Cooling module

The five cooling modules at the rear of the enclosure maintain all system components below their maximum temperature, assuming the ambient temperature is below 95° F (35°C).

The speed of the fans in the cooling modules is controlled by the SSB compute modules. For more information about the system airflow, see System airflow.

Cooling modules can be hot-swapped while the enclosure is still running, assuming that only one module is removed at a time and the swap takes no longer than 2 minutes. Ensure that you have a replacement cooling module before you remove the defective cooling module.

The following figure shows a cooling module.

Figure 1. Cooling module
Rendering of cooling module

System airflow

The system must be operated with low-pressure rear exhaust installation. Back pressure that is created by the rack doors and obstacles is not to exceed 5 pascals (0.5 mm water gauge). The cooling system provides sufficient capacity to ensure that maximum temperatures are not exceeded.

The minimum open area for the rack doors is 70%.

Cooling module LEDs

Cooling modules have LEDs for the module status and fan faults.

The following figure shows the LEDs for a cooling module.

Figure 2. Cooling module LEDs
Diagram shows the location of the two LEDs
Table 1. Cooling module LED states
Module OK (green) Fan fault (amber) Status
X Off Fan OK
X On Communication lost with fan module controller
X On Reported fan speed is out of tolerance
On X Module good (battery and fan)
X = disregard