IBM design recommendations
The
following list outlines IBM®'s basic design recommendations:
- Minimum of 10% spare fibers between distribution points for maintenance
- The use of physical-contact connectors
- Single Mode fiber installed for trunk cabling, if future need or long-distance links are foreseen
- A conduit system with interduct and pull-cords for future expansion
- Sufficient trunk fibers to accommodate short-term growth and migration.
Note: One way to determine the quantity of spare fiber for growth is to increase the planned
quantity by 30%. If the future applications are unknown, plan multimode so that loss does not exceed
5 dB at 1300 nm. This level of loss will accommodate all current applications and leave a margin for
future applications that may have more stringent attenuation requirements than those that are
currently available.