1097 PSU problem

Explanation

One of the power supply units in the node is reporting that no main power is detected.

For the SAN Volume Controller 2145-DH8, a power supply has a fault condition.

User response

  1. For the SAN Volume Controller 2145-DH8, replace the power supply FRU.

    For all other models, complete the following steps.

  2. Ensure that the power supply is attached correctly to both the node and to the UPS.
  3. If the error is not automatically marked fixed after 2 minutes, note the status of the three LEDs on the back of the power supply.
  4. If the power supply error LED is off and the AC and DC power LEDs are both on, this state is the normal condition. If the error is not automatically fixed after 2 minutes, replace the system board.
  5. Follow the action that is specified for the LED states that are noted in the following list.
  6. If the error is not automatically fixed after 2 minutes, contact support.
  7. Run the fix procedure from the event log menu in the GUI.

Possible Cause-FRUs or other:

  • Power cable assembly (85%)
  • UPS-1U assembly (10%)
  • System board (5%)
  • For the SAN Volume Controller 2145-DH8: power supply (100%)