System power requirements

The rack mount requires the following estimated maximum system power:

Note: The power usage outlined in the following table assumes the maximum power features installed (I/O features, memory, etc.) and the maximum ambient temperature and altitude. Typical configurations and data center conditions will result in lower power consumption.
Table 1. System power requirements
# of CPC drawers # of PCIe+ I/O drawers
0 1 2 3
1 4.04 kW 5.46 kW 6.87 kW 8.28 kW
2 8.03 kW 9.44 kW 10.84 kW 12.28 kW
Important:
  • Systems with 1 CPC drawer can be either single phase or three phase PDU powered.
  • Systems with 2 CPC drawers must be three phase PDU powered.