subscribe iconSubscribe to this information

Model 9406-820 server specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

model 9406-820

The 5074, 5079, 507, or 5078 expansion unit is available with model 9406-820.

Table 1. Dimensions
Measurements Width Depth Height
Metric 483 mm 728 mm 610 mm
English 19.0 in. 28.7 in. 24.0 in.

The maximum configuration weight is: 96 kg (210 lb)

Table 2. Electrical
Electrical characteristics Properties
kVA (maximum) 0.862
Rated voltage and frequency 100-127/200-240 V ac at 50-60 plus or minus 0.5 Hz
Thermal output (maximum) 2867 Btu/hr
Power requirements (maximum) 840 W
Power factor 0.95
Inrush current 90 A
Leakage current (maximum) 3.5 mA
Phase 1
Table 3. Temperature requirements
Operating  Nonoperating 
10 - 38°C (50 - 100.4°F) 1 - 60°C (33.8 - 140°F)
Table 4. Environment requirements
Environment Operating Nonoperating
Noncondensing humidity  8 - 80%  8 - 80% 
Wet bulb temperature 22.8°C (73°F) 27°C (80.6°F)
Maximum altitude  3048m (10 000 ft)   
Table 5. Noise emissions1
Property Operating Idle
LWAd Category 2E, General Business 6.1 bel 5.9 bel
LpAm (1-meter bystander) 43 dB 40 dB
Table 6. Service clearances
Front Back Sides2 Top2
762 mm 762 mm 762 mm 762 mm
30 in. 30 in. 30 in. 30 in.
Table 7. Notes
Notes:
  1. For a description of noise emission values, see Acoustics.
  2. Side and top clearances are optional during operation.