Plan for the operating ranges and recommended operating
points of the storage system.
Table 1 provides
the operating ranges for your storage system when its power is on.
Table 1. Operating extremes with the power on
Measurement |
Value |
Altitude |
0 - 2133 m (0 - 7000 ft) |
Dry bulb temperature |
16 - 32°C (60 - 90°F) |
Relative humidity |
20 - 80% |
Wet bulb temperature (maximum) |
23°C (73°F) |
Table 2 provides
the optimum operating points for your storage system with its power
on.
Table 2. Optimum operating points
with the power on
Measurement |
Value |
Temperature |
22°C (72°F) |
Relative humidity |
45% |
Table 3 provides
the operating ranges for a storage system with power on.
Table 3. Optimum operating ranges with power
on
Measurement |
Value |
Temperature |
16 - 32°C (60 - 90°F) |
Relative humidity |
40 - 50% |