Power consumption specification for client-provided PDUs

The following power consumption information for IBM Fusion HCI components is provided as a planning aid for you to connect these components to PDUs that you provide.

Product kVA Amps Power Inlets Inlet Watts
9155-DB1 service node 0.259 1.29 2 C14 251
9155-D10 with 256GB RAM, no NVMe drives 0.555 2.77 2 C14 538
9155-D10 with 256GB RAM, 10x NVMe drives 0.709 3.55 2 C14 688
9155-D10 with 512GB server, no NVMe drives 0.575 2.88 2 C14 558
9155-D10 with 512GB server, 10x NVMe drives 0.730 3.65 2 C14 708
9155-D14 with 1024GB RAM, no NVMe drives 0.651 3.25 2 C14 631
9155-C14 with 1024GB RAM, 10x NVMe drives 0.805 4.03 2 C14 781
9155-C14 with 2048GB RAM, no NVMe drives 0.690 3.45 2 C14 669
9155-C14 with 2048GB RAM, 10x NVMe drives 0.844 4.22 2 C14 819
9155-TF5 pull out console 0.051 0.26 1 C14 36
9155-S04 1 GbE management switch 0.105 0.53 2 C14 100
9155-S05 200 GbE high-speed switch 0.263 1.32 2 C14 250