TS7770 specifications and requirements
The following specifications and requirements are specific to the TS7770 and its components.
The Tape Frame (3948-F07 or 3952-F07/F06) houses the components of the TS7770.
- TS7770 Server (3948-VED or 3957-VED) (includes control unit and 2 I/O drawers)
- TS7770 Cache Controller (3948-CSB or 3956-CSB)
- TS7770 Cache Drawer(s) (3948-XSB or 3956-XSB) Internal power distribution units
- TS7770 Cache Controllers (3948-CSB or 3956-CSB)
- TS7770 Cache Drawer(s) (3948-XSB or 3956-XSB)
Base Frame | Expansion Frame, each (up to 2) | Client Rack Mount (min config/ max config) | |
---|---|---|---|
Width | 616 mm (24.25 in.) | 616 mm (24.25 in.) | 483 mm (19.0 in.) of each component |
Depth | 1425 mm (56.1 in.) | 1425 mm (56.1 in.) | Depth of the deepest component3757-VED (p9 pSeries) from front to back of the cable management arm & cables in the arm 38.9 inches (98.8 cm) |
Height | 1930.4 mm (76 in.) | 1930.4 mm (76 in.) |
2 disk module config 18U in height = Min config 4 disk module config 22U in height 6 disk module config 26U in height 8 disk module config 30U in height 10 disk module config 34U in height = Max config |
Weight | max 735.3 Kg (1,621 lib) | max 929.3 Kg (2,049 lbs) |
Min weight of components for configuration with 2 disk cache drawers is 243 kg (536.4 lbs) Max weight of components for configuration with 10 disk cache drawers is 456 kg (1,006 lbs) |
Power consumption | max 3480 watts | max 4400 watts | max 3480 watts |
Power phase options | single phase (240 V AC) or three phase (400 V AC) | single phase only (240 V AC) | |
Power frequency | 50 Hz - 60 Hz (+/- 3 Hz) | ||
Dry bulb temperature (recommended operating range) | 20°C to 25°C (68°F to 77°F) | ||
Relative humidity (recommended operating range) | 40 % to 55% |
If FC 7338, TS7700 Encryption-capable expansion frame is installed the TS7770 Storage Expansion Frame has these physical specifications when fully configured:The distance between a TS7770 Storage Expansion Frame and the TS7770 Base Frame cannot exceed 10 meters. This distance permits connection of the frames by using a 30-meter cable.
Base Frame | Expansion Frame, each (up to 2) | Client Rack Mount (min config/ max config) | |
---|---|---|---|
Width | 616 mm (24.25 in.) | 616 mm (24.25 in.) | 483 mm (19.0 in.) of each component |
Depth | 1425 mm (56.1 in.)1274 mm (50.16 in.) | 1425 mm (56.1 in.)1274 mm (50.16 in.) | Depth of the deepest component3757-VED (p9 pSeries) from front to back of the cable management arm & cables in the arm 38.9 inches (98.8 cm) |
Height | 1930.4 mm (76 in.)1930 mm (76 in.) | 1930.4 mm (76 in.)1930 mm (76 in.) |
2 disk module config 18U in height = Min config 4 disk module config 22U in height 6 disk module config 26U in height 8 disk module config 30U in height 10 disk module config 34U in height = Max config |
Weight | max 735.3 Kg (1,621 lib)max 706.7 Kg (1558 lbs) | max 929.3 Kg (2,049 lbs)max 900.8 Kg (1986 lbs) |
Min weight of components for configuration with 2 disk cache drawers is 243 kg (536.4 lbs) Max weight of components for configuration with 10 disk cache drawers is 456 kg (1,006 lbs) |
Power consumption | max 3480 watts | max 4400 watts | max 3480 watts |
Power phase options | single phase (240 V AC) or three phase (400 V AC) | single phase only (240 V AC) | |
Power frequency | 50 Hz - 60 Hz (+/- 3 Hz) | ||
Dry bulb temperature (recommended operating range) | 20°C to 25°C (68°F to 77°F) | ||
Relative humidity (recommended operating range) | 40 % to 55% |
Component | Quantity of each component in Tape Frame as TS7770 Base frame | Quantity of each component in Tape Frame as optional TS7770 Storage Expansion Frame | |
---|---|---|---|
TS7770 Server (3948-Vxx or 3957-Vxx) | 1 | 0 | |
TS7770 Cache Controller (3948-CSB or 3956-CSB) | 1 | 2 | |
TS7770 Cache Drawers (3948-XSB or 3956-XSB) | 9 | 18 | |
Component | Quantity of each component in Tape Frame as TS7770 Base frame | Quantity of each component in Tape Frame as optional TS7770 Storage Expansion Frame with FC 9336 1st Expansion Frame | Quantity of each component in Tape Frame as optional TS7770 Storage Expansion Frame with FC 9337 2nd Expansion Frame |
TS7770 Server (VED) | 1 | 0 | 0 |
TS7770 Cache Controller (CSB) | 1 | 2 | 2 |
TS7770 Cache Enclosures (XSB) | 9 | 18 | 18 |
Specification | TS7770 Server | TS7770 Cache Subsystem | ||
---|---|---|---|---|
Type and Model | 3948-Vxx or 3957-Vxx | I/O expansion drawer (each of 2) |
TS7770 cache controller 3948-CSB or 3956-CSB | TS7770 cache expansion drawer 3948-XSB or 3956-XSB |
Width | 482 mm (18.97 in) | 440 mm (17.32 in.) Total width of two joined drawers |
483 mm (19.0 in) | 483 mm (19.0 in) |
Depth | 766.5 mm (30.2 in) | 800 mm (31.5 in.) | 556 mm (21.9 in) | 556 mm (21.9 in) |
Height | 86.7 mm (3.4 in) | 220 mm (8.66 in.) | 87 mm (3.4 in) | 87 mm (3.4 in) |
Weight | 30.4 kg (67 lbs) | 42.2 kg (92.8 lb.) weight of two combined Reflects weight of each, without cassettes |
27.7 kg (61.0 lb) fully configured | 26.7 kg (58.7 lb) fully configured |
Power | 180-240 V AC 50/60 Hz (+/- 3 Hz) |
180-240 V AC 50/60 Hz |
198-264 RMS† V AC 50/60 Hz |
198-264 RMS† V AC 50/60 Hz |
Unit height | 2 U | 5 U | 2 U | 2 U |
Temperature (non-operating) | 5-45 degrees C (41-113 degrees F) | Included in Tape Frame maximum | −10-65 degrees C (14-149 F) | 5-45 degrees C (41-113 F) |
Temperature (operating) | 5-40 degrees C (41-104 degrees F) Temperature depends on altitude, see Table 5. Suggested: 18-27 degrees C (64-80 degrees F) |
Included in Tape Frame maximum | 10-32 degrees C (50-89.6 F) | 10-32 degrees C (50-89.6 F) |
Relative humidity | Non-operating: 8-85% Operating: 20-60% |
Included in Tape Frame maximum | Non-operating: 8-80% Operating: 20%-80% |
Non-operating: 8-80% Operating: 20%-80% |
Maximum wet bulb (power off) | Non-operating: 28 degrees C (82 degrees F) Operating: tbd degrees C (tbd degrees F) |
Included in Tape Frame maximum | 23 degrees C (73.4 F) | 23 degrees C (73.4 F) |
Power consumption | 1400 watts (2X) max. | Included in Tape Frame maximum | 810 watts | 540 watts |
Thermal output | 6416 Btu/hour (max.) | Included in Tape Frame maximum | 2730 Btu/hr | 1820 Btu/hr |
Power-source loading | 1.6 kVA (max. config.) 3,048 m (10,000 ft.) max. altitude |
Included in Tape Frame maximum | 0.9 kVA | 0.6 kVA |
† Root Mean Square. In a multi-drawer configuration, total power is predicted to be a root mean square of the individual drawer maximums. |
Temperature (operating) | Altitude |
---|---|
5-40 degrees C (41-104 degrees F) Note: The minimum operating temperature cannot
go below 5 C (41 degrees F).
|
Up to 3050 meter @ 5-28 C (41-82 degrees F) |
Up to 2875 meter @ 29 C (84 degrees F) | |
Up to 2700 meter @ 30 C (86 degrees F) | |
Up to 2525 meter @ 31 C (88 degrees F) | |
Up to 2350 meter @ 32 C (89 degrees F) | |
Up to 2175 meter @ 33 C (91 degrees F) | |
Up to 2000 meter @ 34 C (93 degrees F) | |
Up to 1825 meter @ 35 C (95 degrees F) | |
Up to 1650 meter @ 36 C (96 degrees F) | |
Up to 1475 meter @ 37 C (98 degrees F) | |
Up to 1300 meter @ 38 C (100 degrees F) | |
Up to 1125 meter @ 39 C (102 degrees F) | |
Up to 950 meter @ 40 C (104 degrees F) |
TS7770 Base Frame power requirements
Your facility must ensure an available power supply to meet the input voltage requirements for the TS7770 Base Frame. Table 6 displays the maximum input power for a fully configured TS7770.
Power requirement | Value |
---|---|
Voltage | 200-240 V AC (single phase) |
Frequency | 50-60 Hz (+/- 3 Hz) |
Current | 24 amp |
Inrush current | 250 amp |
Power (watt) | 3480 watts |
Input power required | 4.8 kVA (single phase) |
Thermal units | 12.2kBTU/hr, 3.06 kcal/hr |
TS7770 Base Frame operating environment
Table 7 displays the total frame including VED, CSB, nine XSB, TSSC, and Integrated control path.
Operating environment | Value |
---|---|
Temperature | 10° to 32.0° C (50° to 89.6° F) up to 5,000 feet 10 to 28.0° C (50° to 82.4° F) 5,001 to 7,000 feet |
Relative humidity | 20% to 80% up to 5000 feet and 20% to 60% from 5001 to 7000 feet |
Heat output (caloric value) |
12.2 kBTU/hr, 3.06 kcal/hr |
Wet bulb (caloric value) | 23° C |
Electrical power | 3480 watts |
Capacity of exhaust | 775 m3/h |
Noise level | 58 db at ambient 25° C and 65 db at high temperature 32° C |
Leakage | 10 mA |
TS7770 Storage Expansion Frame power requirements
Your facility must ensure an available power supply to meet the input voltage requirements for the TS7770 Storage Expansion Frame. Table 8 displays the maximum input power for a fully configured TS7770.
Power requirement | Value |
---|---|
Voltage | 200-240 V AC (single phase) |
Frequency | 50-60 Hz (+/- 3 Hz) |
Current | 24 amp |
Leakage current | 13.5 ma |
Inrush current | 250 amp |
Power (watt) | 4400 watts |
Input power required | 4.8 kVA (single phase) |
Thermal units | 15.4 kBtu/hr, 4.0 kcal/hr |
Exhaust capacity | 1030 m3/hr |
Noise level | 59 db |