TS7770 specifications and requirements

The following specifications and requirements are specific to the TS7770 and its components.

The Tape Frame (3948-F07 or 3952-F07/F06) houses the components of the TS7770.

When designated as a TS7770 Base Frame (FC 7335 or FC 7337, TS7700 Encryption-capable base frame), the 3948-F07 or 3952-F07/F06 contains the following components:
  • TS7770 Server (3948-VED or 3957-VED) (includes control unit and 2 I/O drawers)
  • TS7770 Cache Controller (3948-CSB or 3956-CSB)
  • TS7770 Cache Drawer(s) (3948-XSB or 3956-XSB) Internal power distribution units
Note: The standard 3952 Tape Frame ships with one internal power distribution unit. However, FC 1904 is required to provide two power distribution units to support the availability characteristics of the TS7770.
If FC 7333, TS7700 Encryption-capable base frame FC 7335 or FC 7337, TS7700 Encryption-capable base frame is installed, the TS7770 Base Frame has these physical specifications when fully configured.
When designated as a TS770 Storage Expansion Frame (FC 7334, TS7700 Encryption Capable Expansion Frame FC 7336 or FC 7338, TS7700 Encryption Capable Expansion Frame the 3948-F07 or 3952-F07/F06 contains the following components:
  • TS7770 Cache Controllers (3948-CSB or 3956-CSB)
  • TS7770 Cache Drawer(s) (3948-XSB or 3956-XSB)
Note: FC 9336, R5 Expansion Frame Attachment is also required to attach the base and expansion frames.
Note: FC 9336 or FC 9337 is also required to attach the base and expansion frames.
If FC 7336, TS7700 Encryption-capable expansion frame is installed the TS7770 Storage Expansion Frame has these physical specifications when fully configured:The distance between a TS7770 Storage Expansion Frame and the TS7770 Base Frame cannot exceed 10 meters. This distance permits connection of the frames by using a 30-meter cable.
Table 1. Encryption- capable TS7770 physical frame characteristicsF06 characteristics (FC 7335 and FC 7336)
  Base Frame Expansion Frame, each (up to 2) Client Rack Mount (min config/ max config)
Width 616 mm (24.25 in.) 616 mm (24.25 in.) 483 mm (19.0 in.) of each component
Depth 1425 mm (56.1 in.) 1425 mm (56.1 in.) Depth of the deepest component3757-VED (p9 pSeries) from front to back of the cable management arm & cables in the arm 38.9 inches (98.8 cm)
Height 1930.4 mm (76 in.) 1930.4 mm (76 in.)

2 disk module config 18U in height = Min config

4 disk module config 22U in height

6 disk module config 26U in height

8 disk module config 30U in height

10 disk module config 34U in height = Max config

Weight max 735.3 Kg (1,621 lib) max 929.3 Kg (2,049 lbs)

Min weight of components for configuration with 2 disk cache drawers is ‭243 kg (‭536.4 lbs)

Max weight of components for configuration with 10 disk cache drawers is ‭456 kg (1,006‬ lbs)

Power consumption max 3480 watts max 4400 watts max 3480 watts
Power phase options single phase (240 V AC) or three phase (400 V AC) single phase only (240 V AC)
Power frequency 50 Hz - 60 Hz (+/- 3 Hz)
Dry bulb temperature (recommended operating range) 20°C to 25°C (68°F to 77°F)
Relative humidity (recommended operating range) 40 % to 55%

If FC 7338, TS7700 Encryption-capable expansion frame is installed the TS7770 Storage Expansion Frame has these physical specifications when fully configured:The distance between a TS7770 Storage Expansion Frame and the TS7770 Base Frame cannot exceed 10 meters. This distance permits connection of the frames by using a 30-meter cable.

Table 2. Encryption- capable TS7770 physical frame characteristics F07 characteristics (FC 7337 and FC 7338 and FC 7339)
  Base Frame Expansion Frame, each (up to 2) Client Rack Mount (min config/ max config)
Width 616 mm (24.25 in.) 616 mm (24.25 in.) 483 mm (19.0 in.) of each component
Depth 1425 mm (56.1 in.)1274 mm (50.16 in.) 1425 mm (56.1 in.)1274 mm (50.16 in.) Depth of the deepest component3757-VED (p9 pSeries) from front to back of the cable management arm & cables in the arm 38.9 inches (98.8 cm)
Height 1930.4 mm (76 in.)1930 mm (76 in.) 1930.4 mm (76 in.)1930 mm (76 in.)

2 disk module config 18U in height = Min config

4 disk module config 22U in height

6 disk module config 26U in height

8 disk module config 30U in height

10 disk module config 34U in height = Max config

Weight max 735.3 Kg (1,621 lib)max 706.7 Kg (1558 lbs) max 929.3 Kg (2,049 lbs)max 900.8 Kg (1986 lbs)

Min weight of components for configuration with 2 disk cache drawers is ‭243 kg (‭536.4 lbs)

Max weight of components for configuration with 10 disk cache drawers is ‭456 kg (1,006‬ lbs)

Power consumption max 3480 watts max 4400 watts max 3480 watts
Power phase options single phase (240 V AC) or three phase (400 V AC) single phase only (240 V AC)
Power frequency 50 Hz - 60 Hz (+/- 3 Hz)
Dry bulb temperature (recommended operating range) 20°C to 25°C (68°F to 77°F)
Relative humidity (recommended operating range) 40 % to 55%
Table 3 displays the maximum configuration of a TS7770. Table 4 displays the physical specifications for each TS7770 component. Use these tables and the tape frame specifications, located from the links in the Related information section, to determine the correct physical requirements for your configuration.
Table 3. TS7770 maximum configuration
Component Quantity of each component in Tape Frame as TS7770 Base frame Quantity of each component in Tape Frame as optional TS7770 Storage Expansion Frame
TS7770 Server (3948-Vxx or 3957-Vxx) 1 0
TS7770 Cache Controller (3948-CSB or 3956-CSB) 1 2
TS7770 Cache Drawers (3948-XSB or 3956-XSB) 9 18
Component Quantity of each component in Tape Frame as TS7770 Base frame Quantity of each component in Tape Frame as optional TS7770 Storage Expansion Frame with FC 9336 1st Expansion Frame Quantity of each component in Tape Frame as optional TS7770 Storage Expansion Frame with FC 9337 2nd Expansion Frame
TS7770 Server (VED) 1 0 0
TS7770 Cache Controller (CSB) 1 2 2
TS7770 Cache Enclosures (XSB) 9 18 18
Table 4. TS7770 component specifications
Specification TS7770 Server TS7770 Cache Subsystem
Type and Model 3948-Vxx or 3957-Vxx I/O expansion drawer
(each of 2)
TS7770 cache controller 3948-CSB or 3956-CSB TS7770 cache expansion drawer 3948-XSB or 3956-XSB
Width 482 mm (18.97 in) 440 mm (17.32 in.)
Total width of two joined drawers
483 mm (19.0 in) 483 mm (19.0 in)
Depth 766.5 mm (30.2 in) 800 mm (31.5 in.) 556 mm (21.9 in) 556 mm (21.9 in)
Height 86.7 mm (3.4 in) 220 mm (8.66 in.) 87 mm (3.4 in) 87 mm (3.4 in)
Weight 30.4 kg (67 lbs) 42.2 kg (92.8 lb.) weight of two combined
Reflects weight of each, without cassettes
27.7 kg (61.0 lb) fully configured

26.7 kg (58.7 lb)

fully configured
Power 180-240 V AC
50/60 Hz (+/- 3 Hz)
180-240 V AC
50/60 Hz
198-264 RMS† V AC
50/60 Hz
198-264 RMS† V AC
50/60 Hz
Unit height 2 U 5 U 2 U 2 U
Temperature (non-operating) 5-45 degrees C (41-113 degrees F) Included in Tape Frame maximum −10-65 degrees C (14-149 F) 5-45 degrees C (41-113 F)
Temperature (operating) 5-40 degrees C (41-104 degrees F)
Temperature depends on altitude, see Table 5.
Suggested:
18-27 degrees C (64-80 degrees F)
Included in Tape Frame maximum 10-32 degrees C (50-89.6 F) 10-32 degrees C (50-89.6 F)
Relative humidity Non-operating: 8-85%
Operating: 20-60%
Included in Tape Frame maximum Non-operating: 8-80%
Operating: 20%-80%
Non-operating: 8-80%
Operating: 20%-80%
Maximum wet bulb (power off) Non-operating:
28 degrees C (82 degrees F)
Operating:
tbd degrees C (tbd degrees F)
Included in Tape Frame maximum 23 degrees C (73.4 F) 23 degrees C (73.4 F)
Power consumption 1400 watts (2X) max. Included in Tape Frame maximum 810 watts 540 watts
Thermal output 6416 Btu/hour (max.) Included in Tape Frame maximum 2730 Btu/hr 1820 Btu/hr
Power-source loading 1.6 kVA (max. config.)
3,048 m (10,000 ft.) max. altitude
Included in Tape Frame maximum 0.9 kVA 0.6 kVA
† Root Mean Square. In a multi-drawer configuration, total power is predicted to be a root mean square of the individual drawer maximums.
Table 5. 3948-VED or 3957-VED Temperature Depending on Altitude
Temperature (operating) Altitude
5-40 degrees C (41-104 degrees F)
Note: The minimum operating temperature cannot go below 5 C (41 degrees F).
Up to 3050 meter @ 5-28 C (41-82 degrees F)
Up to 2875 meter @ 29 C (84 degrees F)
Up to 2700 meter @ 30 C (86 degrees F)
Up to 2525 meter @ 31 C (88 degrees F)
Up to 2350 meter @ 32 C (89 degrees F)
Up to 2175 meter @ 33 C (91 degrees F)
Up to 2000 meter @ 34 C (93 degrees F)
Up to 1825 meter @ 35 C (95 degrees F)
Up to 1650 meter @ 36 C (96 degrees F)
Up to 1475 meter @ 37 C (98 degrees F)
Up to 1300 meter @ 38 C (100 degrees F)
Up to 1125 meter @ 39 C (102 degrees F)
Up to 950 meter @ 40 C (104 degrees F)

TS7770 Base Frame power requirements

Your facility must ensure an available power supply to meet the input voltage requirements for the TS7770 Base Frame. Table 6 displays the maximum input power for a fully configured TS7770.

Table 6. TS7770 Base Frame maximum input power requirements
Power requirement Value
Voltage 200-240 V AC (single phase)
Frequency 50-60 Hz (+/- 3 Hz)
Current 24 amp
Inrush current 250 amp
Power (watt) 3480 watts
Input power required 4.8 kVA (single phase)
Thermal units 12.2kBTU/hr, 3.06 kcal/hr

TS7770 Base Frame operating environment

Table 7 displays the total frame including VED, CSB, nine XSB, TSSC, and Integrated control path.

Table 7. TS7770 maximum configuration frame with all components
Operating environment Value
Temperature 10° to 32.0° C (50° to 89.6° F) up to 5,000 feet 10 to 28.0° C (50° to 82.4° F) 5,001 to 7,000 feet
Relative humidity 20% to 80% up to 5000 feet and 20% to 60% from 5001 to 7000 feet
Heat output (caloric value)

12.2 kBTU/hr, 3.06 kcal/hr

Wet bulb (caloric value) 23° C
Electrical power 3480 watts
Capacity of exhaust 775 m3/h
Noise level 58 db at ambient 25° C and 65 db at high temperature 32° C
Leakage 10 mA

TS7770 Storage Expansion Frame power requirements

Your facility must ensure an available power supply to meet the input voltage requirements for the TS7770 Storage Expansion Frame. Table 8 displays the maximum input power for a fully configured TS7770.

Table 8. TS7770 Storage Expansion Frame maximum input power requirements
Power requirement Value
Voltage 200-240 V AC (single phase)
Frequency 50-60 Hz (+/- 3 Hz)
Current 24 amp
Leakage current 13.5 ma
Inrush current 250 amp
Power (watt) 4400 watts
Input power required 4.8 kVA (single phase)
Thermal units 15.4 kBtu/hr, 4.0 kcal/hr
Exhaust capacity 1030 m3/hr