1140 UPS AC input power fault
Explanation
The UPS has reported that it has a problem with the input AC power.
User response
- Check the input AC power, whether it is missing or out of specification. Correct if necessary. Otherwise, exchange the FRU for a new FRU.
- Check node status. If all nodes show a status of
online
, mark the error that you have just repairedfixed
. If any nodes do not show a status ofonline
, start the fix procedure. If you return to this step, contact your support center to resolve the problem with the uninterruptible power supply. - Run the fix procedure from the event log menu in the GUI.
Possible Cause-FRUs or other:
- UPS input power cable (10%)
- Electronics assembly (10%)
Other:
- The input AC power is missing (40%)
- The input AC power is not in specification (40%)