To provide system
management connectivity for your system, you must connect Ethernet cables to at least Ethernet port
3 of each node canister in the control enclosure.
Procedure
To install the Ethernet cables, complete the following steps.
Connect Ethernet port 3 of both node canisters to the IP network that provides connection to
the system management interfaces, as shown in Figure 1 .
If there is more than one control enclosure is present in the system, ensure port 3 of every
node canister is connected to the same network to provide access if the configuration node
fails.Figure 1. Ethernet ports on a canister
5 Node canister technician port - do not use for Ethernet
connections.
Optionally, connect Ethernet port 1 of each node canister in the system to a second IP network
that will provide redundant connection to the system management interfaces.
If there is more than one control enclosure in the system, ensure that port 1 of every node
canister is connected to the same network to provide access if the configuration node fails.