50-89.6 F) | 10-32 degrees C (50-89.6 F) |
Relative humidity | Non-operating: 8-85% Operating: 20-60% |
Included in 3952 Tape Frame maximum | Non-operating: 8-80% Operating: 20%-80% |
Non-operating: 8-80% Operating: 20%-80% |
Maximum wet bulb (power off) | Non-operating: 28 degrees C (82 degrees F) Operating: tbd degrees C (tbd degrees F) |
Included in 3952 Tape Frame maximum | 23 degrees C (73.4 F) | 23 degrees C (73.4 F) |
Power consumption | 1400 watts (2X) max. | Included in 3952 Tape Frame maximum | 406 watts | 213 watts |
Thermal output | 6655 Btu/hour (max.) | Included in 3952 Tape Frame maximum | 1329 Btu/hr | 730 Btu/hr |
Power-source loading | 1.6 kVA (max. config.) 3,048 m (10,000 ft.) max. altitude |
Included in 3952 Tape Frame maximum | 0.409 kVa | 0.240 kVa |
† Root Mean Square. In a multi-drawer configuration, total power is predicted to be a root mean square of the individual drawer maximums. |
Temperature (operating) | Altitude |
---|---|
5-40 degrees C (41-104 degrees F) Note: The minimum operating temperature cannot
go below 5 C (41 degrees F).
|
Up to 3050 meter @ 5-28 C (41-82 degrees F) |
Up to 2875 meter @ 29 C (84 degrees F) | |
Up to 2700 meter @ 30 C (86 degrees F) | |
Up to 2525 meter @ 31 C (88 degrees F) | |
Up to 2350 meter @ 32 C (89 degrees F) | |
Up to 2175 meter @ 33 C (91 degrees F) | |
Up to 2000 meter @ 34 C (93 degrees F) | |
Up to 1825 meter @ 35 C (95 degrees F) | |
Up to 1650 meter @ 36 C (96 degrees F) | |
Up to 1475 meter @ 37 C (98 degrees F) | |
Up to 1300 meter @ 38 C (100 degrees F) | |
Up to 1125 meter @ 39 C (102 degrees F) | |
Up to 950 meter @ 40 C (104 degrees F) |
TS7760 Base Frame power requirements
Your facility must ensure an available power supply to meet the input voltage requirements for the TS7760 Base Frame. Table 6 displays the maximum input power for a fully configured TS7760.Power requirement | Value |
---|---|
Voltage | 200-240 V AC (single phase) |
Frequency | 50-60 Hz (+/- 3 Hz) |
Current | 24 amp |
Inrush current | 250 amp |
Power (watt) | 3280 watts |
Input power required | 4.8 kVa (single phase) |
Thermal units | 11.5 kBtu/hr, 2.9 kcal/hr |
TS7760 Storage Expansion Frame power requirements
Your facility must ensure an available power supply to meet the input voltage requirements for the TS7760 Storage Expansion Frame. Table 7 displays the maximum input power for a fully configured TS7760.Power requirement | Value |
---|---|
Voltage | 200-240 V AC (single phase) |
Frequency | 50-60 Hz (+/- 3 Hz) |
Current | 24 amp |
Leakage current | 13.5 ma |
Inrush current | 250 amp |
Power (watt) | 3200 watts |
Input power required | 4.8 kVa (single phase) |
Thermal units | 11.2 kBtu/hr, 2.9 kcal/hr |
Exhaust capacity | 750 m3/hr |
Noise level | 59 db |