Hardware Management Console physical specifications

This section contains information for the Hardware Management Console components applicable at the time of publication (determined by the edition notice at the front of this document). Specifications for your Hardware Management Console may differ from those presented below.

Note: All dimensions are considered nominal.
Notes for 2461 Rack Mount HMC (FC 0063):
  • When planning to use the rack mounted HMC (FC 0063), you must provide the rack where the HMC and 1U KMM (keyboard, monitor, mouse) are installed. It is recommended that you install the rack-mounted HMC below the KMM in the customer-provided rack.
  • For USA and Canada, the HMC (FC 0063) use two PDU plug positions for the two AC power supplies in the server. (Other power requirements are country dependent.)
  • Do not block any air vents; usually 15 cm (6 in) of space provides proper airflow.
  • Do not leave open spaces above or below an installed server in your rack cabinet. To help prevent damage to server components, always install a blank filler panel to cover the open space and to help ensure proper air circulation.
  • Install the server only in a rack cabinet with perforated doors.
  • Plan the device installation starting from the bottom of the rack cabinet.
  • Install the heaviest device in the bottom of the rack cabinet.
  • Do not extend more than one device out of the rack cabinet at the same time.
  • Connect the server to a properly grounded outlet.
  • Do not overload the power outlet when you install multiple devices in the rack cabinet.
  • For FC 0063, install the server in a rack that has a minimum depth of 28.25 in (720 mm) and maximum depth of 30 in (762 mm).
Table 1. 2461 Rack Mount Hardware Management Console (FC 0063) specifications
FC 0063 - 2461 Rack Mount Hardware Management Console system unit specifications
 
Dimensions
Height 4.45 cm (1.75 in)
Width 48.26 cm (19 in)
Depth 71.12 cm (28.0 in)
Weight maximum configuration 15.97 kg (35.2 lb)
Power consumption
Maximum power supply rating up to 900W
Working level 200W
Input Power1
Low range input voltage
90 Vrms - 137 Vrms (tolerance range)
100 V AC - 127 V AC (nominal range)
High range input voltage
180 Vrms - 265 Vrms (tolerance range)
200 V AC - 240 V AC (nominal range)
Input frequency range 47 - 63 Hz
Input kilovolt-amperes (kVA) (approximate)
Minimum configuration 0.134 kVA
Maximum configuration 0.988 kVA
Environmental
Server On
  Temperature 0° to 40° C (32° to 104° F)
  Humidity, non-condensing:
    Dew point -12° C (10.4° F)
    Relative humidity 5% - 90%
Storage (non-operating)
  Temperature -40° to 70° C (-40° to 158° F)
  Relative humidity 5% - 100%
  1. Power consumption and heat output vary with the number and type of optional features installed and the power-management optional features in use.
Notes for 2461 HMC Tower (FC 0062):
  • When installing the chassis, ensure that a minimum free air space is available around the system. The installation should have a minimum of 4 in - 6 in (101 mm -152 mm) behind the chassis and 7 in - 8 in (178 mm - 203 mm) in front of the chassis. Any front cabinet doors or access aisles must accommodate a 2461 HMC Tower (FC 0062) front chassis clearance of at least 7.0 in (178 mm) in order to provide proper clearance for the fan FRU. Ideally, a chassis clearance of 0.5 in - 1.5 in (13 mm -38 mm) above the system is desirable.
  • The 2461 HMC Tower (FC 0062) are designed with ruggedness in mind, however, precautions should be observed to ensure safe and reliable performance. Place the chassis on a flat, stable surface capable of supporting both the system weight and any anticipated peripherals. Installation area should be secure and free from danger of liquid or airborne contaminants that could damage internal components as well as supporting all airflow requirements.
  • To protect internal components from electrostatic damage, be sure to observe the following precautions when handling or storing the system:
    • The 2461 HMC Tower (FC 0062) has a net chassis weight of approximately 41.0 lbs. (18.59 kg). Use proper lifting techniques when moving and installing the system.
      C009
    • When removing or installing boards and sub-components, keep these components in their static-shielded bag and/or packaging until you are ready to for component installation.
    • Handle the sub-components by their edges.
    • Do not touch any sub-component I/O connector pins. Do not apply pressure or attach labels to the board-level subcomponents.
    • Use a personal grounding system, such as a wrist or heel strap(s) or ground yourself frequently by touching the metal chassis of the system before handling any subcomponents.
    • Ensure the systems external power source has a solid connection to an earth ground.
    • Use antistatic padding on all work surfaces when installing or removing subcomponents.
    • Avoid static-inducing carpeted areas.
Table 2. 2461 Hardware Management Console Tower (FC 0062) specifications
CPU: Environment: Electrical input:
  • 3.3 GHz Intel Xeon E3-1225 v5
  • 3.8 GHz Intel Xeon E3-1275 v6

    (Hardware Management Appliance only)

Memory:

  • Minimum: 32 GB (HMC), 64 GB (Hardware Management Appliance)
  • Maximum: 32 GB (HMC), 64 GB (Hardware Management Appliance)
  • Type: DDR4, ECC
  • Slots: 4
  • Supports: 32 GB (HMC), 64 GB (Hardware Management Appliance)

Hard drive:

  • 2 TB SATA hard drive

Video:

  • AST2500

Fans:

  • Two side-removable hot-swap fans

Power supply:

  • One 900-watt AC

Integrated function:

  • Six Intel l350 Ethernet ports
  • Two Intel l210 management Ethernet port
  • Eight USB ports (USB 2.0 and USB 3.0)

Operating:

  • Temperature: 0oC - 40oC
    (32oF - 104oF)
  • Altitude: 3050 m (~10,000 ft)
  • Relative humidity: 5% - 90% @ -12oC (10.4oF) dew point, non-condensing
Storage (non-operating):
  • Temperature: -40oC - 70oC
    (-40oF - 158oF)
  • Relative humidity: 5% - 100%

Air flow:

  • 350LFM continuous airflow

Size:

  • Height: 439.2 mm (17.29 in)
  • Depth: 492.25 mm (19.38 in)
  • Width: 215.9 mm (8.5 in)
  • Weight: approximately 18.59 kg (41.0 lb)
  • Sine-wave input (47-63 Hz) required
  • Input voltage low range:
    • 90 Vrms - 137 Vrms (tolerance range)
    • 100 V AC - 127 V AC (nominal range)
  • Input voltage high range:
    • 180 Vrms - 265 Vrms (tolerance range)
    • 200 V AC - 240 V AC (nominal range)
  • Input kilovolt-amperes (kVA), approximately:
    • Minimum: 0.134 kVA
    • Maximum: 0.988 kVA
Notes for 1U KMM (keyboard, monitor, mouse) console unit:

The 1U KMM (keyboard, monitor, mouse) console units include:

  • FC 0148 (for the 2461 HMC Tower unit)
  • FC 0154 (for the 2461 HMC Rack Mounted unit)
  • FC 0157 (for the 2461 TKE Tower unit)
  • FC 0156 (for the 2461 TKE Rack Mounted unit)
  • The following are recommendations for placement of the KMM unit into the customer supplied rack:
    • If you are standing when using the KMM unit, place the unit in EIU locations 21, 22, or 23.
    • If you are sitting when using the KMM unit, place the unit in EIU locations 12, 13, or 14.
    • For special accommodations, you need to make adjustments in the placement of the KMM unit in the rack that meet your needs.
  • For USA and Canada, the KMM unit uses one PDU plug position for the AC power supply in the KMM. (Other power requirements are country dependent.)
  • Elevated operating ambient - If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment might be greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by the manufacturer.
  • Reduced air flow - Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised.
  • Mechanical loading - Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading.
  • Circuit overloading - Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when addressing this concern.
  • Reliable earthing - Reliable earthing of rack-mounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit (for example, use of power strips).
Table 3. 1U KMM (keyboard, monitor, mouse) console unit specifications
1U KMM console unit specifications
(FC 0148 - 2461 HMC Tower unit)
(FC 0154 - 2461 HMC Rack Mounted unit)
(FC 0157 - 2461 TKE Tower unit)
(FC 0156 - 2461 TKE Rack Mounted unit)
Dimensions
Height 45 mm (1.75 in) (in stored position)
Width 440 mm (17.3 in) (main chassis only, slide-rails not included)
Depth 440 mm (17.3 in) (chassis only, bezel in front not included, cable-management arm not included)
Weight (11 lb) - Console Unit
(25 lb) - Console Option Kit
LCD panel
Size 17.3 inch diagonal
Display area (horizontal x vertical) 381.99 mm x 214.91 mm
Type TFT active matrix
Pixel pitch (horizontal x vertical) 0.1989 (H) x 0.1989 (V) mm
Input Power
Input voltage AC - 100-240 VAC - 1 A (nominal range)
Input frequency range 50-60 Hz
Power Consumption
Standard usage 9 watts
Maximum 11 watts
Power supply maximum 36 watts
Power saving < 1 watt (at 100 VAC and 240 VAC)
Environmental - Temperature
Operating 0° to 50° C (32° to 122° F)
Storage -20° to 60° C (-4° to 140° F)
Environmental - Humidity
Operating 20% to 90%
Storage 10% to 90%
Environmental - Altitude
Operating Maximum 5000 meters
Storage Maximum 5000 meters