Server specifications provide detailed information for
your server, including dimensions, electrical, power, temperature,
environment, and service clearances.
Use the following specifications to plan for your server.
Pictured
is model 9406-250 server. The model 9406-250 allows the 7102 expansion
unit to be attached to one side.
Table 1. Dimensions| Measurements |
Width |
Width with 7101 or 7102 |
Depth |
Height |
| Metric |
340 mm |
550 mm |
662 mm |
610 mm |
| English |
13.4 in. |
21.7 in. |
26.1 in. |
24.0 in. |
Table 2. Maximum configuration
weight| Without 7101 or 7102 |
With 7101 or 7102 |
| 38.6 kg (85 lb) |
70.5 kg (155 lb) |
Table 3. Electrical| Electrical characteristics |
Without 7101 or 7102 |
With 7101 or 7102 |
| kVA (maximum) |
0.469 |
0.815 |
| Rated voltage and frequency1 |
100 - 127 200
- 240 V ac
at 50/60 plus or minus 0.5 Hz
|
| Thermal output (maximum) |
1536 Btu/hr |
2669 Btu/hr |
| Power requirements (IP measurement)
maximum |
450 |
782 |
| 1The
power supplies automatically accept any voltage with the published
rated voltage range. If dual power supplies are installed and operating,
the power supplies draw approximately equal current from the utility
(mains) and provide approximately equal current to the load. |
Table 4. Electrical| Electrical characteristics |
Properties |
| Power factor |
0.95 |
| Inrush current |
45 A |
| Leakage current (maximum) |
3.5 mA |
| Phase |
1 |
Table 5. Temperature requirements| Operating |
Nonoperating |
| 10 - 37.8°C (50 - 100°F) |
1 - 60°C (33.8 - 140°F) |
Table 6. Environment requirements| Environment |
Operating |
Nonoperating |
| Noncondensing humidity |
8 - 80% |
8 - 80% |
| Wet bulb temperature |
23°C (73.4 - °F) |
27°C (80.6 - °F) |
| Maximum altitude |
3048 m (10 000 ft) |
|
Table 7. Noise emissions Model
9406-250| |
Operating |
Idle |
| LWAd (Category 2E, General business) |
5.7 bels |
5.6 bels |
| LpAm (1-meter bystander) |
40 dB |
38 dB |
| For a description of
noise emission values, see Acoustics. |
Table 8. Noise emissions Model
9406-250 with 7101 or 71021 | |
Operating |
Idle |
| LWAd (Category 2E, General business) |
6.3 bels |
6.2 bels |
| LpAm (1-meter bystander) |
45 dB |
44 dB |
| For a description of
noise emission values, see Acoustics. |
Table 9. Service clearances| Front |
Back |
Sides |
Top |
| 762 mm |
762 mm |
762 mm |
762 mm |
| 30 in. |
30 in. |
30 in. |
30 in. |