ASHRAE declarations

Use the ASHRAE declarations table and figures to determine the measurement reporting requirements defined in the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) Thermal Guidelines for Data Processing Environments.

These guidelines are available at ASHRAE Technical Committee.

Table 1. ASHRAE declarations
  Typical Heat Release Airflow nominal1 Airflow maximum1 at 35°C (95°F)
Description watts cfm m3/hr cfm m3/hr
Minimum configuration 1500 410 697 580 985
Maximum configuration 14400 2060 2990 2560 373876
Typical configuration 6200 1010 1716 1300 2209
See Planning for 5792 base rack for Weight and Overall system dimension.
ASHRAE Class 3
Minimum configuration One I/O drawer
Maximum configuration 12 I/O drawers
Typical configuration 5 I/O drawers
Note:
  1. Airflow for the typical and minimum configurations do not include redundant power supply, feature code 5158.
Figure 1. Airflow figure for server mounted in a rack
Airflow figure for server mounted in a rack figure