One or more processor sensors detected an over temperature condition.
About this task
To resolve the over temperature condition, complete the following steps:
Procedure
-
Is the room temperature less than 35°C (95°F)?
| If |
Then |
| No: |
Bring the room temperature to within the allowable operating range. This ends the
procedure. |
| Yes: |
Continue with the next step. |
-
Are the system front and rear doors free of obstructions?
| If |
Then |
| No: |
The system must be free of obstructions for proper air flow. Remove any obstructions.
This ends the procedure. |
| Yes: |
Continue with the next step. |
-
Perform the service action that is indicated for any system event logs that are related to fans
and occurred prior to the problem that you are working on. Go to Identifying a service action by using FQPSPxxxxxxx events and system event logs. This ends the procedure.