Electrical power requirements

Each system requires four separately protected power circuits, with four power drops for each system.

The power requirements for each circuit are listed in the following table.
Important: Ensure that the power supplied to the rack is uninterruptible.
Table 1. Model M4001-003 electrical requirements
Specification EU NA AU/NZ
Circuits 4
Total plugs (Drops) 4
Voltage 200 - 240 VAC, 50 Hz/60 Hz (Single Phase)
Circuit Breaker Rating 32 Amps (Single Phase) 30 Amps (Single Phase) 32 Amps (Single Phase)
Connector
IEC 309 32A P+N+G
Hubbell 332C6
NEMA L6-30 2P+G
Clipsal 32A 2P+G
Power Drop Length
8 ft (2.5 m) out top of rack
5 ft (1.5 m) out bottom of rack
Maximum Power 4,300 W
Power/Area
578 W/ft2
(6,218 W/m2)