Learn how to use HyperTerminal.
If you have not installed HyperTerminal, see Installing HyperTerminal.
To use HyperTerminal, complete the following steps:
- Click your path depending on your Windows® operating system.
- In the Connect To window, enter a name, select
an icon, and then click OK. A new Connect
To window is displayed.
- Click the little arrow at the end of the line for Connect
using:.
- Select the communications port being used for the console. It might also be listed as direct to COMn (where
n is 1 to 9).
- Click OK. A COMn Properties window
is displayed.
- Change the speed to 9600, and click OK. The HyperTerminal window opens. In the lower-left
corner, the status displays Connected and the
time is incrementing. In the data window you might see:
- No text
- Unintelligible text
- +++ATH0
Note: Failure to set the speed to 9600 results in all unintelligible
text and you will not be able to view the desired results.
- Select Disconnect.
- Select .
- In the Properties window for the connection you just created, click
the Settings tab.
- Click ASCII Setup.
- Select the following check boxes:
- Send line ends with line feeds
- Echo typed characters locally
- Append line feeds to incoming line ends
- Wrap lines that exceed terminal width
- Click OK, and then click OK again.
- Select Connect.
- At the server's control panel, enter a function 65 (you
must take the server to a known state). The server's control panel
might display D1008065 after a few minutes. Also, in the HyperTerminal window,
you might receive some data.
Note: You might need to enter a function 25 and 26 to
have access to the upper functions.
- At the server's control panel, enter a function 66. The panel might display D1008066. Also, in the HyperTerminal window,
you might receive some data.
- Using uppercase letters, type NEGOTIATE 1 in
the HyperTerminal window, and press Enter. The
HyperTerminal data window displays 115200.
Note: If nothing
is returned, repeat NEGOTIATE 1.
If a speed
value is returned, you had data exchanged in both directions and have full
connectivity. If Operations Console is not connecting, you most likely have
a setup problem on the client side.
If a speed value was not returned,
you might try powering off the PC, powering it back on, and repeating the
test. You might also attempt to connect the console again. In rare cases the
server might need to be restarted. For the best results, complete the following
steps in sequence:
- Power off the server.
- Power off the PC.
- Power on the PC.
- Start a connection for the console.
- Power on the server.
If the above procedure fails to solve your connection problem,
contact your service provider for further assistance.