MTM 9568-CVM

System specifications for IBM® 9568-CVM (W4600) provide detailed information about physical dimensions, electrical data, and environmental requirements.

Dimensions

Table 1. Dimensions1
Width Depth Height Weight Capacity
23.6 in (600 mm) 47.2 in (1200 mm) Height: 79.5 in (2020 mm) 578 kg (1274 lbs) 42 EIA units
1 All W4600 models use 7965-S42 racks. For more information on the 7965-S42 system, see Model 7014-T42, 7014-B42, and 0553.

Electrical

Table 2. Maximum system power1
Electrical characteristics Properties (Minimum/Maximum)
Power consumption2

Min: 3.17 kW (with 2 compute nodes)

Max: 10.60 kW (with 22 compute nodes)

kVA

Min: 3.34 kVA (with 2 compute nodes)

Max: 11.16 kVA (with 22 compute nodes)

Thermal output

Min: 10.83 kBTU/hr (with 2 compute nodes)

Max: 36.18 kBTU/hr (with 22 compute nodes)

Power Distribution Unit (PDU) Qty3 6 (FC 7109)
Voltage 200 to 240 Vac
Frequency 50/60 Hz +/- 3 Hz
1 Power is supplied to one set of line cords only. See PDU Power Cords list.

2When planning the electrical system, it is important to use maximum values to account for internal or environmental conditions that result in power consumption increasing beyond typical values. However, when planning for heat load, you can use the typical value.

3Each system is shipped with a quantity of 6 PDUs. Only 2 quantities are used up to 96 cores, 4 quantities up to 256 cores, and 6 quantities up to 320 cores and for storage expansions

Note: Add 0.295 kW when adding an additional storage unit.

Environmental requirements

Table 3. Environmental requirements
Environment Recommended operating Allowable operating Non-operating
ASHRAE class   A2  
Airflow direction1   Front-to-back  
Temperature 18° to 27° C (64° to 80° F) 5° to 35° C (41° to 95°F) 5° to 45° C (41° to 113° F)
Humidity range 5.5C (42° F) dew point to 60% RH and 15° C (59° F) dew point   8% to 80%
Maximum dew point 28° C (84° F)    
Maximum operating altitude   3050 m (10000 ft)  
1Nominal cubic feet per minute (CFM) is approximately 1110. Maximum CFM is approximately 2105.

Electromagnetic compatibility compliance

The electromagnetic compatibility compliance is: FCC Part 15 Class A, ICES-003, Class A, CISPR 32 Class A, VCCI-A, People's Republic of China commodity inspection law Class A, and KN 32, 35.

Product safety compliance

The product safety compliance is: UL 60950-1, CAN/CSA 60950-1-07, IEC 60950-1, EN 60950-1.

Delivery and subsequent transportation of the equipment

You must prepare your environment, with assistance from an authorized service provider, to accept the new product based on the installation planning information provided. In anticipation of the equipment delivery, prepare the final installation site in advance so that professional movers or riggers can transport the equipment to the final installation site within the computer room. If, for some reason, this is not possible at the time of delivery, you must make arrangements to have professional movers or riggers return to finish the transportation at a later date. Only professional movers or riggers should transport the equipment. The authorized service provider can only perform minimal frame repositioning within the computer room, as needed, to perform required service actions. You are also responsible for using professional movers or riggers when you relocate or dispose of equipment.