Installing the support rails for file module slides

Before installing the file module, you must install support rails in the rack.

Before you begin

Review the documentation that comes with the rack cabinet for safety and cabling information. Before you install the file module in a rack cabinet, review the following guidelines:
  • Two or more people are required to install devices 2U or larger in a rack cabinet.
  • Make sure that the room air temperature is below 35°C (95°F).
  • Do not block any air vents; usually 15 cm (6 inch) of space provides proper airflow.
  • Do not leave open spaces above or below an installed file module in the rack cabinet. To help prevent damage to file module components, always install a blank filler panel to cover the open space and to help ensure proper air circulation.
  • Install the file module only in a rack cabinet with perforated doors.
  • Plan the device installation starting from the bottom of the rack cabinet.
  • Install the heaviest device in the bottom of the rack cabinet.
  • Do not extend more than one device out of the rack cabinet at the same time.
  • Remove the rack doors and side panels to provide easier access during installation.
  • Do not overload the power outlet when you install multiple devices in the rack cabinet.
  • Install the file module in a rack that meets the following requirements:
    • Minimum depth of 70 mm (2.76 inch) between the front mounting flange and inside of the front door.
    • Minimum depth of 157 mm (6.18 inch) between the rear mounting flange and inside of the rear door.
    • Minimum depth of 718 mm (28.27 inch) and maximum depth of 762 mm (30 inch) between the front and rear mounting flanges to support the use of the cable management arm.
    Note: The maximum distance between the front and the rear EIA rails of the rack is 810 mm (31.9 inch). Also, cage nuts and clip nuts are not required to install the file module in a rack cabinet.
  • Install the cable management arm on either side of the file module. These instructions are shown with the cable management arm mounted on the left side. The installation instructions in this document can be reversed if you are installing the cable management arm on the side of the file module not shown.

Figure 1 shows the items that you need to install the file module in the rack cabinet. If any items are missing or damaged, contact your place of purchase. The contents from the slide rail box and the cable management arm box are necessary for this installation.

Figure 1. Cable management arm box contents
Cable management arm box contents
  •  1  Cable-management support bar
  •  2  Cable-management arm assembly
  •  3  Cable-management stop bracket

Figure 2 shows the friction rail box contents.

Figure 2. Friction rail box contents
Friction rail box contents

Procedure

To install the support rails, complete the following steps.

  1. If the slide rails in your rack installation kit came with shipping thumbscrews, remove them.
  2. Select an available 2U space in the rack to install the file modules. Refer to Figure 3.
    Figure 3. Locate a 2U space in the lower section of the rack.
    Locate a 2U space in the lower section of the rack.
  3. Each slide rail is marked with either an R (right) or an L (left). Select one of the slide rails and pull the rear bracket all the way back. If a thumbscrew is installed in the slide rail, remove it. Refer to Figure 4.
    Figure 4. Opening the rear slide rail hooks
    Opening the rear slide-rail hooks
    Note: If you are installing the slide rails into a 1U space with devices already installed directly above and below this 1U space, you need to extend the slide rails to slide the rear of the slide rails into the rear of the rack. When installing a 2U device, be sure to install the slide rails in the bottom positon of the 2U area in the rack.
  4. From the front of the rack, line up the two pins on the rear of the slide rail in the selected unit on the rear of the rack. Push the rails so that the pins go into the holes and slide the rails into the rack to lock the rear of the slide rails into the rack. Refer to Figure 5.
    Figure 5. Installing the rear end of the slide rails
    Installing rear end of slide rail
  5. Push the blue button to allow the latch to slide forward, as shown in Figure 6.
    Figure 6. Install the rear end of the slide rails
    Install the rear end of the slide rails
  6. Pull the slide rail forward and locate the front latch in the appropriate unit space in front of the rack EIA rail. Adjust the length of the rail.
  7. Press the blue button to release the bracket. Push the front latch in all the way. Make sure the latch is fully engaged. Refer to Figure 7.
  8. Repeat this procedure to install the other rail into the rack Make sure that each front latch is fully engaged.
    Figure 7. Install the front end of the slide rails.
    Install the front end of the slide rails.