Power cords and receptacles
The IBM® Diamondback tape library receives a single-phase (200–240 V ac) power on its own power cord from a customer-supplied outlet or from an optional power distribution unit (PDU).
Power cords
Refer to Figure 1 and match the number that is beside each receptacle to the receptacle number listed in the table.
Length and type of power cord | Part number and feature code* | Type of service receptacle |
---|---|---|
Dual 4.3 m (14 ft.) watertight, international 250 V ac, 16 A single phase. This power cord is for countries other than the United States, Canada, and Mexico. | 45E2699 / 9970 | IEC-309 2P +GND 16 A Uses receptacle #2 |
Dual 4.3 m (14 ft.) watertight, 250 V ac, 20 A single phase. This power cord is for the United States, Canada, and Mexico. | 23R9540 / 9970 | Hubbell HBL320R6W, IEC-309 2P +GND 20 A
Uses receptacle #2 |
Dual 4.3 m (14 ft.) non-watertight, twistlock 250 V ac, 15 A. This power cord is for the United States and Canada. | 39M5114 / 9972 | NEMA L6-15R Uses receptacle #1 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 10 A, IRAM 2073. This power cord is for Argentina. | 39M5066 / 9976 | Uses receptacle #3 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 15 A, Earth Pin InMetro NBR 14136. This power cord is for Brazil. | 02WN892 / 9977 | Uses receptacle #4 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 10 A, AS/NZS 3112/2000. This power cord is for Australia and New Zealand. | 39M5100 / 9978 | Uses receptacle #3 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 15 A, JIS C8303, C8306. This power cord is for Japan. | 39M5184 / 9979 | Uses receptacle #5 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 10 A, GB 2099.1, 1002. This power cord is for China. | 39M5204 / 9980 | Uses receptacle #3 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 15 A, with earth pin KS C8305, K60884-1. This power cord is for Korea. | 39M5217 / 9981 | Uses receptacle #6 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 10 A, CNS 10917-3. This power cord is for Taiwan. | 39M5252 / 9982 | Uses receptacle #5 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 16 A, SANS 164-1. This power cord is for South Africa. | 39M5142 / 9983 | Uses receptacle #7 |
Dual 4.3 m (14 ft.) 250 V ac, 15A, single phase power cord, non-watertight twistlock 20A receptacles. This power cord is for US and Canada. | 23R9760 / 9984 | NEMA L6-20R Uses receptacle #8 |
Dual 4.3 m (14 ft.) 250 V ac, 15A, single phase power cord, watertight 15A plugs. This power cord is for US and Canada. | 12X4116 / 9985 | Russellstoll 3743U2 or 9R23U2W receptacles, or
Russellstoll 3913U2 or 9C23U2 connectors Uses receptacle #9 |
Dual 4.3 m (14 ft.) non-watertight, 250 V ac, 10A, single phase power cord with IEC 60320 C14 connector. This power cord can be used worldwide to connect to spare outlets on FC 1852, 1853 PDUs. It can be used in an adjacent library frame or to a customer-provided PDU that is mounted external to the library frames. | 46X7337 / 9989 | IEC 60320 C13 Uses receptacle #13 |
Dual† 4.3 m (14 ft.) power cords with IEC-309 3p+n+g 32A plug, 240-415V ac 3 phase (WYE). This power cord is used in Europe, the Middle East, and Africa. It may be used in US and Canada where permitted by local authority having jurisdiction (AHJ). | 39M5413 / 9948 (Used with FC 1853 only; not compatible with FC 1852) |
IEC-309 3p+n+g 32A Uses receptacle #14 |
Single 2.8 m (9.2 ft.) non-watertight, 250 V ac, 10A single phase power cord with IEC 60320 C20 connector. This power cord can be used worldwide to connect internal library loads with C14 inlet connectors to spare C19 outlets on FC 1752 or 1952 PDUs. Any connected load must not exceed 10A. | 39M5392 / 9949 (Used with FC 1853 only; not compatible with FC 1852) |
IEC 60320 C19 (provided on FC 1853) |
Dual† 4.3 m (14 ft.) power cords with NEMA L6-30P non-watertight 30A plug, 200–240 V ac, 30 Amps, single phase. This power cord is for US, Canada, Latin America, and Japan. | 39M5416 / 9954 (Used with FC 1751, 1752, 1951, or 1952 only) |
NEMA L6-30R Uses receptacle #10 |
Dual† 4.3 m (14 ft.) power cords with watertight Russellstoll 3750DP 30A plug, 200–240 V ac, 30 Amps, single phase. This power cord is used in US, Chicago, Canada, Latin America, and Japan. | 39M5418 / 9955 (Used with FC 1751, 1752, 1951, or 1952 only) |
Russellstoll 3753 or 9R33UOW receptacle, or a
Russellstoll 3933 or 9C33UO connector Uses receptacle #11 |
Dual† 4.3 m (14 ft.) power cords with IEC-309 p+n+g 30A plug, 200–240 V ac single phase. This power cord is used in US, Canada, and Mexico. | 03JJ281 / 9956 (Used with FC 1751, 1752, 1951, or 1952 only) |
IEC-309 p+n+g 30A/32A Uses 30A/32A version of receptacle #2 |
Dual† 4.3 m (14 ft.) power cords with IEC-309 p+n+g 32A plug, 200–240 V ac single phase. This power cord is used for countries other than US, Canada, and Mexico. | 39M5414 / 9956 (Used with FC 1751, 1752, 1951, or 1952 only) |
IEC-309 p+n+g 32A Uses 32A version of receptacle #2 |
Dual† 4.3 m (14 ft.) power cords with PDL 56P332 32A plug, 200–240 V ac single phase, 32 Amps. This power cord is used in Australia and New Zealand. | 39M5419 / 9957 (Used with FC 1751, 1752, 1951, or 1952 only) |
1-gang, 3-pin 32A socket, PDL 56SO332 or
equivalent Uses receptacle #12 |
Dual† 4.3 m (14 ft.) non-watertight power cords with 30A plug type Shin Ju SJ-3302, 200–240 V ac, 30 Amps. This power cord is used in North and South Korea. | 39M5420 / 9958 (Used with FC 1751, 1752, 1951, or 1952 only) |
200–250 V ac single phase Uses receptacle #3 |
Dual† 4.3 m (14 ft.) power cords, unterminated (without a power plug), 200–240 V ac single phase, 30 Amps maximum, with IRAM and BSMI agency certifications. Wire size 4 mm. This is the recommended cord for Argentina, Taiwan, Europe, the Middle East, and Africa if an unterminated power cord is preferred. | 23R7324 / 9959 (Used with FC 1751 or 1951 only; not compatible with FC 1752 or 1952) |
Not specified (no plug supplied) |
Dual† 4.3 m (14 ft.) power cords, unterminated (without a power plug), 200–240 V ac single phase, 30 Amps maximum, with CCC certification. This is the recommended power cord for China. | 23R9543 / 9966 (Used with FC 1751 or 1951 only; not compatible with FC 1752 or 1952) |
Not specified (no plug supplied) |
Notes: * Except where noted, each feature code ships two power cords so that dual power is supported. † Only a single 99xx power cord is shipped with each 99xx feature ordered for installation into model TR1 (for use with PDU feature 1852). |
Power receptacles

Electrical characteristics
Library without PDUs | Library with FC 1951 | Library with FC 1952 and single phase power cord | Library with FC 1952 and 3-phase power cord FC 9948 |
---|---|---|---|
200 - 240 V AC, 8 A, 50 - 60 Hz, 1.6 kVA, single phase | 200 - 240 V AC, 24 A, 50 - 60 Hz, 4.8 kVA, single phase 2 | 200 - 240 V AC, 24 A, 50 - 60 Hz, 4.8 kVA, single phase 2 | 380 - 415 V AC, 20 A, 50 - 60 Hz, 4.8 kVA, 3-phase wye 2 |
Notes:
|
Recommended customer circuit breakers
Maximum rating | Minimum rating |
---|---|
20 A (32 A if FC 1852, or 1853 is installed) | 10 A (20 A if FC 1852, or 1853 is installed) |