Electrical power requirements
Each system requires four separately protected power circuits, with four power drops for each system.
The power requirements for each circuit are listed in the following table.
Important: Ensure that the power supplied to the rack is uninterruptible.
Specification | EU | NA | AU/NZ |
---|---|---|---|
Circuits | 4 | ||
Total plugs (Drops) | 4 | ||
Voltage | 200 - 240 VAC, 50 Hz/60 Hz (Single Phase) | ||
Circuit Breaker Rating | 32 Amps (Single Phase) | 30 Amps (Single Phase) | 32 Amps (Single Phase) |
Connector | IEC 309 32A P+N+G
Hubbell 332C6 |
NEMA L6-30 2P+G
|
Clipsal 32A 2P+G
|
Power Drop Length | 8 ft (2.5 m) out top of rack
5 ft (1.5 m) out bottom of rack |
||
Maximum Power | 4,300 W | ||
Power/Area | 578 W/ft2
(6,218 W/m2) |