Management node specifications
Use this information to view specific information about the Flex System Manager Types 7955, 8731, and 8734 management nodes.
Size:
- Height: 55.5 mm (2.18 in)
- Depth: 492.7 mm (19.37 in)
- Width: 215.5 mm (8.48 in)
- Maximum weight: 7.07 kg (15.6 lb)
Environment: The Flex System Manager Types 7955,
8731, and 8734 complies
with ASHRAE class A3 specifications.
- Power® on 1:
- Temperature: 5°C - 40°C (41°F - 104°F) 2
- Humidity, non-condensing: -12°C dew point (10.4°F) and 8% - 85% relative humidity 3,4
- Maximum dew point: 24°C (75°F)
- Maximum altitude: 3048 m (10,000 ft)
- Maximum rate of temperature change: 5°C/hr (41°F/hr ) 5
- Power off 6:
- Temperature: 5°C to 45°C (41°F - 113°F)
- Relative humidity: 8% - 85%
- Maximum dew point: 27°C (80.6°F)
- Storage (non-operating):
- Temperature: 1°C to 60°C (33.8°F - 140°F)
- Altitude: 3050 m (10,006 ft)
- Relative humidity: 5% - 80%
- Maximum dew point: 29°C (84.2°F)
- Shipment (non-operating) 7:
- Temperature: -40°C to 60°C (-40°F - 140°F)
- Altitude: 10,700 m (35,105 ft)
- Relative humidity: 5% - 100%
- Maximum dew point: 29°C (84.2°F) 8
- Particulate contaminationAttention: Airborne particulates and reactive gases acting alone or in combination with other environmental factors such as humidity or temperature might pose a risk to the management node. For information about the limits for particulates and gases, see Particulate contamination.
- Chassis is powered on.
- A3 - Derate maximum allowable temperature 1°C/175 m above 950 m.
- The minimum humidity level for class A3 is the higher (more moisture) of the -12 °C dew point and the 8% relative humidity. These intersect at approximately 25°C. Below this intersection (~25C) the dew point (-12 °C) represents the minimum moisture level, while above it relative humidity (8%) is the minimum.
- Moisture levels lower than 0.5°C DP, but not lower -10 °C DP or
8% relative humidity, can be accepted if appropriate control measures
are implemented to limit the generation of static electricity on personnel
and equipment in the data center. All personnel and mobile furnishings
and equipment must be connected to ground via an appropriate static
control system. The following items are considered the minimum requirements:
- Conductive materials (conductive flooring, conductive footwear on all personnel that go into the datacenter, all mobile furnishings and equipment will be made of conductive or static dissipative materials).
- During maintenance on any hardware, a properly functioning wrist strap must be used by any personnel who contacts IT equipment.
- 5°C/hr for data centers employing tape drives and 20°C/hr for data centers employing disk drives.
- Chassis is removed from original shipping container and is installed but not in use, for example, during repair, maintenance, or upgrade.
- The equipment acclimation period is 1 hour per 20 °C of temperature change from the shipping environment to the operating environment.
- Condensation is acceptable, but not rain.