Server specifications provide detailed information for
your server, including dimensions, electrical, power, temperature,
environment, and service clearances.
Use the following specifications to plan for your server.
The
5074, 5079, 507, or 5078 expansion unit is available with model
9406-820.
Table 1. Dimensions| Measurements |
Width |
Depth |
Height |
| Metric |
483 mm |
728 mm |
610 mm |
| English |
19.0 in. |
28.7 in. |
24.0 in. |
The maximum configuration weight is: 96 kg (210 lb)
Table 2. Electrical| Electrical characteristics |
Properties |
| kVA (maximum) |
0.862 |
| Rated voltage and frequency |
100-127/200-240 V ac at 50-60
plus or minus 0.5 Hz |
| Thermal output (maximum) |
2867 Btu/hr |
| Power requirements (maximum) |
840 W |
| Power factor |
0.95 |
| Inrush current |
90 A |
| Leakage current (maximum) |
3.5 mA |
| Phase |
1 |
Table 3. Temperature requirements| Operating |
Nonoperating |
| 10 - 38°C (50 - 100.4°F) |
1 - 60°C (33.8 - 140°F) |
Table 4. Environment requirements| Environment |
Operating |
Nonoperating |
| Noncondensing humidity |
8 - 80% |
8 - 80% |
| Wet bulb temperature |
22.8°C (73°F) |
27°C (80.6°F) |
| Maximum altitude |
3048m (10 000 ft) |
|
Table 5. Noise emissions1| Property |
Operating |
Idle |
| LWAd Category 2E, General Business |
6.1 bel |
5.9 bel |
| LpAm (1-meter bystander) |
43 dB |
40 dB |
Table 6. Service clearances| Front |
Back |
Sides2 |
Top2 |
| 762 mm |
762 mm |
762 mm |
762 mm |
| 30 in. |
30 in. |
30 in. |
30 in. |
Table 7. NotesNotes: - For a description of noise emission values, see Acoustics.
- Side and top clearances are optional during operation.
|