subscribe iconSubscribe to this information

Model 7037-A50 server and 7047-185 workstation specifications

Server specifications provide detailed information for your server, including dimensions, electrical, power, temperature, environment, and service clearances.

Use the following specifications to plan for your server.

Table 1. Server or workstation specifications

Plan views

Rear view with connectors

ASHRAE declarations

Rack-mounted 7037-A50 server
Dimensions Width Depth Height EIA units1 Weight
Metric 429 mm 524 mm 218 mm 5 25 kg
English 16.9 in. 20.6 in. 8.6 in. 55 lb.
Stand-alone 7037-A50 server
Dimensions Width Depth Height Weight
Metric

216 mm

257 mm (including stabilizer foot)

496 mm (without rear cover

525 mm (with rear cover8)

469 mm 25 kg
English

8.5 in.

10.1 in. (including stabilizer foot)

19.5 in. (without rear cover)

20.7 in. (with rear cover8)

18.5 in. 55 lb.
Stand-alone 7047-185 workstation
Dimensions Width Depth Height Weight
Metric

216 mm

257 mm (including stabilizer foot)

640 mm (with acoustical cover)

469 mm 25 kg
English

8.5 in.

10.1 in. (including stabilizer foot)

25.2 in. (with acoustical cover)

18.5 in. 55 lb.
Shipping dimensions Width Depth Height Weight
Metric 625 mm 655 mm 485 mm 30 kg
English 24.6 in. 25.8 in. 19.1 in. 67 lb.
Shipping dimensions (China) Width Depth Height Weight
Metric 625 mm 655 mm 599 mm 30 kg
English 24.6 in. 25.8 in. 23.5 in. 67 lb.

Feature code for drawer mounted in rack

Electrical
kVA (maximum) 0.474
Rated voltage and frequency5 100 - 127/200 - 240 V ac at 50/60 plus or minus 0.5 Hz
Thermal output (maximum) 1536 BTU/hr
Maximum power consumption 530 W (1-way 7037-A50 , 1-way 7047-185, and 2-way 7047-185)
750 W (2-way 7037-A50 )
Power factor 0.95
Inrush current (maximum) 90 A
Leakage current (maximum) 1.6 mA
Phase 1
Compatible plug types 2, 4, 5, 6, 18, 19, 22, 23, 24, 25, 26, 32, 57, 59, 62, 66, 69, 70, 73, 75, 76
Branch circuit breaker 20 A (maximum)
Power cord length

2.8 m (9 ft.) - except United States

1.8 m (6 ft.) - United States

Environment requirements
Recommended operating temperature2 5 degrees to 35 degrees C (41 degrees to 95 degrees F)
Nonoperating temperature 5 degrees to 45 degrees C (41 degrees to 113 degrees F)
Shipping temperature -40 degrees to 60 degrees C (-40 degrees to 140 degrees F)
Operating Nonoperating
Maximum dew point 28 degrees C (82.4 degrees F) 29 degrees C (84.2 degrees F)
Noncondensing humidity 8 to 80% 8 to 80%
Maximum altitude 3048 m (10 000 ft.) 3048 m (10 000 ft.)
Noise emissions3, 4, 6, 7
Product description Declared A-weighted sound power level, LWAd (B) Declared A-weighted sound pressure level, LpAm (dB)
Operating Idling Operating Idling
7047-185 1-way workstation with two 10 000 rpm hard disk drives, 2843 graphics card and 2 GB of memory (workstations have acoustical front and rear covers) 5.0 4.7 314 284
7047-185 2-way workstation with two 10 000 rpm hard disk drives, 2843 graphics card and 4GB of memory (workstations have acoustical front and rear covers) 5.1 4.9 33 31
7037-A50 1-way server tower with three 10 000 rpm hard disk drives8 5.3 5.0 38 35
7037-A50 2-way server tower with three 10 000 rpm hard disk drives8 5.8 5.6 40 39
7037-A50 1-way rack-mounted server with three 10 000 rpm hard disk drives 5.3 5.0 384 354
7037-A50 2-way server tower or rack-mounted server with three 10 000 rpm hard disk drives and 4 GB of memory 5.7 5.6 42 41
Service clearances
Clearances Front Back Left or right Top
Operating 762 mm (30 in.) 762 mm (30 in.)  
Nonoperating 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.) 762 mm (30 in.)
Seismic considerations
Data communications
Electromagnetic compatibility compliance: This server meets the following electromagnetic compatibility specifications: FCC (CFR 47, Part 15); VCCI; CISPR-22; 89/336/EEC; BSMI (A2/NZS 3548:1995); C-Tick; ICES/NMB-003; Korean EMI/EMC (MIC Notice 2000–94, Notice 2000–72); People's Republic of China Commodity Inspection Law
Safety compliance: This server is designed and certified to meet the following safety standards: UL 60950; CAN/CSA C22.2 No. 60950–00; EN 60950; IEC 60950 including all National Differences
Note:
  1. See 0551, 0553, 7014, or 0555 rack configurations for typical configurations when the 0551, 0553, 7014, or 0555 rack is populated with various server models.
  2. Class 3 product as defined in ASHRAE Thermal Guidelines for Data Processing Environments. The allowable operating range is 5 degrees to 35 degrees C (41 degrees to 95 degrees F). See the Temperature and humidity design criteria topic for more information.
  3. For a description of noise emission values, see Acoustics.
  4. Estimated value
  5. The power supplies automatically accept any voltage with the published, rated-voltage range. If dual power supplies are installed and operating, the power supplies draw approximately equal current from the utility (mains) and provide approximately equal current to the load.
  6. When a tape drive is installed, using the acoustic cover feature will reduce the noise emissions when the tape drive is in use.
  7. All measurements made in conformance with ISO 7779 and declared in conformance with ISO 9296.
  8. An optional acoustical cover is available for the 7037-A50 server tower that will reduce LWAd and LpAm approximately 0.3 B and 3 dB, respectively.

Send feedback | Rate this page

Last updated: Fri, Oct 30, 2009