Supported power cords (PDU)
Plugs are shipped with the machine line cords as described in the
following table. Power plugs listed in Table 1 are approved for use with
specified models and meet the relevant test laboratory or country/test-house standards. The power
plug must be connected to a correctly wired and grounded receptacle. The customer is responsible for
receptacle wiring.
CAUTION:
A mismatch in the wiring configuration (delta versus wye) between the
IBM® product and your facility AC voltage supply can cause significant product damage. Ensure
that the PDUs of the product match the supply voltage and wiring configuration of your facility. If
the number of wires in the power cord does not match the wiring configuration in your facility, or
if the rated voltage on the product does not match the supply voltage in your facility, or if you
have any questions about the connection method, do not connect the product to the supply
voltage. Contact a certified electrician familiar with your installation, and IBM, for guidance.
(C054)
Feature
code Countries Voltage Amperage Phase Length Wall plug |
IBM system end | Customer end | Customer end (pin contacts) |
Customer facility's branch circuit
feed (Receptacle / Connector)8 |
IBM part number of cord9 |
---|---|---|---|---|---|
FC 7946 USA, Canada, CN, LA2 (except Argentina), & Japan –––– 415 V AC –––– 30 A –––– three phase (WYE) –––– 4.3 m (14 ft) –––– IEC-309 |
plug: Souriau UTG |
HBL530P6V02 | receptacle
type: HBL530R6V02 connector type: HBL530C6V02 |
03FM499 | |
FC 7947 World Trade 1 –––– 415 V AC –––– 32 A –––– three phase (WYE) –––– 4.3 m (14 ft) –––– Cut End |
plug: Souriau UTG |
Cut End3 | Cut End (lead labels) L1 L2 L3 N GND |
(not specified) | 03GN439 |
FC 7948 World Trade 1 –––– 415 V AC –––– 32 A, LSZH –––– three phase (WYE) –––– 4.3 m (14 ft) –––– Cut End –––– low smoke, halogen-free |
plug: Souriau UTG |
Cut End3 | Cut End (lead labels) L1 L2 L3 N GND |
(not specified) | 03FM501 |
FC 7971 USA, Canada, CN, LA2 (except Argentina), & Japan –––– 250 V AC –––– 60 A –––– three phase (Delta) –––– 4.3 m (14 ft) –––– IEC 60309 3P-4W |
plug:
Amphenol 02WN656 |
HBL460P9V05 | receptacle type: HBL460R9W connector type: HBL460C9W |
02WN658 | |
FC 7972 World Trade 1 –––– 250 V AC –––– 63 A –––– three phase (Delta) –––– 4.3 m (14 ft) –––– Cut End |
plug:
Amphenol 02WN656 |
Cut End3 | Cut End (lead labels) PH-1 PH-2 PH-3 GND |
(not specified) | 03NH386 |
FC 7973 World Trade 1 –––– 250 V AC –––– 63 A, LSZH –––– three phase (Delta) –––– 4.3 m (14 ft) –––– low smoke, halogen-free –––– Cut End |
plug:
Amphenol 02WN656 |
Cut End3 | Cut End (lead labels) PH-1 PH-2 PH-3 GND |
(not specified) | 03GN076 |
FC 7976 World Trade –––– 415 V AC –––– 32 A –––– three phase (WYE) –––– 4.3 m (14 ft) –––– IEC-309 |
plug: Souriau UTG |
IEC-309 530P6W | receptacle
type: 530R6W connector type: 530C6W |
03KY961 | |
FC 7977 World Trade –––– 250 V AC –––– 63 A –––– three phase –––– 4.3 m (14 ft) –––– IEC-309 |
plug:
Amphenol 02WN657 |
IEC-309 460P9W | receptacle type: 460R9W connector type: 460C9W |
03KY958 | |
FC 7979 World Trade1 –––– 415 V AC –––– 32 A –––– three phase (WYE) –––– 4.3 m (14 ft) –––– IEC-309 (low smoke, halogen-free) |
plug: Souriau UTG |
IEC-309 530P6W | receptacle
type: 530R6W connector type: 530C6W |
03KY962 | |
FC 7980 World Trade –––– 250 V AC –––– 63 A, LSZH –––– three phase –––– 4.3 m (14 ft) –––– IEC-309 (low smoke, halogen-free) |
plug:
Amphenol 02WN657 |
IEC-309 460P9W | receptacle type: 460R9W connector type: 460C9W |
03KY959 |
Notes:
- World Trade is all countries world-wide except USA, Canada, Mexico, and Japan.
- CN includes the following geographies: Anguilla, Antigua, Aruba,
Bahamas, Barbados, Bermuda, Bonaire, BVI Tortola, Cayman Islands, Curacao, Dominica, Dutch
Caribbean, Grenada, Guyana, Jamaica, Montserrat, St. Kitts & Nevis, St. Lucia, St. Martin NA,
St. Vincent, Suriname, Trinidad, Turks & Caicos.
LA includes the following geographies: Argentina, Belize, Bolivia, Brazil, Chile, Colombia, Costa Rica, Dominican Republic, Ecuador, El Salvador, Guatemala, Haiti, Honduras, Mexico, Nicaragua, Panama, Paraguay, Peru, Uruguay, Venezuela.
- Cut end cord; no plug is provided. Plug is provided by the customer and is electrician-installed. Cut end cords (FCs 7972, 7973, 7947, and 7948) are for special order only, are not offered for general availability.
- It is strongly recommended that you use a metal back box (example shown below) with our
line cords using IEC-60309 plugs. Although in-line connectors and nonmetallic back boxes are
available and compatible, they are not recommended. These recommendations are based on the metal
back box providing:
- An added level of protection against a mis-wired phase and ground reversal
- In some cases, a metal back box may be better for EMI mitigation
- The customer must obtain the appropriate plugs and receptacles, based on existing electrical codes, where those plugs and receptacles are not provided with the system. These customer-provided plugs and receptacles should be installed by qualified electricians.
- The power cord set(s) provided are for use only with this product.
- If you choose to use a Hubbell receptacle, do NOT use the Hubbell C-Series Light Industrial 3.
- If a receptacle is not available, then the connector that is listed should be used in its place.
- IBM part numbers are subject to change.