Clearance requirements
You must meet the specified clearance requirements when moving and positioning the 3948-F07 or 3952-F07.
Clearance – moving the frame
Two persons should be available to move system components between locations. Table 1 shows the minimum aisle and door dimensions for moving components from one location to another for the 3948-F07 or 3952-F07 Tape Frame.Clearance item | Required clearance |
---|---|
Distance to ceiling† | 1955.8 mm (77 in.) |
Aisle and door width | 736 mm (29 in.) |
Corner radius | 2844.8 mm (112 in.) |
Ramp inclination | 10° |
†The 3948-F07 or 3952-F07 Tape Frame is moved on casters and has four leveling pads. The frame's nominal height is 1.94 m (76.5 in.) from the bottom of the leveling pads to the top of the frame. The leveling pads can vary the height of the frame by up to 30 mm (1.2 in.). The pads are completely raised when the frame is shipped to allow it to roll on its casters. The shipping height of the frame on its casters is 1.93 m (75.9 in.). |
Clearance – frame in position
Clearances are required around system components for the operator to perform certain tasks and for the service representative to perform certain items. Table 2 lists the specific clearance requirements for the 3948-F07 or 3952-F07 Tape Frame.Figure 1 gives the opening radius of the front and rear doors when the F07 frame is in position. It also shows the side panel access distance. From these dimensions, Table 2 was constructed to allow the service personal space to move while accessing these areas. Access is needed for removing and replacing equipment in the frame.
Door or panel | Required clearance |
---|---|
Front | 121.92 cm (48 in) |
Back | 76.2 cm (30 in) |
Side | 0 cm (0 in) required, but 48 cm (18.9 in) is recommended for side panel removal |