Physical specifications for frame model S25

Table 1. Physical characteristics of frame model S25
Physical Characteristic Measurement
Height of S25 frame (on casters) 1 800 mm (70.9 in)
Height of S25 with TR1 top rack 2 320 mm (91.34 in)
Height of S25 with TR2 top rack 2066.6 mm (81.4 in)
Width of S25 frame with covers 782 mm (30.8 in)
Width of S25 frame without covers1 725 mm (28.5 in)
Depth of S25 frame (including front and rear doors) 1 212 mm (47.7 in)
  Position 1 (Leftmost frame) Position 2+
Minimum weight of frame (0 cartridges)

299 kg (660 lb)

299 kg (660 lb)

Maximum weight of frame (with 0 drives and maximum cartridges)3, 4

491.2 kg (1 083 lb)

540.2 kg (1 191 lb)

Weight of TR1 top rack (empty)2 24.5 kg (54 lb)
Weight of the TR2 top rack (empty)5 17.5 kg (38.5 lbs)
Weight of the TR2 top rack with the Project Olympus Rack Configuration, 2 Side-Panels, Front and Rear Doors. 32.43 kg (71.5 lb)
Notes:
  1. Frame width only. Additional inter frame spacing of 30 mm (1.2 in) is required.
  2. A top rack can optionally be installed on any HD2 frame. Side panels and PDUs are also optional. Each side panel adds 6.8 kg (15 lb). Each PDU adds 4.5 kg (10 lb).
  3. The weight with cartridges assumes a weight of .24 kg (0.5 lb) for a standard 3592 tape cartridge. The actual weight of the frame varies, depending on the configuration and cartridge capacity. Listed weights are plus or minus 2.3 kg (5 lb).
  4. Frames in position 1 (the leftmost frame in a library string) can have a maximum of 798 cartridges. Frames in positions 2+ can accommodate 1 000 cartridges.
  5. Side panels, front and rear doors, and PDUs are also optional. Each side panel adds 3.6 kg (8 lb). Each PDU adds 4.08 kg (9lb), Each door adds 3.2 kg ( 7 lb).