Power consumption specification for client-provided PDUs
The following power consumption information for IBM Fusion HCI components is provided as a planning aid for you to connect these components to PDUs that you provide.
Product | kVA | Amps | Power Inlets | Inlet | Watts |
---|---|---|---|---|---|
9155-DB1 service node | 0.259 | 1.29 | 2 | C14 | 251 |
9155-D10 with 256GB RAM, no NVMe drives | 0.555 | 2.77 | 2 | C14 | 538 |
9155-D10 with 256GB RAM, 10x NVMe drives | 0.709 | 3.55 | 2 | C14 | 688 |
9155-D10 with 512GB server, no NVMe drives | 0.575 | 2.88 | 2 | C14 | 558 |
9155-D10 with 512GB server, 10x NVMe drives | 0.730 | 3.65 | 2 | C14 | 708 |
9155-D14 with 1024GB RAM, no NVMe drives | 0.651 | 3.25 | 2 | C14 | 631 |
9155-C14 with 1024GB RAM, 10x NVMe drives | 0.805 | 4.03 | 2 | C14 | 781 |
9155-C14 with 2048GB RAM, no NVMe drives | 0.690 | 3.45 | 2 | C14 | 669 |
9155-C14 with 2048GB RAM, 10x NVMe drives | 0.844 | 4.22 | 2 | C14 | 819 |
9155-TF5 pull out console | 0.051 | 0.26 | 1 | C14 | 36 |
9155-S04 1 GbE management switch | 0.105 | 0.53 | 2 | C14 | 100 |
9155-S05 200 GbE high-speed switch | 0.263 | 1.32 | 2 | C14 | 250 |