Electrical power requirements
Each system requires six separately protected power circuits, with six power drops for each system (four drops for the compute rack and two drops for the storage rack).
The power requirements for each circuit are listed in
the following table.
Important: Ensure that the power supplied
to the rack is uninterruptible.
Specification | EU | NA | AU/NZ |
---|---|---|---|
Circuits | 6 | ||
Total plugs (Drops) | 6 | ||
Voltage | 200 - 240 VAC, 50 Hz/60 Hz (Single Phase) | ||
Circuit Breaker Rating | 32 Amps (Single Phase) | 30 Amps (Single Phase) | 32 Amps (Single Phase) |
Connector | IEC 309 32A P+N+G
Hubbell 332C6 |
NEMA L6-30 2P+G
|
Clipsal 32A 2P+G
|
Power Drop Length | 8 ft (2.5 m) out top of rack
5 ft (1.5 m) out bottom of rack |
||
Maximum Power | 6,200 W | ||
Power/Area | 407 W/ft2
(4,381 W/m2) |