Installing the cable-management arms
The cable-management arms (CMA) are used to efficiently route the cables so that you can pull the enclosure out to change a fan module without needing to unplug any cables. Use the procedure to install the CMA.
About this task
To install the cable-management arms, complete the following steps.
Procedure
What to do next
Important: When
fitting cables into the CMA, ensure the following:
As you cable the control enclosure, route each cable through the CMAs, as shown in Figure 2.- Signal cables are secured to the canisters by their connector latches.
- Power cables are secured to the power‑supply handles by using the hook‑and‑loop tape as shown.
- The cable length along each CMA includes a minimum amount of slack.
- The enclosure can be extended forward into the service position without placing tension on the cables.
- Cables are retained in each arm by using the hook‑and‑loop tape as shown in the figure.
- Cables for the left canister use the left CMA, and cables for the right canister use the right CMA.