SAS expansion enclosure requirements
Before you install any 2U or 5U SAS expansion enclosure, your physical environment must meet certain requirements. These requirements include verifying that adequate space is available and power and environmental conditions are met.
Power requirements for each power supply (two per enclosure)
Ensure that your environment meets the following power requirements.
To aid in power and cooling requirements planning, Table 1 lists the rating of each power supply unit (PSU) by enclosure.
The power that is used by the system depends on several factors, including the number of enclosures and drives in the system and the ambient temperature.
Model and type | PSU | Input power requirements | Maximum input current | Maximum power output | Caloric value (BTU/hr) |
---|---|---|---|---|---|
4657-12G, or 4657-24G | 764 W (2) |
100 V to 240 V single phase AC at a frequency of 50 Hz to 60 Hz |
10A for 100 V 6A for 240 V |
764 W | 2607 |
4657-92G | 2400 W (2) | AC 200 - 240 V~ nominal; +/- 10% tolerant)
50/60 Hz (nominal; 47 - 63 Hz tolerant) |
12 A (x2 - per inlet redundancy) Requires an IEC C20 appliance coupler (16-20A branch circuit or C19 power socket PDU) |
2400 W | 8189 |
The power and thermal measurements that are shown in Table 2 were obtained in the specific operating environment and under the conditions described. These measurements are presented as an illustration; measurements that are obtained in other operating environments might vary. Conduct your own testing to determine specific measurements for your environment.
Model and type | Configuration | Total power consumption |
---|---|---|
4657-12G, or 4657-24G | One enclosure with 24 2.5-inch flash drives | 151 W |
4657-12G, or 4657-24G | One enclosure with 24 10 K SAS drives | 175 W |
4657-12G, or 4657-24G | One enclosure with 24 15 K SAS drives | 234 W |
4657-12G, or 4657-24G | One enclosure with 12 7.2 K nearline SAS drives | 158 W |
4657-92G | One enclosure with 92 10 TB nearline SAS drives | 848 W |
4657-92G | One enclosure with 92 15 TB tier 1 flash drives | 748 W |
Each SAS expansion enclosure contains four PSUs for redundancy. The total power consumption values represent the total power that is drawn by all the PSUs.
Environmental requirements
Environment | Ambient temperature | Altitude | Relative humidity | Maximum wet bulb temperature |
---|---|---|---|---|
Operating | 5°C to 35°C (5°C to 40°C for 24 drives) 41°F to 95°F (41°F to 104°F for 24 drives) |
0 - 2133 m(0 - 7000 ft) | 8% to 80% noncondensing | 23°C (73°F) |
5°C to 30°C (41°F to 86°F) | 2134 - 3048 m (7001 - 10000 ft) | |||
Non-operating | 1°C to 50°C (34°F to 122°F) | -305 to 12192 m (-1000 to 40000 ft) | 8% to 80% noncondensing | 27°C (80°F) |
Storage | 1°C to 60°C (34°F to 140°F) | 5% to 80% noncondensing | 29°C (84°F) | |
Shipping | -40°C to 60°C (-40°F to 140°F) | 5% to 100% condensing, but not precipitating |
Dimensions and weight requirements for rack installation
Ensure that space is available in a standard 19" rack that can support the enclosure. The rack rail kits support racks with either threaded round or square mounting holes in the rail. The following table lists the dimensions and weights of the expansion enclosures.
Enclosure | Height | Width | Depth | Maximum weight | |
---|---|---|---|---|---|
Drive ready (without drives) | Fully configured (with drives) | ||||
4657-12G, or 4657-24G | 87 mm (3.46 in.) | 483 mm (19.0 in.) | 556 mm (21.9 in.) | 16.7 kg (36.8 lb) | 25.0 kg (55.1 lb) |
4657-92G | 222.2 mm (8.75 in.) | 483 mm (19.0 in.) | 968 mm (38.1 in.) | 67 kg (147.7 lb) | 135 kg (297 lb) |
- When you power off a 92F, 92G, or an A9F 5U expansion enclosure because you intend to transport it to another location.
- When you intend to move a rack that contains a 92F, 92G, or an A9F 5U expansion enclosure.

Enclosure | Minimum rail length | Maximum rail depth |
---|---|---|
4657-12G, or 4657-24G | 595 mm (23.4 in.) | 795 mm (31.3 in.) |
4657-92G | 680 mm (26.8 in.) | 800 mm (31.5 in.) |
Extra rack space requirements
Ensure that these additional space requirements, as shown in Table 6, are available around the enclosures.
Location | Space requirements | Reason |
---|---|---|
Left and right sides | 50 mm (2 in.) | Cooling air flow |
Back | Minimum of 100 mm (4 in.). This space is not needed for 5U expansion enclosure models. | Cable exit |
Supported drives for SAS expansion enclosures
Table 7 provides drive specifications for SAS expansion enclosures.
All drives are dual-port and hot-swappable. Drives of the same form factor and connector type can be intermixed within an enclosure.
Model and type | 3.5-inch drives | 2.5-inch drives |
---|---|---|
4657-12G, or 4657-24G | - |
|
4657-92G | N/A |
|
Acoustical specifications for SAS expansion enclosures
The following table provides the acoustical specifications for the 4657-24G SAS expansion enclosures.
Model and type | Acoustical output per enclosure |
---|---|
4657-24G | Less than 6.3 B LwA - Operating (40% Average seek rate) @ 23°C ambient |
The noise emission level that is stated is the declared (upper limit) sound power level, in decibels, for a random sample of machines. All measurements are made in accordance with ISO 7779 and reported in conformance with ISO 9296.
Model and type | Declared A-Weighted Sound Power Level, LWAd (B) | Declared A-Weighted Sound Pressure Level, LpAm (dB) | ||
---|---|---|---|---|
Operating | Idling | Operating | Idling | |
Fully configured expansion enclosure, MTM / Model 4657-92G | 8.5 | 8.5 | 85 | 85 |
Notes:
Important: Government regulations (such as those regulations that are prescribed by OSHA
or European Community Directives) can govern noise level exposure in the workplace and can apply to
you and your server installation. This system is available with an optional acoustical door feature
that can help reduce the noise that is emitted from this system. The actual sound pressure levels in
your installation depend upon various factors. These factors include the number of racks in the
installation. Other factors include the size, materials, and configuration of the room where you
designate the racks to be installed. Other factors include the noise levels from other equipment,
the room ambient temperature, and the employee's location in relation to the equipment. Further,
compliance with such government regulations also depends upon various other factors, including the
duration of employees' exposure and whether employees wear hearing protection. IBM® recommends that you seek qualified expert opinion in this field to determine
whether you are in compliance with the applicable regulations.
|
Shock and vibration specifications for SAS expansion enclosures
Table 10 and Table 11 provide the shock and vibration testing results for SAS expansion enclosures.
Shock categories | Test level | Performance |
---|---|---|
Operational | 5 g 10 ms 1/2 Sine | <=25 g 10 ms |
Non-operational | 30 g 10 ms 1/2 Sine | <=75 g 11 ms |
Vibration categories | Test level | Performance |
---|---|---|
Operational | 0.21 Grms 5 - 500 Hz Random | Throughput loss <=10% FCAL <= 0.68 Grms |
Non-operational | 1.04 Grms 2 - 200 Hz Random | <=3.12 Grms |
Shipping | 0.3 Grms 2 - 200 Hz Sine | <=5 Grms |
Rotational vibration | Normal operation performance measurements in enclosure with no external vibration. | Throughput loss for all drives of the same type within performance profile. |