Technical specifications
Enclosure dimensions, weights, operating temperature and humidity, and power cooling.
Enclosure dimensions
| Specification | Metric units | Imperial units |
|---|---|---|
| Height (including top cover) | 176.4 mm | 6.94 in |
| Width (excluding ears and rails) | 441.0 mm | 17.36 in |
| Depth (including handles, excluding cables) | 1,139.0 mm | 44.84 in |
Enclosure weights
| CRU/component | Metric units | Imperial units |
|---|---|---|
| Storage enclosure (empty) | 36.30 kg | 80.00 lb |
| Disk drive module (3.5" LFF disks) | 0.80 kg | 1.80 lb |
| Power Supply Unit (PSU) | 1.45 kg | 3.20 lb |
| System fan module | 0.70 kg | 1.50 lb |
| IOM | 0.80 kg | 1.80 lb |
| IOM fan module | 0.345 kg | 0.80 lb |
| HS expander module | 0.10 kg | 0.20 lb |
| Disk Enclosure (fully populated with 106 drives: maximum weight) |
145.60 kg | 321.00 lb |
- 1- Weights shown are nominal, and subject to variances. Disk drive module weights vary by type of disk used.
- 2 - Rail kit adds approximately 6.25 kg (14.9 lb) to the aggregate enclosure weight. The CMA adds 0.91 kg (2.0 lb) to aggregate enclosure weight.
- 3 - Weights may vary due to the number of disks and differing calibrations between scales.
Environmental requirements
| Specification | Temperature range | Relative humidity |
|---|---|---|
| Operating | 5º C to 35ºC (41º F to 95º F, de-rated by 1º C per 300m above 900m) (ASHRAE A2 2015 thermal guidelines) | -12º C DP/10 to 80% (Max) (Non-condensing) |
| Non-operating | -40º C to +70º C (-40º F to +158º F) (Max rate of change: 20º C) | -12º C DP/5 to 100% (Max) (Non-condensing) |
| Specification | Measurement/description |
|---|---|
| Airflow | System must be operated with low pressure rear exhaust installation. Back pressure created by rack doors and obstacles not to exceed 5 Pa (0.5 mm H2O) |
| Altitude, operating | -100 to 3,048 meters (0 to 10,000 feet). Maximum operating temperature is de-rated by 1º C for each 300 m above 900 m (2952.76 feet) |
| Altitude, non-operating | -100 to 12,192 m (-328 to 40,000 feet) |
| Shock, operating | 3.0 g, 11 ms (per axis) |
| Shock, non-operating | 20.0 g, 7 ms, 10 shock pulses (2 shocks per axis X, Y in positive and negative direction, and 2 shocks in positive Z axis) OR ISTA 3H (mounted in a rack, horizontal impact on all sides, 4-in drop tests) |
| Vibration, operating | 0.18 Grms 5Hz to 500 Hz, 30 min per axis |
| Vibration, non-operating | 0.54 Grms 6Hz to 200 Hz (ISTA 3E) |
| Vibration, relocation | ISTA3H air ride for 60 min |
| Acoustics | 4U enclosures: Sound power operating £ 8.5 Bels LWAd @23ºC |
Orientation and mounting:
|
1.2 m rack mount (4 EIA units)
|
Power supply unit specifications
| Specification | Measurement/description |
|---|---|
| Dimensions | 38.1 mm high x 169.9 mm wide x 211.1 mm long:
|
| Maximum output power | 2000 W |
| Voltage range | 200–240 VAC rated |
| Frequency | 50–60 Hz |
| Voltage range selection | Auto-ranging: 90–264 VAC, 47–63 Hz |
| Maximum inrush current | 55A |
| Power conversion efficiency | ³ 94% @ 230 VAC (50% load) |
| Harmonics | Meets EN61000-3-2 (EU), EN 31000-3-3 (EU), EN 55024 (EU), KN 24/KN 35 (S. Korea) |
| Output | +12V @ 164A, +12V Standby Voltage @3.5A |
| Hot pluggable | Yes |
| Switches and LEDs | AC power cable connect and one bi-tonal status indicator LED |
| Enclosure cooling | Four dual-impeller, counter rotating axial fans (enclosure rear-panel) Two single-impeller axial fans (controller bay) |