Input voltage requirements
When you plan for the power requirements of the storage system, consider the input voltage requirements.
The following table provides the input voltages and frequencies that the storage system supports.
| Characteristic | Voltage (single-phase) |
|---|---|
| Nominal input voltages | 200-240 RMS V AC |
| Minimum tolerated input voltage | 180 RMS V AC |
| Maximum tolerated input voltage | 256 RMS V AC |
| System maximum current rating | DS8886 40 Amps |
| DS8884 24 Amps | |
| Wall breaker rating (1 ph)1 | DS8886 US, Canada, and regions that require 20% derating factor 50 - 63 Amps |
| DS8886 Geos with no derating requirement 40 - 63 Amps | |
| DS8884 All regions 30 - 63 Amps | |
| Steady-state input frequencies | 50 ± 3 or 60 ± 3.0 Hz |
| PLD input frequencies (<10 seconds) | 50 ± 3 or 60 ± 3.0 Hz |
|
|
| Characteristic | Three-phase delta (3ØΔ) | Three-phase wye (3ØY: LL[Line-to-Line]) |
|---|---|---|
| Nominal input voltages | 200, 208, 220, or 240 RMS V AC | 380, 400, or 415 RMS V AC |
| Minimum tolerated input voltage | 180 RMS V AC | 315 RMS V AC |
| Maximum tolerated input voltage | 256 RMS V AC | 456 RMS V AC |
| System maximum current rating | 30 Amps for Japan 24 Amps for other regions |
17 Amps |
| Wall breaker rating (3 ph)1 | 30 - 60 Amps | 20 - 32 Amps |
| Steady-state input frequencies | 50 ± 3 or 60 ± 3.0 Hz | 50 ± 3 or 60 ± 3.0 Hz |
| PLD input frequencies (<10 seconds) | 50 ± 3 or 60 ± 3.0 Hz | 50 ± 3 or 60 ± 3.0 Hz |
|
||