Electrical power requirements
Each system requires thirty-two separately protected power circuits, with four power drops for each rack (thirty-two drops per system).
The power requirements for each circuit are listed in
the following table.
Important: Ensure that the power supplied
to the rack is uninterruptible.
| Specification | EU | NA | AU/NZ |
|---|---|---|---|
| Circuits | 32 | ||
| Total plugs (Drops) | 32 | ||
| Voltage | 200 - 240 VAC, 50 Hz/60 Hz (Single Phase) | ||
| Circuit Breaker Rating | 32 Amps (Single Phase) | 30 Amps (Single Phase) | 32 Amps (Single Phase) |
| Connector | IEC 309 32A P+N+G
Hubbell 332C6 ![]() |
NEMA L6-30 2P+G
![]() |
Clipsal 32A 2P+G
![]() |
| Power Drop Length | 8 ft (2.5 m) out top of rack
5 ft (1.5 m) out bottom of rack |
||
| Maximum Power | 54,800 W | ||
| Power/Area | 900 W/ft2
(9,680 W/m2) |
||